Plan Review Details - Permit 05060524
Plan Review Stops For Permit 05060524
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-13 Cont ID  
Sent By btrobaug Date 2005-09-13 Time 13:33 Rev Time 0.50
Received By btrobaug Date 2005-09-13 Time 13:33 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-22 Cont ID  
Sent By btrobaug Date 2005-06-22 Time 13:38 Rev Time 0.33
Received By btrobaug Date 2005-06-22 Time 13:02 Sent To M
Notes
2005-06-22 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
 PLEASE PROVIDE TWO COPIES OF ALL PLANS
 AND SPEC'S.
  
 1} SPECS FOR THE GENERATOR AND TRANSFER
 SWITCH.
  
 2} INDICATE THE PRIME MOVER, HIGHLITE IN
 SPEC OR WRITE ON PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 14:26 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 14:26 Sent To E
Notes
2005-09-08 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-17 Cont ID  
Sent By shill Date 2005-06-17 Time 08:11 Rev Time 0.00
Received By shill Date 2005-06-17 Time 08:11 Sent To E
Notes
2005-06-17 00:00:00TO ELEC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 10:21 Rev Time 0.00
Received By shill Date 2005-06-08 Time 10:21 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-09-13 Cont ID  
Sent By pkrauss Date 2005-09-13 Time 14:03 Rev Time 0.00
Received By pkrauss Date 2005-09-13 Time 14:02 Sent To  
Notes
2005-09-13 00:00:00GAS PERMIT 05081623/GEN-RES 05061226

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-27 Cont ID  
Sent By pkrauss Date 2005-06-27 Time 10:13 Rev Time 0.30
Received By pkrauss Date 2005-06-27 Time 10:12 Sent To  
Notes
2005-06-27 00:00:00DENIED:
 PERMIT APPLICATION INDICATES THE VALUE
 OF WORK FOR "LABOR ONLY".HOMEOWNER TO
 SUPPLY GENERATOR.PER THE CITY
 AMENDMENTS 104.6.5, VALUATION SHALL
 INCLUDE COST FOR ALL EQUIPMENT, LABOR,
 OVERHEAD, AND PROFIT, EXCLUDING ONLY
 LAND VALUE.PLEASE ADJUST VALUE OF
 PERMIT ACCORDINGLY.
  
 PLAN INDICATES GENERATOR TO BE 12" FROM
 THE BUILDING STRUCTURE.PLEASE PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS
 FOR CLEARANCES.PLEASE NOTE, PER 2001
 FBC(M)804.3.5 #3 WHERE THE VENT
 TERMINATION IS LOCATED BELOW AN SDJACENT
 ROOF STRUCTURE, THER TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FEET FROM
 THE STRUCTURE.
  
 ADDITIONAL PERMIT REQUIRED FOR LP GAS.
 PROVIDE PLAN INDICATE THE LOCATION &
 REQUIRED CLEARANCES FOR THE LP TANK IN
 ACCORDANCE WITH NFPA 58.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-06-16 Cont ID  
Sent By mmclean Date 2005-06-16 Time 18:17 Rev Time 0.00
Received By mmclean Date 2005-06-16 Time 18:17 Sent To I
Notes
2005-06-16 00:00:00PROVISO: ALL EQUIPMENT CAN ONLY ENCROACH
 4FT INTO SETBACK.