| 2005-06-08 00:00:00 | DENIED | | | | | | 1) THE PRODUCT APPROVAL SUBMITTED FOR | | | THE MODIFIED BITUMEN SYSTEM HAS A | | | MAXIMUM DESIGN PRESSURE OF -45 PSF WITH | | | LIMITATION #9 WHICH DOES NOT ALLOW FOR | | | ENHANCED FASTENER SPACING TO INCREASE | | | DESIGN PRESSURE. THE PRESSURE AT CORNERS | | | (ZONE 3) IS -89PSF. | | | | | | 2) SPECIFY THE APPROVED ASSEMBLY THAT | | | WILL BE INSTALLED. SEVERAL ARE IN THE | | | NOA SUBMITTED. SOME ARE FOR INSULATED | | | WOOD DECKS AND SOME ARE NON-INSULATED | | | WOOD DECKS. | | | | | | CALL IF YOU HAVE QUESTIONS: | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
|