Plan Review Details - Permit 05060730
Plan Review Stops For Permit 05060730
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-09-01 Cont ID  
Sent By shill Date 2006-09-01 Time 08:35 Rev Time 0.00
Received By shill Date 2006-09-01 Time 08:35 Sent To  
Notes
2006-09-01 00:00:00REVISION, CIVILS 1 THROUGH 3
  
 ROUTED TO INCOMING, NEEDS ZONING AND
 ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-07-06 Cont ID  
Sent By shill Date 2006-07-06 Time 11:47 Rev Time 0.00
Received By shill Date 2006-07-06 Time 11:40 Sent To  
Notes
2006-07-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)RAMPS THAT ARE A PART OF A REQUIRED
 MEANS OF EGRESS SHALL NOT BE LESS THAN
 44", FBC 11-4.8.3, EXCEPTION.
  
 2.)PARKING IS TO COMPLY WITH CITY OF
 WEST PALM BEACH STANDARD, SEE ATTACHED.
 PLEASE INCORPORATE INTO THE PLAN DETAIL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-23 Cont ID  
Sent By lmartine Date 2005-09-23 Time 09:32 Rev Time 0.00
Received By lmartine Date 2005-09-12 Time 16:58 Sent To  
Notes
2005-09-23 00:00:00APPROVED BY SAMANTHA ON 9/12/05

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-09 Cont ID  
Sent By shill Date 2005-08-09 Time 09:30 Rev Time 2.00
Received By shill Date 2005-08-09 Time 09:25 Sent To  
Notes
2005-08-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PLEASE SEE PREVIOUS REQUEST (ITEM
 #3) FOR STATE OR LOCAL PRODUCT APPROVALS
 FAC9B72.THIS IS REQUIRED IN ADDITION
 TO THE NOAS.STATE APPROVALS ARE
 AVAILABLE AT WWW.FLORIDABUILDING.ORG;
 THE APPLICATION FOR LOCAL PRODUCT
 APPROVAL IS ON THE SAME SITE.
  
 2.)ON THE GLASS APPROVALS, PLEASE
 CIRCLE METHOD OF ATTACHMENT AND GLASS
 TYPES/SIZES TO BE INSTALLED.NOT ALL
 ARE CODE COMPLIANT.
  
 3.)SEE PREVIOUS LIST, ITEM #4.THE
 PARAPET WALL 1-A8.1 WAS REVISED TO AN
 EIFS SYSTEM, NOA01-0614.17.THIS IS
 SMALL MISSILE IMPACT ONLY, SHUTTERS
 REQUIRED.REMOVABLE SHUTTERS ON LARGE
 COMMERCIAL BUILDINGS REQUIRES APPROVAL
 BY THE BUILDING OFFICIAL, SEE ATTACHED
 POLICY ITEM #13.
  
 3.)THE CIVIL SHEET PREPARED BY SIMMONS
 & WHITE (SHEET 2 OF 2) SHOWS THE
 EXISTING BUILDING AS 53,368 SF.PLEASE
 CLARIFY WHY THIS NUMBER IS DIFFERENT
 FROM ID.00, EXISTING BUILDING 41,218 SF.
  
 4.)SOME SHEETS HAD CHANGES WITHOUT
 CLOUDS.TO EXPEDITE PLAN REVIEW, PLEASE
 CLEARLY INDICATE ALL CHANGES TO THE
 PLAN AND SUBMIT OLD SHEETS.
  
 5.)(NEW COMMENT) THE DIMENSIONS ON LS1
 (A NEW SHEET, DATED 7/20/05) ARE NOT
 CLEAR AS TO WHAT THEY CORRELATE WITH.
 FOR INSTANCE, THE FARTHEST DISTANCE
 (EXISTING SERVICE MANAGER) TO THE EXIT
 HAS TWO DIMENSIONS, 175' AND 198'.
 NEITHER APPEARS TO BE THE CORRECT
 DISTANCE. THE COMMON PATH OF TRAVEL
 APPEARS TO BE 160' WHEN SCALED; CANNOT
 EXCEED 100' FBC1020.6.PLEASE REVISE
 THE LS TO CLEARLY SHOW CODE COMPLIANCE.
  
 6.)WHEN RESUBMITTING, CHANGE ONLY
 SHEETS WHICH HAVE BEEN REVISED.OLD
 SHEETS SUBMITTED SEPARATELY.ALL
 CHANGES SHOULD BE CLOUDED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By shill Date 2005-07-11 Time 17:53 Rev Time 2.00
Received By shill Date 2005-07-11 Time 17:53 Sent To Z
Notes
2005-07-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)IMPACT FEES ARE DUE TO PALM BEACH
 COUNTY.THE PLANS MUST BE STAMPED AND
 THE RECEIPT ATTACHED TO THE APPLICATION.
 561-233-5025 FOR MORE INFORMATION.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED FOR:
  
 IMPACT STOREFRONT SYSTEM
 ROOF
  
 ANY PRODUCT APPROVALS NOT SUBMITTED AND
 REVIEWED FOR CODE COMPLIANCE PRIOR TO
 ISSUANCE OF THE PERMIT WILL REQUIRE
 SEPARATE PERMITS FOR THOSE ITEMS.
  
 4.)FBC606, TYPE IV TO BE NON
 COMBUSTIBLE WALLS.FBC TABLE 600,
 FOOTNOTE (E) ALLOWS FIRE TREATED PLYWOOD
 FOR THE ROOF BUT DOES NOT HAVE THE SAME
 EXCEPTION FOR WALLS.THE PARAPET WALL
 1-A8.1 SHOWS FIRE TREATED PLYWOOD (OTHER
 DETAILS MAY ALSO BE AFFECTED).
  
 5.)1-A8.1, STUCCO OVER WIRE LATH IN A
 VERTICAL APPLICATION TO BE 7/8",
 FBC2504.2.2, ASTM C926.
  
 6.)ID.00 SHOWS THE ADDITION AS 1905
 SQUARE FEEET; 1885 IS ON THE ENERGY
 CALC.
  
 7.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2006-06-30 Cont ID  
Sent By dpalmer Date 2006-06-30 Time 17:26 Rev Time 0.00
Received By dpalmer Date 2006-06-30 Time 15:22 Sent To  
Notes
2006-06-30 00:00:00SHEETS A 4.1 WHICH SHOWS POWER/DATE IS
 NOT AN ELECTRICAL SHEET AND IS FOR
 REFERENCE ONLY.
 NO ELECTRICAL REVIEW DONE, AS E-SHEETS
 WERE NOT SUBMITTED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 19:07 Rev Time 0.25
Received By dpalmer Date 2005-09-03 Time 19:02 Sent To  
Notes
2005-09-03 00:00:00ELECTRICAL SHEETS STAMPED. OK

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-04 Cont ID  
Sent By dpalmer Date 2005-08-04 Time 09:10 Rev Time 0.33
Received By dpalmer Date 2005-08-04 Time 09:06 Sent To  
Notes
2005-08-04 00:00:00******** UNSAT ******
  
 1)NOTE: PLEASE SEE BOTH SETS ARE TO BE
 SIGNED DATED AND SEALED BY ENGINEER OF
 RECORD. FS 471.025,FAC 61G15-23.002
 PLEASE SEE ONE SET, NEW REVISED SHEETS.
 PLEASE SEE ELECTRICAL COMMENTS WERE
 ADDRESSED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-07-01 Cont ID  
Sent By dpalmer Date 2005-07-01 Time 07:04 Rev Time 0.50
Received By dpalmer Date 2005-06-30 Time 21:05 Sent To  
Notes
2005-07-01 00:00:00************ UNSAT **********
  
 1)NOTE: PLEASE CLARIFY/SHOW NEW OR
 EXISTING ROOFTOP GFI RECEPT FOR A/C
 RTU'S. 210.63,210.8
  
 2)NOTE: PLEASE SEE MISSING RECEPT FOR
 SHOW WINDOW ON WEST AND NORTH OF SHOW
 RM.
 210.62
  
 3)NOTE: PLEASE SEE MDP IS SHOWN BLANK
 AND NO NEW LOADS AND/OR EXISTING LOADS
 ARE SHOWN?
 PLEASE ALSO SEE ALL CONTINUOUS LOADS AND
 LARGEST MOTOR LOADS TO BE SHOWN @125%.
 215.3,230.42,220 ETC.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE BE SURE ALL OLD/VOIDED SHEETS ARE
 REMOVED FROM SETS AND ONLY NEW REVISED
 SHEETS ARE INSERTED INTO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 PLEASE SEE ONE SET OF OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
2005-06-30 00:00:00IN ELEC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2006-10-20 Cont ID  
Sent By rchokshi Date 2006-10-20 Time 14:05 Rev Time 0.00
Received By rchokshi Date 2006-10-20 Time 14:05 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2006-09-08 Cont ID  
Sent By rchokshi Date 2006-09-08 Time 09:32 Rev Time 0.00
Received By rchokshi Date 2006-09-08 Time 09:12 Sent To  
Notes
2006-09-08 00:00:00NEED THE FOLLOWING INFO:
  
 1. POLLUTION PREVENTION PLANS & DETAILS
 2. STORM WATER CALCULATIONS,RUNOFF CAL.,
 PRE & POST CALS., PERVIOUS,IMPERVIOUS
 AREA CHANGES,
 3. NOTES ON DRAWINGS FOR PARKINGS,
 HANDICAP PARKINGS, ADA STANDARDS, CITY
 OF WPB STANDARDS ETC., SHOULD BE
 INCLUDED IN THE DRAWINGS & DRAWN PER
 NOTES.
 4. DUMPSTER ENCLOSURE MUST MEET CITY OF
 WPB STANDARDS.
 5. DRIVEWAY, APPROACH, SIDEWALK,CURBS,
 ETC. MUST MEET CITY OF WPB STANDARDS.
 6. PLEASE MAKE SURE PARKING LOT
 ELEVATIONS ARE THAN ROAD ELEVATION AND
 MUST MEET FLORIDA BLDG CODES.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2005-09-13 Cont ID  
Sent By mamini Date 2005-09-13 Time 14:21 Rev Time 0.50
Received By rchokshi Date 2005-09-13 Time 14:21 Sent To B
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-07-05 Cont ID  
Sent By mamini Date 2005-07-05 Time 16:23 Rev Time 0.50
Received By mamini Date 2005-07-05 Time 16:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-07-03 Cont ID  
Sent By mwennerg Date 2006-07-03 Time 14:09 Rev Time 0.00
Received By mwennerg Date 2006-07-03 Time 14:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-09-14 Cont ID  
Sent By mwennerg Date 2005-09-14 Time 10:33 Rev Time 0.00
Received By mwennerg Date 2005-09-14 Time 10:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-08-10 Cont ID  
Sent By mwennerg Date 2005-08-10 Time 09:26 Rev Time 0.00
Received By mwennerg Date 2005-08-10 Time 09:26 Sent To  
Notes
2005-08-10 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT YOUR RESPONSE TO
 COMMENT #4 INDICATES WHEN VEHICLES WILL
 BE RUNNING OR OFF. AS PER THE FIRST
 REVIEW, VEHICLES WHEN STORED INSIDE MUST
 HAVE ONE BATTERY CABLE DISCONNECTED AND
 LOW FUEL.
  
 2) ALTHOUGH THE BUILDING ADDRESS IS
 EXISTING, PLEASE ILLUSTRATE ON PLANS AND
 ADDRESS MUST BE AT LEAST 6" IN HEIGHT
 AND CONTRASTING TO BACKGROUND.
  
 3) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS AND FAC REQUIREMENTS FOR
 PLANS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 5) PLEASE DIRECT YOUR RESPONSE TO THE
 PLANS REGARDING EMERGENCY LIGHTING
 FACILITIES WITH THE CORRELATING SHEET
 NUMBER.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-11 Cont ID  
Sent By mcarsill Date 2005-07-11 Time 11:19 Rev Time 0.00
Received By mcarsill Date 2005-07-11 Time 10:53 Sent To  
Notes
2005-07-11 00:00:001. KNOX-BOX WILL BE REQUIRED.
  
 2. PLEASE DISPLAY EMERGENCY LIGHTING.
  
 3. SITE PLAN DOES NOT DIPLAY FIRE
 HYDRANTS INSIDE OR OUTSIDE THE CAMPUS.
  
 4. PLEASE INDICATE ON THE PLANS HOW
 THE VEHICLES WILL BE DISPLAYED.
 BATTERIES ARE TO BE DISCONNECTED AND
 THEY SHALL CONTAIN VERY LITTLE FUEL.
  
 5. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 6. NEW SOFFIT SHALL NOT OBSCURE FIRE
 SPRINKLER HEADS.
  
 7. BUILDING ADDRESS WILL BE REQUIRED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 835-2910
  
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-10-16 Cont ID  
Sent By adarroug Date 2006-10-16 Time 11:25 Rev Time 0.00
Received By adarroug Date 2006-10-16 Time 11:25 Sent To ENG
Notes
2006-10-16 11:26:04TO "ENG" BOX

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 17:10 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 17:10 Sent To  
Notes
2006-10-12 13:47:09TO "COMM" BD#27
2006-09-23 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-09-01 Cont ID  
Sent By adarroug Date 2006-09-01 Time 08:38 Rev Time 0.00
Received By adarroug Date 2006-09-01 Time 08:38 Sent To Z
Notes
2006-09-05 00:00:00DENIED BY ZONING.SENT TO ENGINNERING
 IN-BOX.
  
  
2006-09-01 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 12:59 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 12:59 Sent To ENG
Notes
2006-08-14 00:00:00TO "ENG' BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 15:56 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 15:56 Sent To  
Notes
2006-06-27 00:00:00TO "COMM" BD#3
2006-06-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-31 Cont ID  
Sent By adarroug Date 2005-08-31 Time 14:15 Rev Time 0.00
Received By adarroug Date 2005-08-31 Time 14:15 Sent To  
Notes
2005-08-31 00:00:00TO "COMM" BD#48

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 18:45 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 18:45 Sent To  
Notes
2005-07-29 00:00:00TO "COMM" BD#43
2005-07-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 10:22 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 10:22 Sent To  
Notes
2005-07-07 00:00:00TO "COMM" BD#40/W ORIGINAL APPL.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-11 Cont ID  
Sent By shill Date 2005-07-11 Time 18:09 Rev Time 0.00
Received By shill Date 2005-06-09 Time 06:50 Sent To  
Notes
2005-06-10 00:00:00COMM BOARD #40
2005-06-09 00:00:00WAITING FOR COMM BOARD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-11 Cont ID  
Sent By pkrauss Date 2005-07-11 Time 13:32 Rev Time 0.55
Received By pkrauss Date 2005-07-11 Time 13:28 Sent To  
Notes
2005-07-11 00:00:00PROVISO:
 2001 FBC(M)502.11 EXCEPTION #3:
 MECHANICAL EXHAUST WILL NOT BE REQUIRED
 SO LONG AS MOTOR VECHICLES WILL ONLY RUN
 WHILE MOVING TO MOVE VECHICLES IN AND
 OUT OF THE BUILDING (NO IDLING).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-24 Cont ID  
Sent By kstevens Date 2005-08-24 Time 16:38 Rev Time 1.33
Received By kstevens Date 2005-08-24 Time 16:38 Sent To  
Notes
2005-08-24 00:00:00PASSED/PROVISO
  
 ARCHITECT INDICATED THAT AN EXISTING
 SERVICE SINK WAS IN THE BUILDING.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-09 Cont ID  
Sent By kstevens Date 2005-07-09 Time 08:38 Rev Time 1.33
Received By kstevens Date 2005-07-09 Time 08:38 Sent To  
Notes
2005-07-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1. SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES. INDICATE THE SQUARE FOOTAGE
 OF THE EXISTING BUILDING, THE SQUARE
 FOOTAGE OF EACH OCCUPANCY, AND THE
 SQUARE FOOTAGE OF THE ADDITION. INDICATE
 THE NUMBER OF FIXTURES REQUIRED PER
 TABLES 1003.1 (BLDG) AND 403.1 (PLMG).
 2. SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW SF OF NEW
 ROOF AND SHOW 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS ADDED TO THE
 AREA OF THE ROOF IN THE CALCULATIONS.
 3. MORE INFORMATION REQUIRED FOR ROOF.
 APPLICATION INDICATES 6,263SF ADDITION,
 BUT ROOF DRAIN AREAS ONLY ADD UP TO
 2,500SF. PLEASE CLARIFY. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status F Date 2006-10-16 Cont ID  
Sent By eschneid Date 2006-10-16 Time 10:03 Rev Time 0.00
Received By eschneid Date 2006-10-16 Time 10:03 Sent To  
Notes
2006-10-16 10:05:50FAILED
  
 THE PLAN SUBMITTED WITH THE PERMIT DOES NOT MATCH THE
 CURRENTLY APPROVED PARKING LAYOUT.THE PLAN SUBMITTED
 MATCHES THE PLANS THAT HAVE NOT PROCEEDED TO THE CITY
 COMMISSION FOR APPROVAL.
  
 ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status F Date 2006-09-05 Cont ID  
Sent By eschneid Date 2006-09-05 Time 12:54 Rev Time 0.00
Received By eschneid Date 2006-09-05 Time 12:54 Sent To  
Notes
2006-09-05 00:00:00THE REVISION TO THE PARKING AREA HAS NOT
 BEEN APPROVED BY THE CITY COMMISSION
 THROUGH THE MAJOR DSI AMENDMENT PROCESS.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-19 Cont ID  
Sent By eschneid Date 2006-07-19 Time 13:45 Rev Time 0.00
Received By eschneid Date 2006-07-19 Time 13:36 Sent To  
Notes
2006-07-19 00:00:001) THE ADDITION OF THE RAMPS DOES NOT
 MATCH THE APPROVED LANDSCAPE PLAN.
  
 2) NO LANDSCAPE PLAN SUBMITTED.
  
 3) DSI AMENDMENT REQUIRE TO MODIFY THE
 SITE PLAN.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-07-13 Cont ID  
Sent By jlong Date 2005-07-13 Time 17:33 Rev Time 0.00
Received By jlong Date 2005-07-13 Time 17:33 Sent To  
Notes
2005-07-13 00:00:00RESOLUTION NO. 256-05 PASSED CITY
 COMMISSION ON JUNE 6, 2005 WHICH
 APPROVED THIS RENOVATION PROJECT.