Plan Review Details - Permit 05060127
Plan Review Stops For Permit 05060127
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-23 Cont ID  
Sent By jwitmer Date 2005-08-23 Time 07:38 Rev Time 0.00
Received By jwitmer Date 2005-08-30 Time 06:56 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-26 Cont ID  
Sent By jwitmer Date 2005-06-26 Time 15:43 Rev Time 0.77
Received By jwitmer Date 2005-06-26 Time 15:43 Sent To  
Notes
2005-06-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05060127
 ADD: 500 S AUSTRALIAN AV # 825
 CONT: KARL CORP
 TEL: (561)718-3799
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 2) SHEET A2.1 REFLECTED CEILING PLAN
 MISSING EXIT DIRECTIONAL SIGNAL LIGHTS
 1016.3.1 EXITS SHALL BE MARKED BY AN
 APPROVED SIGN READILY VISIBLE FROM
 ANY DIRECTION OF EXIT ACCESS.EVERY
 EXIT SIGN SHALL BE SUITABLY
 ILLUMINATED BY A RELIABLE LIGHT
 SOURCE.EXTERNALLY AND INTERNALLY
 ILLUMINATED SIGNS SHALL BE VISIBLE IN
 BOTH THE NORMAL AND EMERGENCY
 LIGHTING.
  
 3) TI-1 DOOR DETAIL- BUCKS TO BE:
 609.2.1 TYPE I AND TYPE II
 CONSTRUCTION. PARTITIONS SHALL BE
 CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-07-11 Cont ID  
Sent By dpalmer Date 2005-06-23 Time 10:57 Rev Time 0.00
Received By dpalmer Date 2005-06-23 Time 10:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-30 Cont ID  
Sent By jwitmer Date 2005-08-30 Time 06:57 Rev Time 0.00
Received By jwitmer Date 2005-08-30 Time 06:57 Sent To  
Notes
2005-08-30 00:00:00PASSED PER M. CARCELLO/JW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-06-28 Cont ID  
Sent By mwennerg Date 2005-06-28 Time 14:10 Rev Time 0.00
Received By mwennerg Date 2005-06-28 Time 13:57 Sent To  
Notes
2005-06-28 00:00:00******DENIED******
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED NOT TO EXCEED 75' TRAVEL
 DISTANCE BETWEEN EXTINGUISHERS.
  
 3) ILLUMINATED EXIT SIGNS APPEAR TO BE
 MISSING ON SHEET A-2.1.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-05 Cont ID  
Sent By adarroug Date 2005-08-05 Time 11:37 Rev Time 0.00
Received By adarroug Date 2005-08-05 Time 11:37 Sent To  
Notes
2005-08-08 00:00:00TO "COMM" BD#24
2005-08-05 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-11 Cont ID  
Sent By pkrauss Date 2005-07-11 Time 11:12 Rev Time 0.00
Received By pkrauss Date 2005-06-07 Time 15:55 Sent To  
Notes
2005-06-09 00:00:00TO 'COMM BD#57'
2005-06-07 00:00:00WAITING FOR COMM BOARD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-11 Cont ID  
Sent By pkrauss Date 2005-07-11 Time 10:55 Rev Time 0.35
Received By pkrauss Date 2005-07-11 Time 10:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-07-06 Cont ID  
Sent By kstevens Date 2005-07-06 Time 18:00 Rev Time 0.25
Received By kstevens Date 2005-07-06 Time 18:00 Sent To  
Notes
2005-07-06 00:00:00NO PLUMBING SHOWN ON PLANS