| 2005-06-26 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05051913 |
| | ADD: 1645 P. B. LAKES BLVD |
| | SUITES: 800 |
| | 1150 |
| | 1200 |
| | CONT: D. B. MARCUS CONST |
| | TEL: (561)346-5667 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) CS- PROJECT DATA INDICATES |
| | CONSTRUCTION TYPE TO BE TYPE V |
| | UNPROTECTED? HIGH RISE EITHER TYPE I OR |
| | II FULLY SPRINKLERED. |
| | |
| | 3) NOTE FOR ALL THREE FLOORS!!!!! |
| | 412.6.1 ALL ELEVATORS ON ALL FLOORS |
| | SHALL OPEN INTO ELEVATOR LOBBIES WHICH |
| | ARE SEPARATED FROM THE REMAINDER OF THE |
| | BUILDING BY 1-HOUR FIRE RESISTANT |
| | CONSTRUCTION WITH 20-MINUTE OPENING |
| | PROTECTIVES. |
| | EXCEPTIONS: |
| | 1. ELEVATOR LOBBIES WITHIN AN ATRIUM. |
| | 2. WHERE THERE ARE OPEN EXTERIOR |
| | CORRIDORS THE ENTIRE WIDTH OF THE |
| | BUILDING WITH STAIRS LOCATED AT EACH END |
| | AND THE ELEVATORS ARE LOCATED ON THE |
| | EXTERIOR OF THE BUILDING. |
| | 3.THE MAIN ENTRANCE LEVEL OF THE |
| | BUILDING. |
| | |
| | 412.6.2 OPENINGS IN THE ELEVATOR LOBBY |
| | SHALL BE LIMITED TO THOSE REQUIRED FOR |
| | ACCESS TO THE ELEVATORS AND FOR EGRESS |
| | FROM THE BUILDING. ALL ROOMS AND |
| | ENCLOSURES SHALL HAVE AT LEAST ONE |
| | REQUIRED EXIT ACCESSIBLE WITHOUT TRAVEL |
| | THROUGH THE ELEVATOR LOBBY.OPENINGS |
| | MAY BE PROVIDED WITH HORIZONTAL SLIDING |
| | DOORS CONFORMING TO ?1012.4.EXIT |
| | STAIRWAYS, CHUTES, JANITOR CLOSETS, |
| | GUEST ROOMS, SERVICE ROOMS, ETC., SHALL |
| | NOT OPEN INTO THE ELEVATOR LOBBY. |
| | |
| | 412.6.3 EACH ELEVATOR LOBBY SHALL BE |
| | PROVIDED WITH AN APPROVED SMOKE |
| | DETECTOR LOCATED ON THE LOBBY CEILING. |
| | WHEN THE DETECTOR IS ACTIVATED, |
| | ELEVATOR DOORS SHALL NOT OPEN AND ALL |
| | CARS SERVING THAT LOBBY ARE TO RETURN TO |
| | THE MAIN FLOOR AND BE UNDER MANUAL |
| | CONTROL ONLY.IF THE MAIN FLOOR |
| | DETECTOR OR A TRANSFER FLOOR DETECTOR IS |
| | ACTIVATED, ALL CARS SERVING THE MAIN |
| | FLOOR OR TRANSFER FLOOR SHALL RETURN TO |
| | A LOCATION APPROVED BY THE FIRE |
| | DEPARTMENT AND BUILDING OFFICIAL AND BE |
| | UNDER MANUAL CONTROL ONLY.THE DETECTOR |
| | MAY SERVE TO CLOSE THE LOBBY DOORS. |
| | |
| | SUITE 800 |
| | 4) DEALS WITH THE ABOVE MENTIONED |
| | COMMENT, THAT ALL ROOMS AND ENCLOSURES |
| | ARE REQUIRED TO HAVE AT LEAST ONE |
| | REQUIRED EXIT ACCESSIBLE WITHOUT TRAVEL |
| | THROUGH THE ELEVATOR LOBBY. DOORWAY IS |
| | BLOCKED BY DESK AND A NEW DOOR WILL BE |
| | REQUIRED TO BLOCK THE RESTROOMS FROM THE |
| | ELEVATOR LOBBY. |
| | |
| | 5) 704.2.1.4 CORRIDOR PARTITIONS, |
| | SMOKE STOP PARTITIONS, HORIZONTAL EXIT |
| | PART- ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 6) DOORS THAT DO NOT MEET THE |
| | MANEUVERING CLEARENCES AT DOORS ARE: |
| | A824- AUTO CLOSER, ROOMS 812, 813 & 814. |
| | |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 11-4.1.6(2) DUTY TO PROVIDE AN |
| | ACCESSIBLE PATH OF TRAVEL TO ALTERED |
| | AREAS SHALL BE DEEMED DISPROPORTIONATE |
| | TO THE OVERALL ALTERATION WHEN THE COST |
| | EXCEEDS 20 % OF THE COST OF THE ALTERA- |
| | TION TO THE PRIMARY FUNCTION AREA. |
| | (A)(I) AN ACCESSIBLE ENTRANCE |
| | (II) AN ACCESSIBLE ROUTE |
| | (III) AT LEAST ONE ACCESSIBLE REST- |
| | ROOM FOR EACH SEX OR A SINGLE |
| | UNISEX RESTROOM |
| | (IIII) ACCESSIBLE TELEPHONE |
| | (IV) ELEMENTS SUCH AS PARKING, STOR- |
| | AGE OR ALARMS. |
| | |
| | 7)609.2.1 TYPE I AND TYPE II |
| | CONSTRUCTION. PARTITIONS SHALL BE |
| | CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS. |
| | EXCEPTIONS: |
| | 1. FRAMING MEMBERS MAY BE OF FIRE |
| | RETARDANT TREATED WOOD. |
| | 2. POCKET DOORS AND THEIR FRAMES MAY BE |
| | OF WOOD. |
| | |
| | SUITE 1150 |
| | 8) THE SAME COMMENT ABOUT TENANTS HAVING |
| | ACCESS TO A STAIRWAY WITHOUT HAVING TO |
| | TRAVEL THROUGH AN ELEVATOR LOBBY HOLDS |
| | TRUE, SEE 412.6.1/ 412.6.2 & 412.6.3. |
| | |
| | 9) ENTRY DOOR REQUIRES AN AUTOMATIC DOOR |
| | CLOSER ENVOKING MANEUVERING CLEARENCES |
| | AT DOORS 11-4.13.6 MANEUVERING |
| | CLEARENCES AT DOORS. MINIMUM MANEUVERING |
| | CLEARENCES AT DOORS THAT ARE NOT |
| | AUTOMATIC OR POWER-ASSISTED SHALL BE AS |
| | SHOWN IN FIG. 25. THE FLOOR OR GROUND |
| | AREA WITH IN THE REQUIRED CLEARENCES |
| | SHALL BE CLEAR & LEVEL.ALSO STORAGE |
| | CLOSET 1101 REQUIRES THE 18" SIDE |
| | CLEARENCE. |
| | |
| | 10) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | SUITE 1200 |
| | 11) ELEVATOR LOBBY WORKS FOR THIS |
| | CONFIGURATION, BUT ON THE ELECTRICAL |
| | SHEET STILL INDICATES EXIT SIGNAGE WHERE |
| | THE DOORWAY WAS CLOSED, THERE IS NO EXIT |
| | SIGNAGE NOR EMERGENCY LIGHTING ON THE |
| | NORTH SIDE OF THE OFFICE? |
| | |
| | 12)704.2.1.4 CORRIDOR PARTITIONS, |
| | SMOKE STOP PARTITIONS, HORIZONTAL EXIT |
| | PART- ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| 2005-06-07 00:00:00 | COMM BOARD #53 |