Plan Review Details - Permit 05060589
Plan Review Stops For Permit 05060589
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-10-14 Cont ID  
Sent By shill Date 2005-10-14 Time 10:21 Rev Time 0.50
Received By shill Date 2005-10-14 Time 10:15 Sent To  
Notes
2005-10-14 00:00:00***PROVISO***ELEVATION CERT REQUIRED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-02 Cont ID  
Sent By shill Date 2005-09-02 Time 07:34 Rev Time 1.00
Received By shill Date 2005-09-02 Time 06:57 Sent To  
Notes
2005-09-02 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SEE PREVIOUS LIST, ITEM #1, PROVIDE
 ANCHORING INFORMATION TO COMPLY WITH
 FBC1606.1.3; STRUCTURAL MEMBERS AND
 SYSTEMS, AND COMPONENTS AND CLADDING IN
 A BUILDING OR STRUCTURE SHALL BE
 ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
 2.)PROVIDE THE ORIGINAL PERMIT
 APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-12 Cont ID  
Sent By shill Date 2005-07-01 Time 11:50 Rev Time 0.50
Received By shill Date 2005-07-01 Time 11:50 Sent To  
Notes
2005-07-01 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
 2.)THE VALUE IS TOO LOW.PROVIDE A
 REASONABLE VALUE OR AN ESTIMATED VALUE
 WILL BE DONE FOR YOU USING MARSHALL &
 SWIFT.
  
 3.)PROVIDE A SURVEY AND SITE PLAN
 SHOWING THE LOCATION OF THE GENERATOR
 AND SLAB.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-16 Cont ID  
Sent By btrobaug Date 2005-11-16 Time 18:58 Rev Time 0.50
Received By btrobaug Date 2005-11-16 Time 18:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-16 Cont ID  
Sent By btrobaug Date 2005-08-16 Time 12:59 Rev Time 0.50
Received By btrobaug Date 2005-08-16 Time 12:33 Sent To  
Notes
2005-08-16 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE WHICH FLOOD ZONE THIS
 PROJECT IS IN. PROVIDE A FLOOD ELEVATION
 CERTIFICATE.
  
 2} THE INFORMATION SUBMITTED FOR THE
 TRANSFER SWITCH DOES NOT INDICATE IT IS
 SERVICE RATED PER 225.36, . PLEASE
 INDICATE THAT IT IS PER SPEC'S OR
 INDICATE COMPLIANCE WITH THAT ARTICLE.
  
 3} THE PLANS MUST BEAR THE SIGNATURE AND
 PRINTED NAME OF THE PERSON RESPONSIBLE.
  
 4} PLEASE ATTACH THE ORIGINAL PERMIT
 APPLICATION WHEN RESUBMITTING. CURRENTLY
 ONLY TWO HALF COPIES ARE IN THE PACKAGE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-22 Cont ID  
Sent By btrobaug Date 2005-06-22 Time 14:17 Rev Time 0.75
Received By btrobaug Date 2005-06-16 Time 12:17 Sent To I
Notes
2005-06-16 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} IT APPEARS THAT LINE AND LOAD FOR THE
 DISCONNECTS ARE IN THE SAME GUTTER. SHOW
 SEPARATION PER 230.7.
  
 2} SHOW LOCATION OF DISCONNECTING MEANS
 FOR GENERATOR FEEDERS PER 225.31, 32,
 36.
  
 3} SUBMIT MANUFACTURERS SPECS FOR THE
 GENERATOR AND TRANSFER SWITCH.
  
 4} THE PLANS INDICATE THE FEEDERS FROM
 THE GENERATOR ARE #4/0(CU?) AND THE
 GENERATOR APPEARS TO HAVE A 250 AMP OCP.
 SEE 445.13 FOR 115% AND 310.16 FOR
 ALLOWABLE AMPACITIES.
  
 5} PLEASE FURNISH CALCULATIONS FOR THE
 LOADS SELECTED TO BE SUPPLIED ON
 EMERGENCY POWER.
  
 6} THE COST OF ALL EQUIPMENT BEING
 INSTALLED MUST BE INCLUDED ON THE
 APPLICATIION, EVEN THOUGH OWNER
 SUPPLIED. 104.2.1 CWPB AMMENDMENTS.
  
 7} PLEASE INDICATE WHICH FLOOD ZONE THIS
 PROJECT IS IN.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-11-09 Cont ID  
Sent By mwennerg Date 2005-11-09 Time 10:44 Rev Time 0.00
Received By mwennerg Date 2005-11-09 Time 10:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-06 Cont ID  
Sent By mwennerg Date 2005-09-06 Time 14:43 Rev Time 0.00
Received By mwennerg Date 2005-09-06 Time 14:43 Sent To  
Notes
2005-09-06 00:00:00******PROVISO******
  
 PLEASE PROVIDE FURTHER INFORMATION
 REGARDING FUEL AMOUNT AND STORAGE. PLANS
 WILL BE RESUBMITTED FOR OTHER REVIEW
 COMMENTS, AND WILL BE STAMPED BY FIRE AT
 THAT TIME.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-07-12 Cont ID  
Sent By mwennerg Date 2005-07-12 Time 13:01 Rev Time 0.00
Received By mwennerg Date 2005-07-12 Time 13:01 Sent To  
Notes
2005-07-12 00:00:00******DENIED******
  
 1) WORK TO COMPLY WITH NFPA 110 AND
 OTHER APPLICABLE CODES.
  
 2) PLEASE ILLUSTRATE THE ON SITE
 LOCATION OF THE GENERATOR AND FUEL
 SUPPLY.
  
 3) PLEASE PROVIDE MANUFACTURER CUT
 SHEETS FOR THE PROPOSED GENERATOR.
  
 4) PLEASE SHOW WHERE EXHAUSTING WILL
 OCCUR IN REGARDS TO SURROUNDING
 STRUCTURES AND OR OPENINGS.
  
 5) PLEASE PROVIDE ADDITIONAL INFORMATION
 IN REGARDS TO THE FUEL SUPPLY AND SIZE
 OF STORAGE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-03 Cont ID  
Sent By adarroug Date 2005-10-03 Time 08:33 Rev Time 0.00
Received By adarroug Date 2005-10-03 Time 08:33 Sent To  
Notes
2005-10-12 00:00:00TO "COMM" BD#33
2005-10-03 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-10 Cont ID  
Sent By adarroug Date 2005-08-10 Time 16:38 Rev Time 0.00
Received By adarroug Date 2005-08-10 Time 16:38 Sent To  
Notes
2005-08-15 00:00:00TO "COMM" BD#50
2005-08-10 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-22 Cont ID  
Sent By adarroug Date 2005-06-22 Time 16:07 Rev Time 0.00
Received By adarroug Date 2005-06-22 Time 16:38 Sent To  
Notes
2005-06-27 00:00:00TO "COMM" BD#7
2005-06-22 00:00:00WAITING FOR SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 17:20 Rev Time 0.00
Received By shill Date 2005-06-10 Time 17:20 Sent To E
Notes
2005-06-10 00:00:00TO ELEC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 11:26 Rev Time 0.00
Received By shill Date 2005-06-08 Time 11:26 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-09 Cont ID  
Sent By pkrauss Date 2005-09-09 Time 07:43 Rev Time 0.45
Received By pkrauss Date 2005-09-09 Time 07:07 Sent To  
Notes
2005-09-09 00:00:00PROVISO:
 PLEASE PROVIDE ANCHORING DETAIL FOR THE
 GENERATOR TO THE SLAB PER 2001 FBC
 1606.1.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-20 Cont ID  
Sent By pkrauss Date 2005-07-20 Time 07:02 Rev Time 0.45
Received By pkrauss Date 2005-07-20 Time 07:02 Sent To  
Notes
2005-07-20 00:00:00DENIED:
 1.PROVIDE MANUFACTURER SUBMITTAL DATA
 FOR THE DIESEL GENERATOR.
  
 2.PROVIDE SITE PLAN OR SURVEY,
 INDICATE DISTANCES FROM THE PROPERTY
 LINES, AND ADJACENT BUILDINGS.
  
 3.INDICATE DISTANCES FROM DOORS,
 WINDOWS AND FRESH AIR INTAKES.SHOW
 COMPLIANCE WITH 2001 FBC(M)401.5 &
 501.3.
  
 4.PROVIDE DETAIL FOR ANCHORING OF THE
 GENERATOR IN ACCORDANCE WITH 2001 FBC
 1606.1.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-29 Cont ID  
Sent By mmclean Date 2005-08-29 Time 15:45 Rev Time 0.00
Received By mmclean Date 2005-08-29 Time 15:45 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-10 Cont ID  
Sent By mmclean Date 2005-06-10 Time 11:38 Rev Time 0.00
Received By mmclean Date 2005-06-10 Time 08:46 Sent To I
Notes
2005-06-10 00:00:00 
 THE FOLLOWING IS NOT A ZONING PLAN
 REVIEW, IT IS A RECORD OF TELEPHONE
 CONVERSATION ONLY:
  
 TELEPHONE CONVERSATION WITH JOHN BELL
 (TEL: 561-688 2299 AND 561-262 6566) ON
 6/10/05 AT 9:30AM:
  
 MR BELL CONFIRMED THAT THE NEW GENERATOR
 WILL BE EXTERIOR EQUIPMENT.HE WAS THEN
 ADVISED THAT THE SUBMITTED PLANS DO NOT
 MAKE THAT CLEAR AND HE WILL BE REQUIRED
 TO SUBMIT A SURVEY DRAWING WITH
 DIMENSIONS TO SHOW THE EQUIPMENT
 LOCATION IN RELATION TO PROPERTY LINES.
 DENIED,
 1. MUST PROVIDE TWO COPY OF SURVEY
 SHOWING THE LOCATION OF THE GENERATOR
 AND THE SETBACKS FROM THE PROPERTY LINE
 AND IF ANY STRUCTURE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720