Plan Review Details - Permit 05060746
Plan Review Stops For Permit 05060746
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-10-20 Cont ID  
Sent By alange Date 2005-10-20 Time 11:43 Rev Time 0.33
Received By alange Date 2005-10-20 Time 11:43 Sent To  
Notes
2005-10-20 00:00:00INSULATION REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-07-11 Cont ID  
Sent By alange Date 2005-07-11 Time 10:40 Rev Time 0.33
Received By alange Date 2005-07-11 Time 10:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-27 Cont ID  
Sent By alange Date 2005-06-27 Time 09:45 Rev Time 0.50
Received By alange Date 2005-06-27 Time 09:44 Sent To E
Notes
2005-06-27 00:00:00DENIED
  
 1.THE ARCHITECTS FIRM LICENSE NUMBER
 IS REQUIRED ON THE TITLE BLOCK PER
 61G1-16.004 FAC.
 ARCHITECTS SEAL AND SIGNATURE IS
 REQUIRED FBC 104.2.2
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-08-11 Cont ID  
Sent By btrobaug Date 2005-08-11 Time 11:29 Rev Time 0.50
Received By btrobaug Date 2005-08-11 Time 11:20 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-07 Cont ID  
Sent By btrobaug Date 2005-07-07 Time 12:15 Rev Time 0.50
Received By btrobaug Date 2005-07-07 Time 12:09 Sent To B
Notes
2005-07-07 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 COMMENTS FROM PREVIOUS REVIEW.
  
 2} THERE MUST BE 2 APPLIANCE CIRCUITS ON
 THE PANEL SCHEDULE PER 220.16. SHOW
 SAME.
  
 3} SHOW LOCATION OF THE CONDENSING UNIT
 AND DISCONNECT PER 440.14. ALSO SERVICE
 RECEPTACLE LOCATION PER 210.63.
  
 4} PLEASE VERIFY THE DRYER IS 110 VOLT
 AS INDICATED ON THE PANEL SCHEDULE. SEE
 220.18.
  
 5} INDENTIFY THE REQUIRED ARC FAULT
 BREAKERS IN THE PANEL PER 210.12.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-27 Cont ID  
Sent By btrobaug Date 2005-06-27 Time 10:50 Rev Time 0.75
Received By btrobaug Date 2005-06-27 Time 10:04 Sent To B
Notes
2005-06-27 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE SERVICE EQUIPMENT
 LOCATION ON THE PLAN. METER, DISCONNECT
 AND PANEL(S). 215.5.
  
 2} THERE MUST BE 2 APPLIANCE CIRCUITS ON
 THE PANEL SCHEDULE PER 220.16.
  
 3} SHOW LOCATION OF THE CONDENSING UNIT
 AND DISCONNECT PER 440.14. ALSO SERVICE
 RECEPTACLE LOCATION PER 210.63.
  
 4} PLEASE VERIFY THE DRYER IS 110 VOLT
 AS INDICATED ON THE PANEL SCHEDULE. SEE
 220.18.
  
 5} INDENTIFY THE REQUIRED ARC FAULT
 BREAKERS IN THE PANEL PER 210.12.
  
 6} SMOKE DETECTORS ARE REQUIRED PER
 NFPA-72 8-1.4.1.6.2 AND 905.2.2 FBC.
 PLEASE LOCATE ON PLAN.
  
 7} THE KITCHEN COUNTERTOP RECEPTACLES
 MUST COMPLY WITH 210.52(C)(1) SPACING
 AND 210.8(A)(6), GFI.
  
 8} THE ARCHITECTS SEAL IS REQUIRED ON
 THE PLANS. SEE FS 481.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-14 Cont ID  
Sent By adarroug Date 2005-10-14 Time 18:44 Rev Time 0.00
Received By adarroug Date 2005-10-14 Time 18:44 Sent To B
Notes
2005-10-14 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-10 Cont ID  
Sent By adarroug Date 2005-08-10 Time 17:37 Rev Time 0.00
Received By adarroug Date 2005-08-10 Time 17:37 Sent To E
Notes
2005-08-10 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-28 Cont ID  
Sent By adarroug Date 2005-06-28 Time 16:00 Rev Time 0.00
Received By adarroug Date 2005-06-28 Time 16:00 Sent To E
Notes
2005-06-28 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-28 Cont ID  
Sent By adarroug Date 2005-06-28 Time 15:59 Rev Time 0.00
Received By adarroug Date 2005-06-24 Time 14:14 Sent To  
Notes
2005-06-24 00:00:00TO "JWITMER" DESK/SUBMITTAL