Plan Review Details - Permit 05060105
Plan Review Stops For Permit 05060105
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-27 Cont ID  
Sent By shill Date 2005-08-27 Time 15:20 Rev Time 0.50
Received By shill Date 2005-08-27 Time 15:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-02 Cont ID  
Sent By shill Date 2005-07-02 Time 10:18 Rev Time 0.50
Received By shill Date 2005-07-02 Time 10:18 Sent To PC
Notes
2005-08-23 00:00:00MECH. NOTES ATTACHED.
  
 PR 8/23/05
2005-07-02 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
 2.)THE VALUE IS TOO LOW.PROVIDE A
 REASONABLE VALUE OR AN ESTIMATED VALUE
 WILL BE DONE FOR YOU USING MARSHALL &
 SWIFT.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED FS713.13.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-12 Cont ID  
Sent By btrobaug Date 2005-08-12 Time 10:59 Rev Time 0.50
Received By btrobaug Date 2005-08-12 Time 10:59 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-15 Cont ID  
Sent By btrobaug Date 2005-06-15 Time 15:29 Rev Time 0.50
Received By btrobaug Date 2005-06-15 Time 12:56 Sent To M
Notes
2005-06-15 00:00:00 
 PLEASE PROVIDE A RISER DIAGRAM
 INDICATING WHERE THE GENERATOR EQUIPMENT
 INTERACTS WITH THE SERVICE EQUIPMENT.
  
 ALSO SUBMIT A SPEC ON THE TRANSFER
 SWITCH.
  
 SHOW COMPLIANCE WITH 225.32 AND 225.36 &
 37. DISCCNNECTING MEANS.
  
 THERE MAY BE MORE COMMENTS WHEN
 REVIEWING RISER DIAGRAM.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-12 Cont ID  
Sent By adarroug Date 2005-08-12 Time 08:58 Rev Time 0.00
Received By adarroug Date 2005-08-12 Time 08:58 Sent To E
Notes
2005-08-12 00:00:00TO "BTROBAUG" DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-14 Cont ID  
Sent By shill Date 2005-06-14 Time 14:07 Rev Time 0.00
Received By shill Date 2005-06-14 Time 14:07 Sent To E
Notes
2005-06-14 00:00:00TO ELEC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-07 Cont ID  
Sent By shill Date 2005-06-07 Time 10:56 Rev Time 0.00
Received By shill Date 2005-06-07 Time 10:56 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-23 Cont ID  
Sent By prafter Date 2005-08-23 Time 14:11 Rev Time 1.00
Received By prafter Date 2005-08-23 Time 14:11 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-27 Cont ID  
Sent By hmoser Date 2005-06-27 Time 13:52 Rev Time 0.00
Received By hmoser Date 2005-06-27 Time 13:50 Sent To B
Notes
2005-06-27 00:00:00PLAN DENIED
 1) PLEASE INDICATE TYPE OF FUEL USED FOR
 GENERATOR.
 2) PLEASE SUBMIT PLAN SHOWING WINDOWS
 AND LOCATION OF THE GENERATOR.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-11 Cont ID  
Sent By mmclean Date 2005-08-11 Time 18:52 Rev Time 0.00
Received By mmclean Date 2005-08-11 Time 18:52 Sent To I
Notes
2005-08-11 00:00:00NOTE: GENERATOR CAN ONLY ENCROACH 4FT
 INTO SETBACK.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-13 Cont ID  
Sent By mmclean Date 2005-06-13 Time 18:07 Rev Time 0.00
Received By mmclean Date 2005-06-13 Time 18:07 Sent To I
Notes
2005-06-13 00:00:00DENIED,
 1. NEED TO PROVIDE THE SIDE SETBACK OF
 GENERATOR FROM THE STRUCTURE AND
 PROPERTY LINE ON TWO COPY OF SURVEY.
 2. GENERATOR CAN ONLY ENCROACH 4FT INTO
 ANY SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720