Plan Review Details - Permit 05060079
Plan Review Stops For Permit 05060079
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-02-06 Cont ID  
Sent By jwitmer Date 2006-02-06 Time 11:16 Rev Time 0.33
Received By jwitmer Date 2006-02-06 Time 11:16 Sent To PC
Notes
2006-02-06 00:00:00REV# 2

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-06 Cont ID  
Sent By jwitmer Date 2005-09-06 Time 11:40 Rev Time 0.77
Received By jwitmer Date 2005-09-06 Time 11:36 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-08 Cont ID  
Sent By jwitmer Date 2005-08-08 Time 11:21 Rev Time 0.33
Received By jwitmer Date 2005-08-08 Time 11:21 Sent To Z
Notes
2005-08-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05060079
 ADD: 200 NORTHPOINT PRKWY
 CONT: KNIGHT ELEC
 TEL: (561)662-4444
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION:DENIED
  
 1) FIRST REVIEW APPROVED,
 ONLY ONE SET OF ASP-1 SUBMITTED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-06-17 Cont ID  
Sent By jwitmer Date 2005-06-17 Time 14:33 Rev Time 0.55
Received By jwitmer Date 2005-06-17 Time 14:33 Sent To  
Notes
2005-06-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05060079
 ADD: 200 NORTHPOINT PARKWAY
 CONT: J.P.HURBON
 TEL: (561)685-4356
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 NOTE!!!!!!!!!!
  
  
 3109.1.2 FLOODPLAIN MANAGEMENT
 CONSTRUCTION STANDARDS. THIS CODE
 SPECIFICALLY DEFERS TO THE AUTHORITY
 GRANTED TO LOCAL GOVERNMENT BY TITLE
 44 CFR, SECTIONS 59 AND 60.THIS CODE
 IS NOT INTENDED TO SUPPLANT OR
 SUPERCEDE LOCAL ORDINANCES ADOPTED
 PURSUANT TO THAT AUTHORITY, NOR ARE
 LOCAL FLOODPLAIN MANAGEMENT ORDINANCES
 TO BE DEEMED AMENDMENTS TO THE
 CODE.
  
 LOCATED IN A A8 FLOOD ZONE BASE FLOOD
 ELEVATION, TOP OF SLAB IS 15'-6".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-01 Cont ID  
Sent By dpalmer Date 2005-09-01 Time 18:03 Rev Time 0.60
Received By dpalmer Date 2005-09-01 Time 18:03 Sent To  
Notes
2005-09-01 00:00:00REDLINED SPEC BOOKS FROM 310KW TO 300KW
 GEN.
 REDLINED CHANGE IN ATS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-03 Cont ID  
Sent By dpalmer Date 2005-08-03 Time 20:33 Rev Time 1.25
Received By dpalmer Date 2005-08-03 Time 20:18 Sent To  
Notes
2005-08-03 00:00:00IN ELECTRIC FOR REVIEW.
 CALLED CONTRACTOR TO GO OVER ELECTRICAL
 PLANS SUBMITTED. NO SPECS FOR ATS , ETC
 SUBMITTED.
 ENGINEER TO BE CALLED BY CONTRACTOR TO
 GO OVER ELECTRICAL.
 ****** UNSAT 2ND REVIEW ******
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 THESE ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW AND RESPONSE LTR SUBMITTED.
  
 1)NOTE: NOTE #1, OK.
  
 2)NOTE: NOTE #2, OK, EXCEPTION FOR OCP
 AT GEN OK.
  
 3)NOTE: NOTE #3, NO, PLEASE SEE SPEC
 BOOKS WERE SUBMITTED SHOWING A DIFFERENT
 RATING.
 PLEASE NOW, SEE ALL SPECS FOR GENERATOR,
 SUB-BASE FUEL TANK, ATS ETC WERE NOT
 SUBMITTED BACK WITH PLANS AND PERMIT
 APPLICATION. THIS IS REQUIRED FOR
 REVIEW.
  
 4)NOTE: NOTE #4 NO,PLEASE SEE
 225.31,-225.36 AS NOTED ON PREVIOUS
 REVIEW.THE DISCONNECTING MEANS ON
 GENERATOR IS NOT AN ACCEPTABLE MEANS OF
 DISCONNECT REQUIRED.
  
 5)NOTE: NOTE #5 NO. PREVIOUS NOTES.
 225.36
  
 6)NOTE: NOTE #6, OK, CORRECTED.
  
 7)NOTE: NOTE #7 NO. PLEASE SEE RESPONSE
 LTR MENTIONS "NO SPECS SUBIMTTED" ,
 HOWEVER PLEASE CONTACT ELECTRICAL
 CONTRACTOR AS REQUIRED SPECS WERE INDEED
 SUBMITTTED FOR REVIEW ON ORIGINAL
 SUBMITTED PACKAGE.
 GROUND FOR FOOTER STEEL ADDED, OK.
 NOTE FOR GENERATOR BEING A "SEPARATELY
 DERIVED SYSTEM" SHOULD BE ADDED TO
 RISER. IT IS KNOWN THAT THE ATSSHOWN
 ON PLANS IS A 4-POLE ATS FOR SEPARATELY
 DERIVED SYSTEMAND ALSO NOTED THATTHE
 NEUTRAL TO GROUNDWAS SHOWN TO NEW
 GROUNDING ELECTRODE SYSTEM. PLEASE SEE
 SPECS SUBMITTED, (NOT PART OF ENGINEER'S
 PLANS) INDICATED A 3-POLE ATS AND WAS
 THE REASON FOR COMMENT.
  
 NEW NOTE:
  
 8)NOTE: PLEASE SEE ONLY ONE COPY OF
 ORIGINALASP-1/A_1 SHEETS/SETS WERE
 SUBMITTED. IT IS NOTED THAT NEW A-1
 SHEETS WERE SUBMITTED, HOWEVER 2ND COPY
 OF ASP-1 WAS NOT SUBMITTED BACK WITH
 SET.
  
 *************************************
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT TWO COMPLETE SETS FOR
 REVIEW AND STMAPING.
 ONCE AGAIN, IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-22 Cont ID  
Sent By dpalmer Date 2005-06-22 Time 14:35 Rev Time 2.00
Received By dpalmer Date 2005-06-22 Time 14:35 Sent To  
Notes
2005-06-22 00:00:00**********UNSAT **************
  
 1)NOTE: PLEASE SEE 250.30 FOR GROUNDING
 OF TRANSFORMER AS SHOWN.
 PLEASE SEE THIS MUST ALSO TIE INOT
 EXISTING EFFECTIVE GROUNDING ELECTRODE
 SYSTEM.
  
 2)NOTE: PLEASE SEE 445.13 FIR MIN SIZING
 OF CONDUCTORS FROM GEN.
 PLEASE SEE 310.16
  
 3)NOTE: PLEASE CORRELATE KW RATING OF
 GEN. FROM PLANS TO SPEC BOOK SUBMITTED.
 310,300?
 215.5
  
 4)NOTE: PLEASE SEE A MAIN OR MCB IN
 EHVAC WILL BE REQUIRED. PLEASE SEE
 225.31-225.36
 PLEASE INDICATE HOW AND WHICH METHOD OF
 DISCONNECT WILL BE TAKEN.
  
 5)NOTE: PLEASE SEE SPECS FOR TRANSFER
 SWITCH SUBMITTED DOES NOT INDICATE IF
 EQUIPMENT IS "SERVICE ENT RATED".
 215.5
  
 6)NOTE: PLEASE SEE 450.3 FOR AS MAX OCP
 FOR TRANSFORMER TO BE 125%.
  
 7)NOTE: PLEASE VERIFY NEW GEN SHOWN
 INDICATES BEING A SEPARATELY DERIVED
 SYSTEM, HOWEVER AN EQUIPMENT GROUNDING
 CONDUCTOR IS BEING SHOWN FROM GEN TO
 EXIST SYSTEM?
 PLEASE ALSO SEE ONLY GRND ROD IS SHOWN?
 PLEASE SEE ANY NEW FOOTER STEEL WILL
 ALSO BE REQUIRED TO BE BONDED AND OR
 USED AS THE GROUNDING ELECTRODE IF IT
 MEETS 250.50.
 PLEASE ALSO SEE SPEC BOOK INDICATES A
 3POLE ATS?
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-06-23 Cont ID  
Sent By mamini Date 2005-06-23 Time 08:31 Rev Time 0.50
Received By mamini Date 2005-06-23 Time 08:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-06-30 Cont ID  
Sent By mwennerg Date 2005-06-30 Time 10:40 Rev Time 0.00
Received By mwennerg Date 2005-06-30 Time 10:21 Sent To  
Notes
2005-06-30 00:00:00******APPROVED******
  
  
 ALL WORK TO COMPLY WITH THE REQUIREMENTS
 OF NFPA 110.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-19 Cont ID  
Sent By adarroug Date 2006-01-19 Time 10:27 Rev Time 0.00
Received By adarroug Date 2006-01-19 Time 10:27 Sent To B
Notes
2006-01-19 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-31 Cont ID  
Sent By adarroug Date 2005-08-31 Time 13:22 Rev Time 0.00
Received By adarroug Date 2005-08-31 Time 13:22 Sent To  
Notes
2005-08-31 00:00:00TO "COMM" BD#24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-29 Cont ID  
Sent By adarroug Date 2005-07-29 Time 14:29 Rev Time 0.00
Received By adarroug Date 2005-07-29 Time 14:29 Sent To  
Notes
2005-08-02 00:00:00TO "COMM" BD#9
2005-07-29 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-11 Cont ID  
Sent By shill Date 2005-07-11 Time 16:06 Rev Time 0.00
Received By pkrauss Date 2005-06-02 Time 15:39 Sent To  
Notes
2005-06-10 00:00:00TO COMM BOARD #36
2005-06-02 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-11 Cont ID  
Sent By pkrauss Date 2005-07-11 Time 16:05 Rev Time 0.55
Received By pkrauss Date 2005-07-11 Time 16:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-07-06 Cont ID  
Sent By kstevens Date 2005-07-06 Time 17:24 Rev Time 0.26
Received By kstevens Date 2005-07-06 Time 17:24 Sent To  
Notes
2005-07-06 00:00:00NO NATURAL OR LP GAS FOR GENERATOR

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-29 Cont ID  
Sent By alongo Date 2005-08-29 Time 15:48 Rev Time 0.00
Received By alongo Date 2005-08-29 Time 15:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-14 Cont ID  
Sent By alongo Date 2005-07-14 Time 14:57 Rev Time 0.00
Received By alongo Date 2005-07-14 Time 14:56 Sent To  
Notes
2005-07-14 00:00:00PLEASE REVEIW AND PROVIDE LETTER OF
 APPROVAL FROM THE NORTHPOINT
 ARCHITECTURAL REVIEW COMMITTEE.
  
 A HEDGE MUST BE PLANTED TO SCREEN ALL
 MECHANICAL EQUIPMENT FROM VIEW FROM ALL
 THOROUGHFARES, THE HEDGE IS SUBJECT TO
 THE REQUIREMENT OF SUBSECTION 94-445(4)E