| Plan Review Stops For Permit 05060090 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-09-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-09-16 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-09-16 |
Time |
10:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-08-09 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-08-09 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2005-08-09 00:00:00 | DENIED | | | | | | 1) PROVIDE STRUCTURAL DETAILS FOR THE | | | COLUMNS AT THE FRONT PORCH. SEE COMMENT | | | #5 ON FIRST REVIEW. | | | | | | 2) REVISE THE ROOF SHEATHING FASTENING | | | NOTES ON D1. CITY AMENDMENTS TO FBC | | | TABLE 2306.1, REQUIRES 8D COMMON NAILS | | | AT 4"OC AT EDGES AND 6"OC INTERMEDIATE | | | IN ZONE 3. ZONE 3 INCLUDES THE OUTSIDE | | | CORNERS OF HIP ROOFS IN ADDITION TO | | | GABLE ENDS. SEE COMMENT #7 ON FIRST | | | REVIEW. | | | | | | 3) ON SHEET A3 THE FOOTING STEEL HAS | | | BEEN CHANGED FROM ONE #5 TO 2 #5S BY | | | REDLINING. REDLINED CHANGES TO THE PLANS | | | ARE REQUIRED TO BE INITIALED AND DATED | | | BY THE DESIGNER OF RECORD. ALSO PLEASE | | | SUBMIT A SIGNED AND SEALED LETTER FROM | | | THE DESIGNER OF RECORD LISTING THE | | | REDLINE CHANGES HE HAS MADE TO THE | | | PLANS. | | | | | | 4) SUBMIT THE PRODUCT EVAULATION REPORT | | | (NOA OR OTHER) THAT CORRESPONDS TO THE | | | FL PRODUCT APPROVAL COVER SHEET AS | | | LISTED ON THE STATE PRODUCT APPROVAL | | | WEBSITE FOR THE WINDOW MULLIONS AND | | | SLIDING GLASS DOORS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-06-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-06-27 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-06-27 |
Time |
07:22 |
Sent To |
|
|
| Notes |
| 2005-06-27 00:00:00 | DENIED | | | 1)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 3) THE RIGHT SIDE ELEVATION ON A2 DOES | | | NOT INDICATE THE THREE WINDOWS THAT ARE | | | SPECIFIED ON THE FLOOR PLAN. | | | | | | 4) REVISE THE WALL SECTION ON A3 TO | | | COMPLY WITH FBC 1804.1.3 AND CITY | | | AMENDMENT 1804.1.7, WHICH REQUIRE THE | | | BOTTOM OF THE FOOTING TO BE A MINIMUM OF | | | 12 INCHES BELOW GRADE AND THE FLOOR | | | ELEVATION TO BE A MINIMUM OF 4 INCHES | | | ABOVE GRADE. | | | | | | 5) PROVIDE STRUCTURAL DETAILS FOR THE | | | COLUMNS AT THE FRONT PORCH. | | | | | | 6) SPECIFY THE LINTEL SIZE AND | | | REINFORCEMENT IN THE LINTEL SCHEDULE ON | | | A4. | | | | | | 7) REVISE ROOF SHEATHING FASTENING NOTES | | | ON D1. CITY AMENDMENT TO FBC TABLE | | | 2306.1, REQUIRES 8D COMMON NAILS AT | | | 4"O.C. AT EDGES AND 6"O.C. INTERMEDIATE | | | IN ZONE 3. ZONE 3 INCLUDES THE OUTSIDE | | | CORNERS OF HIP ROOFS IN ADDITION TO | | | GABLE ENDS. | | | | | | 8) SPECIFY ON THE FLOOR PLAN THAT THE | | | WALL BETWEEN THE GARAGE AND THE LIVING | | | SPACE IS INSULATED AS INDICATED ON THE | | | ENERGY CALC. FORM. | | | | | | 9) THE TYPICAL WALL SECTION ON A3 SHOWS | | | AN 8X8 BOND BEAM WITH ONE #5 REBAR AND | | | D1 HAS A 8X16 BOND BEAM WITH TWO #5 | | | REBARS. PLEASE CLARIFY. | | | | | | 10) PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SUBMIT | | | COVER SHEETS WITH THE APPROPRIATE FL # | | | FOR THE PRODUCT AND THE TESTING AND | | | INSTALLATION DRAWINGS THAT WERE | | | SUBMITTED AND APPROVED BY THE STATE. | | | | | | 11) SUBMIT PRODUCT APPROVAL FOR THE | | | FOLLOWING: STRUCTURAL WINDOW MULLIONS, | | | SLIDING GLASS DOOR AND OUTSWING FRONT | | | DOOR. | | | | | | 12) SUBMIT (2) COPIES OF A KEY PLAN AND | | | AN INSTALLATION SCHEDULE FOR THE STORM | | | PANELS. SPECIFY THE TYPE OF MOUNT, THE | | | FASTENER TYPE AND FASTENER SPACING. | | | | | | THE CALCULATED VALUE FOR THE STRUCTURE | | | HAS BEEN INCREASED BASED ON SBCCI/ICC | | | BUILDING VALUATION DATA. THE NEW VALUE | | | IS $142,796. ADDITIONAL PERMIT FEES ARE | | | DUE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2005-09-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-22 |
Time |
19:10 |
Rev Time |
0.40 |
| Received By |
dpalmer |
Date |
2005-09-22 |
Time |
18:55 |
Sent To |
|
|
| Notes |
| 2005-09-22 00:00:00 | | | | | | | | | | | | | | | | | | | | | | | | | REDLINED 210.52 LIVING RM WALL SPACE. | | | ******* NOTE *********** | | | | | | | | | PLEASE HAVE MR. JESUS (JAY) MEDINA PRINT | | | NAME AND SIGN EACH COPY OF PLANS. | | | | | | PLEASE RETAIN ONE COPY ALREADY STAMPED | | | AS "FILE COPY" AND GIVE BACK TO DVP. | | | PLEASE GIVE "CONTRACTOR'S COPY" TO | | | CONTRACTOR. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-08-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-31 |
Time |
19:59 |
Rev Time |
0.60 |
| Received By |
dpalmer |
Date |
2005-08-31 |
Time |
19:55 |
Sent To |
P |
|
| Notes |
| 2005-08-31 00:00:00 | ****** PROVISO/ REVISION ******** | | | | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | AIC RATING SHOWN FOR PANEL, HOWEVER NOT | | | INDICATED FOR MAIN DISCONNECT. | | | | | | 2)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN TO PANEL. | | | 250.110,250.24 AND SIZED PER 250.122 | | | | | | 3)NOTE: PLEASE SEE FAN J-BOX IN BEDRMS | | | DOES NOT MEET THE REQUIREMENTS OF 210.70 | | | AND NFPA-101 5-8 | | | PLEASE SEE AN OUTLET/LT FIXTURES SHALL | | | BE PROVIDED. | | | | | | 4)NOTE: PLEASE SEE MIN CLEARENCE | | | REQUIRED FOR DISCONNECT FOR AHU. | | | 110.26 | | | | | | 5)NOTE: PLEASE SEE MISSING GFI RECEPT | | | REQUIRED IN BATHRM. | | | 210.52D,210.8, 210.11C3 | | | MUST BE 20A AND #12 AWG. | | | | | | 6)NOTE: PLEASE PROVIDE ROOM/AREA | | | DESIGNATIONS ON PLANS. | | | | | | PLEASE SUBMIT THE ABOVE REVISED PLANS | | | BEFORE ANY ELECTRICAL INSPECTIONS ARE | | | CALLED IN. | | | THIS INCLUDES ROUGH UNDERGROUND/STEEL | | | FOOTING INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER. | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | ********** NOTE ************* | | | | | | IF PLANS ARE RETURNED FOR ANY OTHER | | | COMMENTS FROM OTHER TRADES, PLEASE | | | ADDRESS "PROVISO" AT THIS TIME. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-07-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-07-26 |
Time |
11:43 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-07-26 |
Time |
10:02 |
Sent To |
P |
|
| Notes |
| 2005-07-26 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE INDICATE THE LOCATION OF THE | | | DISCONNECT SHOWN ON THE RISER, ON THE | | | PLAN. | | | | | | | | | 2} RECEPTACLES IN ALL BEDROOMS NEED | | | RELOCATED OR ADDED TO COMPLY WITH | | | 210.5(A)(1&2) | | | | | | 3) THE PERSON RESPONSIBLE MUST PRINT | | | NAME AND SIGN PLANS. IN THE CASE OF A | | | DESIGN PROFESSIONAL SEE FS 481. | | | | | | IF THERE ARE ANY QUESTIONS PLAESE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-06-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-06-15 |
Time |
10:12 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-06-15 |
Time |
06:44 |
Sent To |
M |
|
| Notes |
| 2005-06-15 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLANS MUST BE SEALED AND SIGNED BY | | | THE ARCHITECT PER FS 481.221. | | | | | | 2}THE NOTE REGARDING ARC FAULT SHOULD | | | READ "OUTLETS" NOT "RECEPTACLES". ALL | | | DEVICES IN THE ROOM MUST BE PROTECTED | | | PER 210.12. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-09-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-21 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-21 |
Time |
15:23 |
Sent To |
E |
|
| Notes |
| 2005-09-21 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-08-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-30 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-30 |
Time |
08:20 |
Sent To |
E |
|
| Notes |
| 2005-08-30 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-07-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-18 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-18 |
Time |
15:54 |
Sent To |
E |
|
| Notes |
| 2005-07-18 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-06-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-14 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-14 |
Time |
14:19 |
Sent To |
E |
|
| Notes |
| 2005-06-14 00:00:00 | TO RESIDENTIAL RACK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-06-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-27 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-06-03 |
Time |
15:25 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2005-09-09 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-09-09 |
Time |
15:06 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2005-09-09 |
Time |
15:06 |
Sent To |
B |
|
| Notes |
| 2005-09-09 00:00:00 | *** PROVISO *** | | | 1) COPPER LINES SHELL BE SIZED PER | | | MENUFACTURER SPECIFICATIONS. | | | 2) DRAIN LINE SHELL TREMINATE 12" FROM | | | THE BULDING. PER 2001 FBC 1503.4.4 . | | | 3) OVERFLOW DEVICE SHELL BE INSTALLED | | | AT AUXILIARY DRAIN TO AHU. | | | PER 2001 FBC/M 307.2.4 . | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2005-08-01 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2005-08-01 |
Time |
17:47 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2005-08-01 |
Time |
17:47 |
Sent To |
B |
|
| Notes |
| 2005-08-01 00:00:00 | --------------DENIED-------------------- | | | | | | PLANS REQUIRE PRINTED NAME AND SIGNATURE | | | OF PERSON RESPONSIBLE FOR DESIGN.IF | | | PERSON RESPONSIBLE IS AN ARCHITECT OR | | | ENGINEER (AS INDICATED BY PRESENCE OF | | | ARCHITECT'S TITLE BLOCK), SEE FS 481. | | | | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-06-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-06-24 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-06-17 |
Time |
17:21 |
Sent To |
P |
|
| Notes |
| 2005-06-17 00:00:00 | NO PLANS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2005-09-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-09-09 |
Time |
12:33 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2005-09-09 |
Time |
12:33 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-07-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-07-26 |
Time |
14:35 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-07-26 |
Time |
14:35 |
Sent To |
M |
|
| Notes |
| 2005-07-26 00:00:00 | DENIED; | | | 1.SEE ELECTRICAL PLAN REVIEW NOTE 1. | | | 2.W/M DISCHARGE SHALL BE DOWN STREAM OF | | | A BATHROOM GROUP. SEC 909.1. | | | 3.C.O. REQUIRED ON W/M STACK 48" ABOVE | | | FINISH FLOOR. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-06-18 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-06-18 |
Time |
08:09 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2005-06-18 |
Time |
08:09 |
Sent To |
B |
|
| Notes |
| 2005-06-18 00:00:00 | DENIED; | | | W/M STACK MISSING FROM RISER DIAGRAM. | | | MASTER BATHROOM HAS 2 LAVS. PLEASE SHOW | | | BOTH ON RISER DIAGRAM. | | | MARK ON PLAN THAT C.O. IS TO BE A TWO | | | WAY . | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-06-13 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-06-13 |
Time |
17:42 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-06-13 |
Time |
17:42 |
Sent To |
I |
|
| Notes |
| 2005-06-13 00:00:00 | DON'T HAVE ANY RECOLLECTION OF SIGNING | | | IT THE FIRST TIME. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-06-07 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-06-07 |
Time |
11:32 |
Sent To |
B |
|
| Notes |
| 2005-06-07 00:00:00 | RETURNED TO DEAN RUNNELS, LICENSE & | | | PERMIT SUPERVISOR |
|
|