| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-08-09 |
Time |
11:31 |
Rev Time |
2.00 |
| Received By |
prafter |
Date |
2005-08-09 |
Time |
12:03 |
Sent To |
P |
|
| Notes |
| 2005-08-09 00:00:00 | MECH. PLAN REVIEW: | | | | | | 1. A/C PERMIT VALUE MUST BE INCREST TO | | | REFLECT SCOPE OF WORK. | | | | | | 2. UP DATE NOTICE OF COMMENCEMENT MUST | | | BE SUBMITED. | | | | | | 3. A/C PLAN MUST REFLECT R/A OUT OF | | | HABITABLE ROOMS.2003 FBC/M 601.4 | | | | | | 4. A.H.U. REQUIRE SAFE PANS UNDER UNITS | | | WITH DRAIN PAN PROTECTION. 2003 FBC/M | | | 307.2.3 AUX. DRAIN PAN. | | | | | | 5. UTILITY ROOM REQUIRES COMBUSTION AIR | | | FOR GAS DRYER. 2000 FBC/M CHAPTED #7 | | | | | | 6. PLEASE COMPLY WITH PROVISO M-1 | | | 9/20/04 PATTY KRAUSS MECH. PLAN REVIEW. | | | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | | PATTY KRAUSS | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. |
|
|
|