Plan Review Details - Permit 05060090
Plan Review Stops For Permit 05060090
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-16 Cont ID  
Sent By rmcdouga Date 2005-09-16 Time 10:13 Rev Time 0.00
Received By rmcdouga Date 2005-09-16 Time 10:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-09 Cont ID  
Sent By rmcdouga Date 2005-08-09 Time 16:20 Rev Time 0.00
Received By rmcdouga Date 2005-08-09 Time 16:20 Sent To  
Notes
2005-08-09 00:00:00DENIED
  
 1) PROVIDE STRUCTURAL DETAILS FOR THE
 COLUMNS AT THE FRONT PORCH. SEE COMMENT
 #5 ON FIRST REVIEW.
  
 2) REVISE THE ROOF SHEATHING FASTENING
 NOTES ON D1. CITY AMENDMENTS TO FBC
 TABLE 2306.1, REQUIRES 8D COMMON NAILS
 AT 4"OC AT EDGES AND 6"OC INTERMEDIATE
 IN ZONE 3. ZONE 3 INCLUDES THE OUTSIDE
 CORNERS OF HIP ROOFS IN ADDITION TO
 GABLE ENDS. SEE COMMENT #7 ON FIRST
 REVIEW.
  
 3) ON SHEET A3 THE FOOTING STEEL HAS
 BEEN CHANGED FROM ONE #5 TO 2 #5S BY
 REDLINING. REDLINED CHANGES TO THE PLANS
 ARE REQUIRED TO BE INITIALED AND DATED
 BY THE DESIGNER OF RECORD. ALSO PLEASE
 SUBMIT A SIGNED AND SEALED LETTER FROM
 THE DESIGNER OF RECORD LISTING THE
 REDLINE CHANGES HE HAS MADE TO THE
 PLANS.
  
 4) SUBMIT THE PRODUCT EVAULATION REPORT
 (NOA OR OTHER) THAT CORRESPONDS TO THE
 FL PRODUCT APPROVAL COVER SHEET AS
 LISTED ON THE STATE PRODUCT APPROVAL
 WEBSITE FOR THE WINDOW MULLIONS AND
 SLIDING GLASS DOORS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-27 Cont ID  
Sent By rmcdouga Date 2005-06-27 Time 09:06 Rev Time 0.00
Received By rmcdouga Date 2005-06-27 Time 07:22 Sent To  
Notes
2005-06-27 00:00:00DENIED
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE RIGHT SIDE ELEVATION ON A2 DOES
 NOT INDICATE THE THREE WINDOWS THAT ARE
 SPECIFIED ON THE FLOOR PLAN.
  
 4) REVISE THE WALL SECTION ON A3 TO
 COMPLY WITH FBC 1804.1.3 AND CITY
 AMENDMENT 1804.1.7, WHICH REQUIRE THE
 BOTTOM OF THE FOOTING TO BE A MINIMUM OF
 12 INCHES BELOW GRADE AND THE FLOOR
 ELEVATION TO BE A MINIMUM OF 4 INCHES
 ABOVE GRADE.
  
 5) PROVIDE STRUCTURAL DETAILS FOR THE
 COLUMNS AT THE FRONT PORCH.
  
 6) SPECIFY THE LINTEL SIZE AND
 REINFORCEMENT IN THE LINTEL SCHEDULE ON
 A4.
  
 7) REVISE ROOF SHEATHING FASTENING NOTES
 ON D1. CITY AMENDMENT TO FBC TABLE
 2306.1, REQUIRES 8D COMMON NAILS AT
 4"O.C. AT EDGES AND 6"O.C. INTERMEDIATE
 IN ZONE 3. ZONE 3 INCLUDES THE OUTSIDE
 CORNERS OF HIP ROOFS IN ADDITION TO
 GABLE ENDS.
  
 8) SPECIFY ON THE FLOOR PLAN THAT THE
 WALL BETWEEN THE GARAGE AND THE LIVING
 SPACE IS INSULATED AS INDICATED ON THE
 ENERGY CALC. FORM.
  
 9) THE TYPICAL WALL SECTION ON A3 SHOWS
 AN 8X8 BOND BEAM WITH ONE #5 REBAR AND
 D1 HAS A 8X16 BOND BEAM WITH TWO #5
 REBARS. PLEASE CLARIFY.
  
 10) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 COVER SHEETS WITH THE APPROPRIATE FL #
 FOR THE PRODUCT AND THE TESTING AND
 INSTALLATION DRAWINGS THAT WERE
 SUBMITTED AND APPROVED BY THE STATE.
  
 11) SUBMIT PRODUCT APPROVAL FOR THE
 FOLLOWING: STRUCTURAL WINDOW MULLIONS,
 SLIDING GLASS DOOR AND OUTSWING FRONT
 DOOR.
  
 12) SUBMIT (2) COPIES OF A KEY PLAN AND
 AN INSTALLATION SCHEDULE FOR THE STORM
 PANELS. SPECIFY THE TYPE OF MOUNT, THE
 FASTENER TYPE AND FASTENER SPACING.
  
 THE CALCULATED VALUE FOR THE STRUCTURE
 HAS BEEN INCREASED BASED ON SBCCI/ICC
 BUILDING VALUATION DATA. THE NEW VALUE
 IS $142,796. ADDITIONAL PERMIT FEES ARE
 DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-09-22 Cont ID  
Sent By dpalmer Date 2005-09-22 Time 19:10 Rev Time 0.40
Received By dpalmer Date 2005-09-22 Time 18:55 Sent To  
Notes
2005-09-22 00:00:00 
  
  
  
  
  
  
  
 REDLINED 210.52 LIVING RM WALL SPACE.
 ******* NOTE ***********
  
  
 PLEASE HAVE MR. JESUS (JAY) MEDINA PRINT
 NAME AND SIGN EACH COPY OF PLANS.
  
 PLEASE RETAIN ONE COPY ALREADY STAMPED
 AS "FILE COPY" AND GIVE BACK TO DVP.
 PLEASE GIVE "CONTRACTOR'S COPY" TO
 CONTRACTOR.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-08-31 Cont ID  
Sent By dpalmer Date 2005-08-31 Time 19:59 Rev Time 0.60
Received By dpalmer Date 2005-08-31 Time 19:55 Sent To P
Notes
2005-08-31 00:00:00****** PROVISO/ REVISION ********
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATING SHOWN FOR PANEL, HOWEVER NOT
 INDICATED FOR MAIN DISCONNECT.
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 250.110,250.24 AND SIZED PER 250.122
  
 3)NOTE: PLEASE SEE FAN J-BOX IN BEDRMS
 DOES NOT MEET THE REQUIREMENTS OF 210.70
 AND NFPA-101 5-8
 PLEASE SEE AN OUTLET/LT FIXTURES SHALL
 BE PROVIDED.
  
 4)NOTE: PLEASE SEE MIN CLEARENCE
 REQUIRED FOR DISCONNECT FOR AHU.
 110.26
  
 5)NOTE: PLEASE SEE MISSING GFI RECEPT
 REQUIRED IN BATHRM.
 210.52D,210.8, 210.11C3
 MUST BE 20A AND #12 AWG.
  
 6)NOTE: PLEASE PROVIDE ROOM/AREA
 DESIGNATIONS ON PLANS.
  
 PLEASE SUBMIT THE ABOVE REVISED PLANS
 BEFORE ANY ELECTRICAL INSPECTIONS ARE
 CALLED IN.
 THIS INCLUDES ROUGH UNDERGROUND/STEEL
 FOOTING INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER.
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 ********** NOTE *************
  
 IF PLANS ARE RETURNED FOR ANY OTHER
 COMMENTS FROM OTHER TRADES, PLEASE
 ADDRESS "PROVISO" AT THIS TIME.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-26 Cont ID  
Sent By btrobaug Date 2005-07-26 Time 11:43 Rev Time 0.50
Received By btrobaug Date 2005-07-26 Time 10:02 Sent To P
Notes
2005-07-26 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE LOCATION OF THE
 DISCONNECT SHOWN ON THE RISER, ON THE
 PLAN.
  
  
 2} RECEPTACLES IN ALL BEDROOMS NEED
 RELOCATED OR ADDED TO COMPLY WITH
 210.5(A)(1&2)
  
 3) THE PERSON RESPONSIBLE MUST PRINT
 NAME AND SIGN PLANS. IN THE CASE OF A
 DESIGN PROFESSIONAL SEE FS 481.
  
 IF THERE ARE ANY QUESTIONS PLAESE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-24 Cont ID  
Sent By btrobaug Date 2005-06-15 Time 10:12 Rev Time 0.50
Received By btrobaug Date 2005-06-15 Time 06:44 Sent To M
Notes
2005-06-15 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLANS MUST BE SEALED AND SIGNED BY
 THE ARCHITECT PER FS 481.221.
  
 2}THE NOTE REGARDING ARC FAULT SHOULD
 READ "OUTLETS" NOT "RECEPTACLES". ALL
 DEVICES IN THE ROOM MUST BE PROTECTED
 PER 210.12.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 15:23 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 15:23 Sent To E
Notes
2005-09-21 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-30 Cont ID  
Sent By adarroug Date 2005-08-30 Time 08:20 Rev Time 0.00
Received By adarroug Date 2005-08-30 Time 08:20 Sent To E
Notes
2005-08-30 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-18 Cont ID  
Sent By adarroug Date 2005-07-18 Time 15:54 Rev Time 0.00
Received By adarroug Date 2005-07-18 Time 15:54 Sent To E
Notes
2005-07-18 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-14 Cont ID  
Sent By shill Date 2005-06-14 Time 14:19 Rev Time 0.00
Received By shill Date 2005-06-14 Time 14:19 Sent To E
Notes
2005-06-14 00:00:00TO RESIDENTIAL RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-03 Cont ID  
Sent By shill Date 2005-06-27 Time 09:06 Rev Time 0.00
Received By rmcdouga Date 2005-06-03 Time 15:25 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-09-09 Cont ID  
Sent By tgordon Date 2005-09-09 Time 15:06 Rev Time 0.30
Received By tgordon Date 2005-09-09 Time 15:06 Sent To B
Notes
2005-09-09 00:00:00*** PROVISO ***
 1) COPPER LINES SHELL BE SIZED PER
 MENUFACTURER SPECIFICATIONS.
 2) DRAIN LINE SHELL TREMINATE 12" FROM
 THE BULDING. PER 2001 FBC 1503.4.4 .
 3) OVERFLOW DEVICE SHELL BE INSTALLED
 AT AUXILIARY DRAIN TO AHU.
 PER 2001 FBC/M 307.2.4 .
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-08-01 Cont ID  
Sent By rregueir Date 2005-08-01 Time 17:47 Rev Time 0.00
Received By rregueir Date 2005-08-01 Time 17:47 Sent To B
Notes
2005-08-01 00:00:00--------------DENIED--------------------
  
 PLANS REQUIRE PRINTED NAME AND SIGNATURE
 OF PERSON RESPONSIBLE FOR DESIGN.IF
 PERSON RESPONSIBLE IS AN ARCHITECT OR
 ENGINEER (AS INDICATED BY PRESENCE OF
 ARCHITECT'S TITLE BLOCK), SEE FS 481.
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-06-17 Cont ID  
Sent By btrobaug Date 2005-06-24 Time 16:43 Rev Time 0.00
Received By hmoser Date 2005-06-17 Time 17:21 Sent To P
Notes
2005-06-17 00:00:00NO PLANS

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-09-09 Cont ID  
Sent By jleech Date 2005-09-09 Time 12:33 Rev Time 0.33
Received By jleech Date 2005-09-09 Time 12:33 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-07-26 Cont ID  
Sent By jleech Date 2005-07-26 Time 14:35 Rev Time 0.50
Received By jleech Date 2005-07-26 Time 14:35 Sent To M
Notes
2005-07-26 00:00:00DENIED;
 1.SEE ELECTRICAL PLAN REVIEW NOTE 1.
 2.W/M DISCHARGE SHALL BE DOWN STREAM OF
 A BATHROOM GROUP. SEC 909.1.
 3.C.O. REQUIRED ON W/M STACK 48" ABOVE
 FINISH FLOOR.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-18 Cont ID  
Sent By jleech Date 2005-06-18 Time 08:09 Rev Time 0.33
Received By jleech Date 2005-06-18 Time 08:09 Sent To B
Notes
2005-06-18 00:00:00DENIED;
 W/M STACK MISSING FROM RISER DIAGRAM.
 MASTER BATHROOM HAS 2 LAVS. PLEASE SHOW
 BOTH ON RISER DIAGRAM.
 MARK ON PLAN THAT C.O. IS TO BE A TWO
 WAY .
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2005-06-13 Cont ID  
Sent By mmclean Date 2005-06-13 Time 17:42 Rev Time 0.00
Received By mmclean Date 2005-06-13 Time 17:42 Sent To I
Notes
2005-06-13 00:00:00DON'T HAVE ANY RECOLLECTION OF SIGNING
 IT THE FIRST TIME.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-09 Cont ID  
Sent By mmclean Date 2005-06-07 Time 11:32 Rev Time 0.00
Received By mmclean Date 2005-06-07 Time 11:32 Sent To B
Notes
2005-06-07 00:00:00RETURNED TO DEAN RUNNELS, LICENSE &
 PERMIT SUPERVISOR