| Plan Review Stops For Permit 05060746 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-10-20 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-10-20 |
Time |
11:43 |
Rev Time |
0.33 |
| Received By |
alange |
Date |
2005-10-20 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2005-10-20 00:00:00 | INSULATION REVISION OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-07-11 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-07-11 |
Time |
10:40 |
Rev Time |
0.33 |
| Received By |
alange |
Date |
2005-07-11 |
Time |
10:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-06-27 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-06-27 |
Time |
09:45 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2005-06-27 |
Time |
09:44 |
Sent To |
E |
|
| Notes |
| 2005-06-27 00:00:00 | DENIED | | | | | | 1.THE ARCHITECTS FIRM LICENSE NUMBER | | | IS REQUIRED ON THE TITLE BLOCK PER | | | 61G1-16.004 FAC. | | | ARCHITECTS SEAL AND SIGNATURE IS | | | REQUIRED FBC 104.2.2 | | | | | | ANY QUESTIONS CALL ME | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-08-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-08-11 |
Time |
11:29 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-08-11 |
Time |
11:20 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-07-07 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-07-07 |
Time |
12:15 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-07-07 |
Time |
12:09 |
Sent To |
B |
|
| Notes |
| 2005-07-07 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | COMMENTS FROM PREVIOUS REVIEW. | | | | | | 2} THERE MUST BE 2 APPLIANCE CIRCUITS ON | | | THE PANEL SCHEDULE PER 220.16. SHOW | | | SAME. | | | | | | 3} SHOW LOCATION OF THE CONDENSING UNIT | | | AND DISCONNECT PER 440.14. ALSO SERVICE | | | RECEPTACLE LOCATION PER 210.63. | | | | | | 4} PLEASE VERIFY THE DRYER IS 110 VOLT | | | AS INDICATED ON THE PANEL SCHEDULE. SEE | | | 220.18. | | | | | | 5} INDENTIFY THE REQUIRED ARC FAULT | | | BREAKERS IN THE PANEL PER 210.12. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-06-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-06-27 |
Time |
10:50 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2005-06-27 |
Time |
10:04 |
Sent To |
B |
|
| Notes |
| 2005-06-27 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE INDICATE THE SERVICE EQUIPMENT | | | LOCATION ON THE PLAN. METER, DISCONNECT | | | AND PANEL(S). 215.5. | | | | | | 2} THERE MUST BE 2 APPLIANCE CIRCUITS ON | | | THE PANEL SCHEDULE PER 220.16. | | | | | | 3} SHOW LOCATION OF THE CONDENSING UNIT | | | AND DISCONNECT PER 440.14. ALSO SERVICE | | | RECEPTACLE LOCATION PER 210.63. | | | | | | 4} PLEASE VERIFY THE DRYER IS 110 VOLT | | | AS INDICATED ON THE PANEL SCHEDULE. SEE | | | 220.18. | | | | | | 5} INDENTIFY THE REQUIRED ARC FAULT | | | BREAKERS IN THE PANEL PER 210.12. | | | | | | 6} SMOKE DETECTORS ARE REQUIRED PER | | | NFPA-72 8-1.4.1.6.2 AND 905.2.2 FBC. | | | PLEASE LOCATE ON PLAN. | | | | | | 7} THE KITCHEN COUNTERTOP RECEPTACLES | | | MUST COMPLY WITH 210.52(C)(1) SPACING | | | AND 210.8(A)(6), GFI. | | | | | | 8} THE ARCHITECTS SEAL IS REQUIRED ON | | | THE PLANS. SEE FS 481. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-10-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-14 |
Time |
18:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-14 |
Time |
18:44 |
Sent To |
B |
|
| Notes |
| 2005-10-14 00:00:00 | TO "ALANGE" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-08-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-10 |
Time |
17:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-10 |
Time |
17:37 |
Sent To |
E |
|
| Notes |
| 2005-08-10 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-06-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-06-28 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-06-28 |
Time |
16:00 |
Sent To |
E |
|
| Notes |
| 2005-06-28 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-06-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-06-28 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-06-24 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2005-06-24 00:00:00 | TO "JWITMER" DESK/SUBMITTAL |
|
|