Plan Review Details - Permit 05060430
Plan Review Stops For Permit 05060430
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-07-19 Cont ID  
Sent By jhiggins Date 2005-07-19 Time 10:35 Rev Time 0.00
Received By jwitmer Date 2005-11-16 Time 10:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-11-16 Cont ID  
Sent By jwitmer Date 2005-11-16 Time 10:13 Rev Time 1.55
Received By jwitmer Date 2005-11-16 Time 10:13 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-27 Cont ID  
Sent By jwitmer Date 2005-08-27 Time 13:36 Rev Time 0.77
Received By jwitmer Date 2005-08-27 Time 13:15 Sent To  
Notes
2005-08-27 00:00:00PLANS APPEAR TO BE CODE COMPLIANT, I
 RECEIVED AN E-MAIL FROM DEAN LAUDERMILK,
 THERE SEEMS TO BE ISSUES ABOUT EASEMENTS
 THAT HAVE NOT BEEN APPROVED BY THE LAW
 DEPARTMENT. JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-19 Cont ID  
Sent By jwitmer Date 2005-07-19 Time 11:09 Rev Time 2.22
Received By jwitmer Date 2005-07-19 Time 11:03 Sent To PC
Notes
2005-07-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05060430
 ADD: 7500 NORTHLAKES BLVD
 CONT: METRO EQUIPMENT SERVICES
 TEL: (305)586-8925
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) METRO EQUIPMENT SERVICES TO PROVIDE
 STATE LICENSE NUMBER FL S S 489.
  
 2) PLANS INDICATE A PRE-MANUFACTURED
 CONTROL BUILDING, PROVIDE STATE
 APPROVED PLANS BY THE DEPARTMENT OF
 COMMUNITY AFFAIRS.FL S S 553.1 RULE B-1.
  
 3) DEPENDING ON THE STATE APPROVAL FOR
 THE MANUFACTURED BUILDING, PRODUCT
 APPROVALS MAY BE REQUIRED FOR THE DOORS
 AND VENTS.
  
 4) STATE APPROVED PLANS SHALL INDICATE:
 FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5) THIS STRUCTURE IS IN A "A" FLOOD ZONE
  
 THE FLOOD HEIGHT HAS NOT BEEN
 DETERMINED, HAS THE BASE FLOOD HEIGHT
 FOR THE CONTROL BUILDING BEEN
 CONSIDERED?
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-12 Cont ID  
Sent By dpalmer Date 2006-09-12 Time 18:31 Rev Time 0.00
Received By dpalmer Date 2006-09-11 Time 19:49 Sent To PC
Notes
2006-09-12 00:00:00REV FOR MOVING THE ANT, AND PROVIDING
 LOAD TESTING.
2006-09-11 00:00:00IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-26 Cont ID  
Sent By dpalmer Date 2005-08-26 Time 19:51 Rev Time 0.50
Received By dpalmer Date 2005-08-26 Time 19:51 Sent To  
Notes
2005-08-26 00:00:00NEEDS 2ND SET OF GENERATORS SPEC/CUT
 SHEETS.
 ONLY ONE SET SUBMITTED.
 STAMPED ELECTRICAL PLANS AND ONE SET OF
 GEN SPECS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-23 Cont ID  
Sent By dpalmer Date 2005-06-23 Time 15:01 Rev Time 1.50
Received By dpalmer Date 2005-06-23 Time 13:56 Sent To  
Notes
2005-06-23 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SEE MISSING TITLE BLOCK
 AND TITLE BLOCK INFORMATION AS REQUIRED
 UNDER FAC 61G15-23.002, FS 471.023.
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLEASE COMPLETE ELECTRICAL
 PLANS. PLEASE SEE NO SEC'S, FEEDER SIZES
 ARE INDICATED. THERE APPEARS TO BE
 NOTS/NUMBERS TO EACH, HOWEVER THERE IS
 NO FEEDER SCHEDULE TO CORRELATE.
 215.5,310.16,240.4 ETC
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.NO PANEL
 SCHEDULE SUBMITTED.
 215.5
  
 4)NOTE: PLEASE SUBMIT MANUFACTURE
 SPECS/CUT SHEETS FOR GENERATOR AND ATS
 SWITCH. THESE ARE TO SHOW ALL LISTINGS
 PER A NRTL.
 PLEASE ALSO SEE MECH/FIRE REVIEW
 COMMENTS, AS SPECS ETC MAY BE REQUIRED
 ALSO FOR FUEL TANK.
  
 5)NOTE: PLEASE SEE PERMIT APPLICATION
 WAS SUBMITTED FOR $1.7 MIL SCOPE OF WORK
 AND NOW INDICATES $250K?? PLEASE SUBMIT
 ONLY PLANS FOR SCOPE OF WORK PROPOSED.
 IF WORL IN THIS SCOPE IS FOR BLDG ONLY,
 THNE PLAN REVISE PERMIT APPLICATION AND
 SUBMIT PLANS FOR BLDG ONLY.
 215.5
  
 6)NOTE: PLEASE SEE 250.50 FOR MIN
 REQUIRED GROUNDING ELECTRODE SYSTEM.
 NO DETAIL PROVIDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-06-14 Cont ID  
Sent By mamini Date 2005-06-14 Time 15:22 Rev Time 1.00
Received By mamini Date 2005-06-14 Time 15:22 Sent To  
Notes
2005-06-14 00:00:00PASSED:
  
 1. REVIEWED FOR THE PORTION THAT IS
 LOCATED ON CITY PROPERTY.PER DEAN
 RUNNELS, PERMIT WILL BE ISSUED FOR THAT
 PORTION ONLY.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-01 Cont ID  
Sent By mwennerg Date 2005-09-01 Time 14:33 Rev Time 0.00
Received By mwennerg Date 2005-09-01 Time 14:33 Sent To  
Notes
2005-09-01 00:00:00OK - PLEASE SEE COMMENTS REGARDING 2ND
 SET OF GENERATOR SPECIFICATIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-06-30 Cont ID  
Sent By mwennerg Date 2005-06-30 Time 15:17 Rev Time 0.00
Received By mwennerg Date 2005-06-30 Time 15:16 Sent To  
Notes
2005-06-30 00:00:00******DENIED******
  
 1) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS AND FAC REQUIREMENTS.
  
 2) PLEASE PROVIDE CLARIFICATION FOR
 SCOPE OF WORK AS IT APPLIES TO THE
 PERMIT APPLICATION.
  
 3) IS THERE ANY EMERGENCY VEHICLE ACCESS
 TO ANY STRUCTURE OR FUEL TANK OTHER THAN
 NORTHLAKE BLVD?
  
 4) PLEASE PROVIDE CUT SHEETS FOR FUEL
 TANK AND PRODUCT.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-10-05 Cont ID  
Sent By kstevens Date 2006-10-05 Time 09:40 Rev Time 0.00
Received By kstevens Date 2006-10-05 Time 09:40 Sent To  
Notes
2006-10-05 00:00:00GAS REVISION OK - CHANGED LOCATION OF
 VALVES, GUAGES, FLEX HOSE CONNECTIONS
 ETC.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-09-06 Time 15:02 Rev Time 0.00
Received By adarroug Date 2006-09-06 Time 15:02 Sent To E
Notes
2006-09-06 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 11:12 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 11:12 Sent To Z
Notes
2005-11-14 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-10 Cont ID  
Sent By adarroug Date 2005-11-10 Time 16:42 Rev Time 0.00
Received By adarroug Date 2005-11-10 Time 16:42 Sent To P
Notes
2005-11-10 00:00:00TO "PSCHMITZ" DESK/AS PER "JWITMER"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-19 Cont ID  
Sent By adarroug Date 2005-08-19 Time 11:04 Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 11:04 Sent To  
Notes
2005-08-22 00:00:00TO "COMM" BD#41
2005-08-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-19 Cont ID  
Sent By shill Date 2005-07-19 Time 12:57 Rev Time 0.00
Received By jwitmer Date 2005-06-08 Time 07:03 Sent To  
Notes
2005-06-27 00:00:00MOVED TO BD#6 ADARROUGH
2005-06-10 00:00:00COMM BOARD #60
2005-06-08 00:00:00ON THE TABLE WAITING TO GO ON COMM
 BOARD.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-07-22 Cont ID  
Sent By pkrauss Date 2005-07-22 Time 16:07 Rev Time 0.40
Received By pkrauss Date 2005-07-22 Time 16:07 Sent To  
Notes
2005-07-22 00:00:00PER MEETING W/DESIGN GROUP - UNDERGROUND
 LP TANK (500 GALLON) - APPROVED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-12 Cont ID  
Sent By pkrauss Date 2005-07-12 Time 11:58 Rev Time 0.45
Received By pkrauss Date 2005-07-12 Time 11:58 Sent To  
Notes
2005-07-12 00:00:00PLAN DOES NOT INDICATE DISTANCE FROM THE
 UNDERGROUND LP TANK TO THE PROPERTY
 LINE.SHOW COMPLIANCE WTIH NFPA 58.
 GENERATOR ROOM INDICATED ON PLAN SHEET
 S7 IS CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-11-14 Cont ID  
Sent By pschmitz Date 2005-11-14 Time 10:12 Rev Time 0.00
Received By pschmitz Date 2005-11-14 Time 10:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-08-28 Cont ID  
Sent By pschmitz Date 2005-08-28 Time 10:59 Rev Time 0.00
Received By pschmitz Date 2005-08-28 Time 10:59 Sent To  
Notes
2005-08-28 00:00:00PAUL SCHMITZ, PLUMBING & GAS PLANS
 EXAMINER561-805-6692
  
 [email protected]
 GAS PLAN REVIEW FBC 2001
 DENIED
 1. ONLY ONE SET OF GENERATOR
 SPECIFICATIONS SUBMITTED.
 2.PLEASE ADDRESS COMMENTS BY OTHER PLAN
 REVIEWERS.
 END OF COMMENTS
  
 DENIED
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-06 Cont ID  
Sent By kstevens Date 2005-07-06 Time 18:22 Rev Time 0.60
Received By kstevens Date 2005-07-06 Time 18:22 Sent To  
Notes
2005-07-06 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
  
 A. SUBMIT THE FOLLOWING INFORMATION FOR
 THE GAS PIPING PERMIT:
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 4. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 7. WELDING CERTIFICATIONS, PICTURE I.D.,
 AND WELDING PROCEDURE REQUIRED AT TIME
 OF GAS PERMIT APPLICATION. SEPARATE GAS
 PERMIT REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2005-11-15 Cont ID  
Sent By mmclean Date 2005-11-15 Time 17:30 Rev Time 0.00
Received By mmclean Date 2005-11-15 Time 17:30 Sent To B
Notes
2005-11-15 00:00:00OK TO APPROVE PER GRACE JOYCE, A
 RESOLUTION WAS APPROVED FOR THE PROPSED
 PROJECT, RESOLUTION NUMBER 385-05
 10/24/05

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-01 Cont ID  
Sent By gjoyce Date 2005-09-01 Time 14:58 Rev Time 0.00
Received By gjoyce Date 2005-09-01 Time 14:58 Sent To  
Notes
2005-10-13 00:00:00AGREEMENT TO BE SIGNED BY CIY AT
 COMMISSION ON MONDAY OCT 24TH OK TO
 APPROVE ON TUESDAY OCTOBER 25TH.
2005-09-01 00:00:00NEEDS EASEMENT FROM CITY PER AJVANN