Plan Review Details - Permit 05060026
Plan Review Stops For Permit 05060026
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-30 Cont ID  
Sent By jwitmer Date 2005-08-30 Time 14:56 Rev Time 0.55
Received By jwitmer Date 2005-08-30 Time 14:56 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-23 Cont ID  
Sent By jwitmer Date 2005-08-23 Time 08:51 Rev Time 0.77
Received By jwitmer Date 2005-08-23 Time 08:34 Sent To PC
Notes
2005-08-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05060026
 ADD: 1226 ROEBUCK CT
 CONT: HMR FABRICATION
 TEL: (561)(386)749-9307
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMMENT # 1 FROM THE PEVIOUS REVIEW,
 UNDER THE PERMIT APPLIED FOR THE
 CONTRACTOR HMR FABRICAION IS USING THE
 NAME SHAWN MARTIN AS THE QUALIFIER THE
 STATE INDICATES HENRY ELKIN TORNWALL AS
 THE QUALIFIER. WE DO NOT HAVE SHAUN R
 MARTIN AS AN AUTHERIZED AGENT TO PULL
 PERMITS. FOR THE CBC LICENSE SHAUN R
 MARTIN IS THE QUALIFIER.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-26 Cont ID  
Sent By jwitmer Date 2005-06-26 Time 14:49 Rev Time 0.77
Received By jwitmer Date 2005-06-26 Time 14:44 Sent To  
Notes
2005-06-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05060026
 ADD: 1226 ROEBUCK CT
 CONT:HMR FABRICATION
 TEL: (386)749-4907
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A) THE COMPANY THAT HAS MADE
 APPLICATION FOR INSTALLTION OF A SPRAY
 BOOTH AND STRUCTURAL CHANGES TO THE CBS
 BUILDING DOES NOT MATCH WITH THE LICENSE
 FOR A SHEET METAL CONTRACTORNOR DOES THE
 QUALIFIER OF THE SHEET METAL COMPANY
 MATCHTHE SIGNATURE OF THE PERMIT
 APPLICATION.
  
 1B) A SHEET METAL CONTRACTOR WILL BE
 WORKING OUT OF THE SCOPE OF LICENSE WHEN
 WORKING ON A CBS TYPE BUILDING
 489.105D).
  
 2) MOLYET ENGINEERING LLC-471.023 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF
 AN ENGINEER PRACTICING UNDER A
 FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER. ADD THE NUMBER
 TO EACH SHEET.THIS MAY BE ADDED BY
 HAND.
  
 3) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) ENGINEER TO PROVIDE DATA ON HOW THE
 EXISTING BEAM WITH NO HOOPS AND
 SUPPORTED BY A BLOCK WALL WILL STILL
 HOLD THE ROOF LOADS WITHOUT ANY
 ADDITIONAL REINFORCEMENT. PROVIDE WHAT
 TYPE OF ROOF STRUCTURE EXIST, SPAN AND
 LOADINGOF THIS AREA OF BEAM?
  
 5A) THE OTHER ISSUE IS THE VERTICAL #5
 REBAR, HOW DEEP DOES THE BAR HAVE TO BE
 DRILLED INTO THE SLAB & BEAM? WILL EPOXY
 BE REQUIRED? THE THIRD QUESTION IS HOW
 MUCH OF A CELL IS REQUIRED?
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-11 Cont ID  
Sent By dpalmer Date 2005-08-11 Time 17:32 Rev Time 0.50
Received By dpalmer Date 2005-08-11 Time 17:23 Sent To  
Notes
2005-08-11 00:00:00REDLINED,
 AREAS AROUND BOOTH PER NEC 516.
 NOT SHOWN ON PLANS?

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-15 Cont ID  
Sent By dpalmer Date 2005-06-15 Time 18:11 Rev Time 0.33
Received By dpalmer Date 2005-06-15 Time 18:10 Sent To  
Notes
2005-06-15 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE SEE PLANS REFERENCE A
 2003 NEC/ NFPA-70.
 PLEASE SEE WE ARE UNDER THE 2002 NEC AND
 A 2003 EDITION DOES NOT EXSIT.
 (MISPRINT).
  
 2)NOTE: PLEASE SEE FAC 61G1-16.004, FAC
 61G15-23.002, ALL PLANS WHICH ARE
 SIGNED, DATED AND SEALED BY AN ARCH OR
 ENGINEER IS REQUIRED TO HAVE TITLE
 BLOCKS WITH AS INFORMATION AS REQUIRED
 IN ARTICLES QUOTED ABOVE.
 PLEASE ALSO SEE FS 471.023 FOR CERT OF
 AUTH # REQUIRED.
  
 3)NOTE: PLEASE PROVIDE LAYOUT OF AREAS
 CONTAINED IN NEC 516 AND LIST AREAS.
  
 4)NOTE: PLEASE SEE ELECTRICAL PLANS
 SUBMITTED. PLEASE SEE PANEL SCHEDULE
 MENTIONS CONTINOUS @94%??
 PLEASE SEE ANY CONTINUOUS LOADS ARE TO
 BE SHOWN @ 125%.215.3,230.42 ETC.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 EELCTRICAL PLANS.
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-18 Cont ID  
Sent By mwennerg Date 2005-08-18 Time 14:14 Rev Time 0.00
Received By mwennerg Date 2005-08-18 Time 14:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-06-16 Cont ID  
Sent By mwennerg Date 2005-06-16 Time 13:57 Rev Time 0.00
Received By mwennerg Date 2005-06-16 Time 13:57 Sent To  
Notes
2005-06-16 00:00:00****DENIED****
  
 1) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FAC REQUIREMENTS FOR TITLE
 BLOCKS.
  
 2) NO SMOKING OR OPEN FLAME SIGNS ARE TO
 BE POSTED IN THE AREAS OF SPRAYING AND
 FLAMMABLE/COMBUSTIBLE MATERIAL STORAGE
 IN LARGE LETTERS CONTRASTING WITH THE
 BACKGROUND.
  
 3) 2A-10 B,C RATED FIRE EXTINGUISHERS
 ARE REQUIRED IN THE AREA OF THE BOOTH
 AND STORAGE FACILITY.
  
 4) PLEASE PROVIDE MORE INFORMATION AND
 DETAILS IN REGARDS TO OPENINGS AND
 COMBUSTIBLE MATERIAL DISTANCES TO THE
 EXHAUST DISCHARGE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-08 Cont ID  
Sent By adarroug Date 2005-08-08 Time 15:20 Rev Time 0.00
Received By adarroug Date 2005-08-08 Time 15:20 Sent To  
Notes
2005-08-08 00:00:00TO "COMM" BD#10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-13 Cont ID  
Sent By mmclean Date 2005-07-13 Time 11:20 Rev Time 0.00
Received By mmclean Date 2005-06-02 Time 13:49 Sent To  
Notes
2005-06-02 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-22 Cont ID  
Sent By pkrauss Date 2005-08-22 Time 15:12 Rev Time 0.45
Received By pkrauss Date 2005-08-22 Time 14:20 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-07-12 Cont ID  
Sent By pkrauss Date 2005-07-12 Time 09:13 Rev Time 0.55
Received By pkrauss Date 2005-07-12 Time 08:59 Sent To  
Notes
2005-07-12 00:00:00DENIED:
 1.PROVIDE DISTANCES TO PROPERTY LINES
 OR ADJACENT BUILDINGS.
  
 2.ADDITIONAL PERMIT REQUIRED FOR THE
 FIRE SUPPRESSION.
  
 3.PLAN SHEET LISTED UNDER "CODE
 INFORMATION" NFPA 86 FOR OVENS AND
 FURNACES.WILL THIS ALSO CONTAIN A
 DRYING BOOTH?
  
 4.PROVIDE CLEARANCES TO COMBUSTIBLES.
  
 5.PLEASE PROVIDE INFORMATION ON THE
 EXISTING VENTILATION FOR THE BUILDING
 SHOP AREA.
  
 SEE COMMENTS #1A, 1B, #2 BY JIM WITMER,
 BUILDING PLANS EXAMINER.
  
 PLEASE PROVIDE WRITTEN RESPONSE TO
 COMMENTS TO HELP EXPEDITE RE-SUBMITTAL.
  
 IF YOU HAVE ANY QUESTIONS. PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-07-13 Cont ID  
Sent By mmclean Date 2005-07-13 Time 11:19 Rev Time 0.00
Received By mmclean Date 2005-07-13 Time 11:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-22 Cont ID  
Sent By mmclean Date 2005-08-22 Time 14:49 Rev Time 0.00
Received By mmclean Date 2005-08-22 Time 14:49 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-07-12 Cont ID  
Sent By mmclean Date 2005-07-12 Time 16:56 Rev Time 0.00
Received By mmclean Date 2005-07-12 Time 16:56 Sent To  
Notes
2005-07-12 00:00:00DENIED
 1. NEED TO APPLY FOR A OCCUPATIONAL
 LICENSE WITH THE CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 2. NEED TO INDICATE IF THERE IS A
 LICENSE FOR HEAVY DUTY OR LIGHT DUTY
 AUTO REPAIR.
 3. MUST PROVIDE A LOCATION OF THE SPRAY
 BOOTH ON THE SITEPLAN
 4. MUST SHOW THE SETBACKS OF THE
 STRUCTURE ON SITEPLAN.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720