| Plan Review Stops For Permit 05060105 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-08-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-08-27 |
Time |
15:20 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-08-27 |
Time |
15:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-07-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-07-02 |
Time |
10:18 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-07-02 |
Time |
10:18 |
Sent To |
PC |
|
| Notes |
| 2005-08-23 00:00:00 | MECH. NOTES ATTACHED. | | | | | | PR 8/23/05 | | 2005-07-02 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)PROVIDE ANCHORING INFORMATION TO | | | COMPLY WITH FBC1606.1.3; STRUCTURAL | | | MEMBERS AND SYSTEMS, AND COMPONENTS AND | | | CLADDING IN A BUILDING OR STRUCTURE | | | SHALL BE ANCHORED TO RESIST WIND-INDUCED | | | OVERTURNING, UPLIFT AND SLIDING AND TO | | | PROVIDE CONTINUOUS LOAD PATHS FOR THESE | | | FORCES TO THE FOUNDATION.WHERE A | | | PORTION OF THE RESISTANCE TO THESE | | | FORCES IS PROVIDED BY DEAD LOAD, THE | | | MINIMUM DEAD LOAD LIKELY TO BE IN PLACE | | | DURING A DESIGN WIND EVENT SHALL BE | | | USED. | | | | | | 2.)THE VALUE IS TOO LOW.PROVIDE A | | | REASONABLE VALUE OR AN ESTIMATED VALUE | | | WILL BE DONE FOR YOU USING MARSHALL & | | | SWIFT. | | | | | | 3.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED FS713.13. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-08-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-08-12 |
Time |
10:59 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-08-12 |
Time |
10:59 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-06-15 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-06-15 |
Time |
15:29 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-06-15 |
Time |
12:56 |
Sent To |
M |
|
| Notes |
| 2005-06-15 00:00:00 | | | | PLEASE PROVIDE A RISER DIAGRAM | | | INDICATING WHERE THE GENERATOR EQUIPMENT | | | INTERACTS WITH THE SERVICE EQUIPMENT. | | | | | | ALSO SUBMIT A SPEC ON THE TRANSFER | | | SWITCH. | | | | | | SHOW COMPLIANCE WITH 225.32 AND 225.36 & | | | 37. DISCCNNECTING MEANS. | | | | | | THERE MAY BE MORE COMMENTS WHEN | | | REVIEWING RISER DIAGRAM. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-08-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-12 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-12 |
Time |
08:58 |
Sent To |
E |
|
| Notes |
| 2005-08-12 00:00:00 | TO "BTROBAUG" DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-06-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-14 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-14 |
Time |
14:07 |
Sent To |
E |
|
| Notes |
| 2005-06-14 00:00:00 | TO ELEC BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-06-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-07 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-07 |
Time |
10:56 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-08-23 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-08-23 |
Time |
14:11 |
Rev Time |
1.00 |
| Received By |
prafter |
Date |
2005-08-23 |
Time |
14:11 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-06-27 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-06-27 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-06-27 |
Time |
13:50 |
Sent To |
B |
|
| Notes |
| 2005-06-27 00:00:00 | PLAN DENIED | | | 1) PLEASE INDICATE TYPE OF FUEL USED FOR | | | GENERATOR. | | | 2) PLEASE SUBMIT PLAN SHOWING WINDOWS | | | AND LOCATION OF THE GENERATOR. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-08-11 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-08-11 |
Time |
18:52 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-08-11 |
Time |
18:52 |
Sent To |
I |
|
| Notes |
| 2005-08-11 00:00:00 | NOTE: GENERATOR CAN ONLY ENCROACH 4FT | | | INTO SETBACK. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-06-13 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-06-13 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-06-13 |
Time |
18:07 |
Sent To |
I |
|
| Notes |
| 2005-06-13 00:00:00 | DENIED, | | | 1. NEED TO PROVIDE THE SIDE SETBACK OF | | | GENERATOR FROM THE STRUCTURE AND | | | PROPERTY LINE ON TWO COPY OF SURVEY. | | | 2. GENERATOR CAN ONLY ENCROACH 4FT INTO | | | ANY SETBACK. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|