Plan Review Details - Permit 05051913
Plan Review Stops For Permit 05051913
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-03-19 Cont ID  
Sent By jwitmer Date 2007-03-19 Time 10:33 Rev Time 0.77
Received By jwitmer Date 2007-03-19 Time 10:33 Sent To PC
Notes
2007-03-19 10:35:56REVISION# 9 ELEVATOR LOBBY FIRE RATED SOFFIT SYSTEM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-07-19 Cont ID  
Sent By jwitmer Date 2006-07-19 Time 08:48 Rev Time 0.55
Received By jwitmer Date 2006-07-19 Time 08:25 Sent To PC
Notes
2006-07-19 00:00:00REVISION: 11TH FLOOR REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-03-30 Cont ID  
Sent By jwitmer Date 2006-03-30 Time 08:56 Rev Time 0.66
Received By jwitmer Date 2006-03-30 Time 08:56 Sent To PC
Notes
2006-03-30 00:00:0003-30-06 8TH FL RED LINED PLAN SUBMITTED
 81/2X 11

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-01-11 Cont ID  
Sent By jwitmer Date 2006-01-11 Time 09:21 Rev Time 1.22
Received By jwitmer Date 2006-01-11 Time 09:21 Sent To PC
Notes
2006-01-11 00:00:0001-11-06 ARCH ROBERT HILL RED LINED
 DRAWINGS 8TH FL & 12TH FLOOR CORRECTING
 FOR ELEVATOR LOBBY DOOR REQUIREMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-01-10 Cont ID  
Sent By jwitmer Date 2006-01-10 Time 15:03 Rev Time 1.11
Received By jwitmer Date 2006-01-10 Time 15:03 Sent To PC
Notes
2006-01-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051913
 ADD: 1645 PALM BCH LAKES #1200
 CONT:)(PLAN REVIEW) CONTRACTOR TO
  
 BE DECIDED
 TEL: (561)706-7201
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1) THE 2ND COMMENT FROM THE PREVIOUS
 REVIEW, THE SECOND ISSUE:
 THE SECOND ISSUE WITH 412.6.3 DEALS
 WITH WHICH OPENINGS ARE ACCEPTIBLE TO BE
 IN A ELEVATOR LOBBY AND WHICH AREN'T.
 EXIT STAIRWAYS, CHUTES, JANITOR CLOSETS,
 GUEST ROOMS, SERVICE ROOMS, ETC., SHALL
 NOT OPEN INTO THE ELEVATOR LOBBY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-13 Cont ID  
Sent By jwitmer Date 2005-09-13 Time 07:03 Rev Time 0.77
Received By jwitmer Date 2005-09-13 Time 06:31 Sent To  
Notes
2005-09-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051913
 ADD: 1645 PALM BCH LAKES #1200
 CONT:)(PLAN REVIEW) CONTRACTOR TO
  
 BE DECIDED
 TEL: (561)706-7201
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) COMMENT# 1 FROM THE FIRST REVIEW,
 PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
  
 2) COMMENT# 3 FROM THE PEVIOUS REVIEW,
 NOTE FOR ALL THREE FLOORS!!!!!
 412.6.1 ALL ELEVATORS ON ALL FLOORS
 SHALL OPEN INTO ELEVATOR LOBBIES WHICH
 ARE SEPARATED FROM THE REMAINDER OF THE
 BUILDING BY 1-HOUR FIRE RESISTANT
 CONSTRUCTION WITH 20-MINUTE OPENING
 PROTECTIVES.
 EXCEPTIONS:
 1. ELEVATOR LOBBIES WITHIN AN ATRIUM.
 2. WHERE THERE ARE OPEN EXTERIOR
 CORRIDORS THE ENTIRE WIDTH OF THE
 BUILDING WITH STAIRS LOCATED AT EACH END
 AND THE ELEVATORS ARE LOCATED ON THE
 EXTERIOR OF THE BUILDING.
 3.THE MAIN ENTRANCE LEVEL OF THE
 BUILDING.
  
 412.6.2 OPENINGS IN THE ELEVATOR LOBBY
 SHALL BE LIMITED TO THOSE REQUIRED FOR
 ACCESS TO THE ELEVATORS AND FOR EGRESS
 FROM THE BUILDING. ALL ROOMS AND
 ENCLOSURES SHALL HAVE AT LEAST ONE
 REQUIRED EXIT ACCESSIBLE WITHOUT TRAVEL
 THROUGH THE ELEVATOR LOBBY.OPENINGS
 MAY BE PROVIDED WITH HORIZONTAL SLIDING
 DOORS CONFORMING TO 1012.4.EXIT
 STAIRWAYS, CHUTES, JANITOR CLOSETS,
 GUEST ROOMS, SERVICE ROOMS, ETC., SHALL
 NOT OPEN INTO THE ELEVATOR LOBBY.
  
 412.6.3 EACH ELEVATOR LOBBY SHALL BE
 PROVIDED WITH AN APPROVED SMOKE
 DETECTOR LOCATED ON THE LOBBY CEILING.
 WHEN THE DETECTOR IS ACTIVATED,
 ELEVATOR DOORS SHALL NOT OPEN AND ALL
 CARS SERVING THAT LOBBY ARE TO RETURN TO
 THE MAIN FLOOR AND BE UNDER MANUAL
 CONTROL ONLY.IF THE MAIN FLOOR
 DETECTOR OR A TRANSFER FLOOR DETECTOR IS
 ACTIVATED, ALL CARS SERVING THE MAIN
 FLOOR OR TRANSFER FLOOR SHALL RETURN TO
 A LOCATION APPROVED BY THE FIRE
 DEPARTMENT AND BUILDING OFFICIAL AND BE
 UNDER MANUAL CONTROL ONLY.THE DETECTOR
 MAY SERVE TO CLOSE THE LOBBY DOORS.
  
 THESE COMMENTS ABOVE DEAL WITH COMMENTS
 3,4 & 8FROM THE PREVIOUS REVIEW.
 412.6.2 ACTUALLY DEALS WITH (2) ISSUES
 THE FIRST STATING THAT ALL ROOMS SHALL
 HAVE AT LEAST ONE MEANS OF EGRESS TO A
 EXIT WITHOUT HAVING TO TRAVEL THROUGH A
 ELEVATOR LOBBY. THERE ARE NO EXCEPTIONS
 TO FEASIBLITY TO COMPLY. THERE ARE THREE
 EXCEPTIONS LISTED ABOVE WHICH ARE NOT
 REQUIRED TO COMPLY WITH THIS SECTION.
  
 THE SECOND ISSUE WITH 412.6.3 DEALS
 WITH WHICH OPENINGS ARE ACCEPTIBLE TO BE
 IN A ELEVATOR LOBBY AND WHICH AREN'T.
 EXIT STAIRWAYS, CHUTES, JANITOR CLOSETS,
 GUEST ROOMS, SERVICE ROOMS, ETC., SHALL
 NOT OPEN INTO THE ELEVATOR LOBBY.
  
  
 3)COMMENT# 6 FROM THE PREVIOUS REVIEW,6)
 DOORS THAT DO NOT MEET THE MANEUVERING
 CLEARENCES AT DOORS ARE:
 A824- AUTO CLOSER, ROOMS 812, 813 & 814.
  
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 THE CODE IS VERY CLEAR WHERE THERE IS
 EXISTING ACCESSIBILITY ISSUES, THE
 TENANT IN THIS CASE HAS A DUTY TO
 CORRECT THE EXISTING VIOLATIONS TO THE
 EXTENT OF 20% OF THE CONTRACT VALUE.
  
 11-4.1.6(2)(A)(I)AN ACCESSIBLE ENTRANCE
 DOOR A824 CAN COUNT PART OF THE
 DISPROPORTIONATE COST IF YOU INDICATE ON
 THE E PAGES THE ELECTRICAL CIRCUIT
 REQUIRED TO OPERATE THE DOOR, ALSO
 PROVIDE SPEC ON HARDWARE.
  
 11-4.1.6(2)(A)(II)AN ACCESSIBLE ROUTE:
 DOORS 8112,813 & 814 ALSO NEED TO COMPLY
 BY REARRANGING THE CONFIGURATION.THERE
 IS STILL DUTY TO COMPLY IF THE 20% OF
 THE CONTRACT VALUE HAS NOT BEEN MEET.
 PROVIDE INFORMATION AS TO WHERE THE
 ADDITIONAL FUNDS ARE TO BE DISPERSED.
  
 11-4.1.6(2)(A)(III) DEALS WITH RESTROOMS
 THAT WOULD NEED TO BE UPGRADED.BELOW IS
 THE ACTUAL COST BREAK OUT TO INDICATE
 HOW THE 20% IS TO BE SPENT.
  
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
  
 4) COMMENT# 9A FROM THE PREVIOUS REVIEW,
 AS STATED ABOVE INDICATE THE AUTOMATIC
 DOOR OPENER FOR A824 ON BOTH THE A & E
 SHEETS, PROVIDE SPECIFICATIONS FOR SUCH
 HARDWARE. IF THE ELECTRIC GOES OUT, WILL
 THIS DOOR AUTOMATICLLY OPEN OR WILL IT
 BE PUT ON THE GENERATOR EMERGENCY
 CIRCUITS?
  
  
 5) COMMENT 5, 10 & 12 FROM THE PREVIOUS
 REVIEW, DEALS WITH STENCILING OF RATED
 WALLS, BUT I COULD NOT FIND WHERE THE
 REVISION WAS MADE WITH EITHER A DELTA OR
 CLOUD?
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-26 Cont ID  
Sent By shill Date 2005-06-07 Time 15:12 Rev Time 2.22
Received By jwitmer Date 2005-06-26 Time 12:57 Sent To  
Notes
2005-06-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051913
 ADD: 1645 P. B. LAKES BLVD
 SUITES: 800
 1150
 1200
 CONT: D. B. MARCUS CONST
 TEL: (561)346-5667
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) CS- PROJECT DATA INDICATES
 CONSTRUCTION TYPE TO BE TYPE V
 UNPROTECTED? HIGH RISE EITHER TYPE I OR
 II FULLY SPRINKLERED.
  
 3) NOTE FOR ALL THREE FLOORS!!!!!
 412.6.1 ALL ELEVATORS ON ALL FLOORS
 SHALL OPEN INTO ELEVATOR LOBBIES WHICH
 ARE SEPARATED FROM THE REMAINDER OF THE
 BUILDING BY 1-HOUR FIRE RESISTANT
 CONSTRUCTION WITH 20-MINUTE OPENING
 PROTECTIVES.
 EXCEPTIONS:
 1. ELEVATOR LOBBIES WITHIN AN ATRIUM.
 2. WHERE THERE ARE OPEN EXTERIOR
 CORRIDORS THE ENTIRE WIDTH OF THE
 BUILDING WITH STAIRS LOCATED AT EACH END
 AND THE ELEVATORS ARE LOCATED ON THE
 EXTERIOR OF THE BUILDING.
 3.THE MAIN ENTRANCE LEVEL OF THE
 BUILDING.
  
 412.6.2 OPENINGS IN THE ELEVATOR LOBBY
 SHALL BE LIMITED TO THOSE REQUIRED FOR
 ACCESS TO THE ELEVATORS AND FOR EGRESS
 FROM THE BUILDING. ALL ROOMS AND
 ENCLOSURES SHALL HAVE AT LEAST ONE
 REQUIRED EXIT ACCESSIBLE WITHOUT TRAVEL
 THROUGH THE ELEVATOR LOBBY.OPENINGS
 MAY BE PROVIDED WITH HORIZONTAL SLIDING
 DOORS CONFORMING TO ?1012.4.EXIT
 STAIRWAYS, CHUTES, JANITOR CLOSETS,
 GUEST ROOMS, SERVICE ROOMS, ETC., SHALL
 NOT OPEN INTO THE ELEVATOR LOBBY.
  
 412.6.3 EACH ELEVATOR LOBBY SHALL BE
 PROVIDED WITH AN APPROVED SMOKE
 DETECTOR LOCATED ON THE LOBBY CEILING.
 WHEN THE DETECTOR IS ACTIVATED,
 ELEVATOR DOORS SHALL NOT OPEN AND ALL
 CARS SERVING THAT LOBBY ARE TO RETURN TO
 THE MAIN FLOOR AND BE UNDER MANUAL
 CONTROL ONLY.IF THE MAIN FLOOR
 DETECTOR OR A TRANSFER FLOOR DETECTOR IS
 ACTIVATED, ALL CARS SERVING THE MAIN
 FLOOR OR TRANSFER FLOOR SHALL RETURN TO
 A LOCATION APPROVED BY THE FIRE
 DEPARTMENT AND BUILDING OFFICIAL AND BE
 UNDER MANUAL CONTROL ONLY.THE DETECTOR
 MAY SERVE TO CLOSE THE LOBBY DOORS.
  
 SUITE 800
 4) DEALS WITH THE ABOVE MENTIONED
 COMMENT, THAT ALL ROOMS AND ENCLOSURES
 ARE REQUIRED TO HAVE AT LEAST ONE
 REQUIRED EXIT ACCESSIBLE WITHOUT TRAVEL
 THROUGH THE ELEVATOR LOBBY. DOORWAY IS
 BLOCKED BY DESK AND A NEW DOOR WILL BE
 REQUIRED TO BLOCK THE RESTROOMS FROM THE
 ELEVATOR LOBBY.
  
 5) 704.2.1.4 CORRIDOR PARTITIONS,
 SMOKE STOP PARTITIONS, HORIZONTAL EXIT
 PART- ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 6) DOORS THAT DO NOT MEET THE
 MANEUVERING CLEARENCES AT DOORS ARE:
 A824- AUTO CLOSER, ROOMS 812, 813 & 814.
  
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 7)609.2.1 TYPE I AND TYPE II
 CONSTRUCTION. PARTITIONS SHALL BE
 CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS.
 EXCEPTIONS:
 1. FRAMING MEMBERS MAY BE OF FIRE
 RETARDANT TREATED WOOD.
 2. POCKET DOORS AND THEIR FRAMES MAY BE
 OF WOOD.
  
 SUITE 1150
 8) THE SAME COMMENT ABOUT TENANTS HAVING
 ACCESS TO A STAIRWAY WITHOUT HAVING TO
 TRAVEL THROUGH AN ELEVATOR LOBBY HOLDS
 TRUE, SEE 412.6.1/ 412.6.2 & 412.6.3.
  
 9) ENTRY DOOR REQUIRES AN AUTOMATIC DOOR
 CLOSER ENVOKING MANEUVERING CLEARENCES
 AT DOORS 11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARENCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIG. 25. THE FLOOR OR GROUND
 AREA WITH IN THE REQUIRED CLEARENCES
 SHALL BE CLEAR & LEVEL.ALSO STORAGE
 CLOSET 1101 REQUIRES THE 18" SIDE
 CLEARENCE.
  
 10) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 SUITE 1200
 11) ELEVATOR LOBBY WORKS FOR THIS
 CONFIGURATION, BUT ON THE ELECTRICAL
 SHEET STILL INDICATES EXIT SIGNAGE WHERE
 THE DOORWAY WAS CLOSED, THERE IS NO EXIT
 SIGNAGE NOR EMERGENCY LIGHTING ON THE
 NORTH SIDE OF THE OFFICE?
  
 12)704.2.1.4 CORRIDOR PARTITIONS,
 SMOKE STOP PARTITIONS, HORIZONTAL EXIT
 PART- ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
2005-06-07 00:00:00COMM BOARD #53

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-07-19 Cont ID  
Sent By dpalmer Date 2006-07-19 Time 08:58 Rev Time 0.00
Received By dpalmer Date 2006-07-19 Time 08:58 Sent To  
Notes
2006-07-19 00:00:00REV FOR RELOCATION OF SWITCH.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-20 Cont ID  
Sent By dpalmer Date 2005-12-20 Time 18:37 Rev Time 0.75
Received By dpalmer Date 2005-12-20 Time 18:37 Sent To  
Notes
2005-12-20 00:00:00REMOVED ALL OLD SHEETS AND INSERTED NEW
 REVISED SHEETS INTO TWO COMPLETE SETS,
 NOT DONE DESIGN TEAM/CONTRACTOR.
 RE-STAMPED NEW ELECTRICAL SHEETS.
 PLACED ORIGINAL STAMPED MECHANICAL PLANS
 INTO NEW SETS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 20:50 Rev Time 0.50
Received By dpalmer Date 2005-09-03 Time 20:25 Sent To  
Notes
2005-09-03 00:00:00 
 ****************************************
 PLANS SUBMITTED FOR "PLAN REVIEW" ONLY
 AND NOT FOR PERMIT.
 PLANS CAME BACK IN AS 1ST RESUB WHEN
 PLANS ARE IN FOR PLAN REVIEW.
 OWES FEES FOR PROJECT PLAN REVIEW,
 CALLED MONICA NUNEZ ON 9/3, WILL COME IN
 ON 9/6/05 TO PAY $420 FEE.
 NO MORE REVIEWS CAN BE DONE UNTIL THIS
 IS PAID.
  
  
  
  
  
 **** NOTES REDLINED ****
  
 1)NOTE: KITCHEN/BRK RM SHALL HAVE GFI
 PROTECTED 15A/20A 125V CIRCUITS OR
 RECEPTS PER 2002 210.8B3
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-27 Cont ID  
Sent By dpalmer Date 2005-06-27 Time 09:15 Rev Time 0.50
Received By dpalmer Date 2005-06-27 Time 09:15 Sent To  
Notes
2005-06-27 00:00:00********* UNSAT *********
  
 PLEASE NOTE: PLANS ARE ONLY SUBMITTED
 FOR "PLAN REVIEW" AND NOT FOR PERMIT.
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004, FS
 481.219, WHICH REQUIRES ALL LICENSE
 INFORMATION ETC ON TITLE BLOCK(S). THIS
 IS REQUIRED ON ALL SHEETS AND FOR ALL
 TRADES WHEATHER OR NOT COMMENT IS MADE
 BY OTHER REVIEWER(S).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-12 Cont ID  
Sent By mcarsill Date 2005-09-12 Time 14:46 Rev Time 0.00
Received By mcarsill Date 2005-09-12 Time 14:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-06-24 Cont ID  
Sent By mcarsill Date 2005-06-24 Time 15:00 Rev Time 0.00
Received By mcarsill Date 2005-06-24 Time 15:00 Sent To  
Notes
2005-06-24 00:00:001. ALL WORK TO COMPLY WITH NFPA 241.
  
 2. ALL EXITS ARE TO REMIAN CLEAR AND
 UNOBSTRUCTED DURING DEMOLITION
 AND CONSTRUCTION.
  
 3. DEBRIS SHALL BE REMOVED DAILY.
  
 4. AS NOTED ON PAGE A 2.1 "MAINTAIN
 ALL LIFE SAFETY SYSTEM AND CONDITIONS".
  
 5. NO FIRE RATINGS NOTED FOR DOORS
 ON PAGE A 4.3.
  
 6. WRONG LIFE SAFETY CODE NOTED
 ON PLANS. SHOULD READ THE 2003 EDITION
 OF THE LIFE SAFETY CODE.
  
 MIKE CARSILLO, FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-03-03 Cont ID  
Sent By adarroug Date 2007-03-03 Time 16:03 Rev Time 0.00
Received By adarroug Date 2007-03-03 Time 16:03 Sent To B
Notes
2007-03-03 16:04:35TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-07-13 Cont ID  
Sent By adarroug Date 2006-07-13 Time 10:18 Rev Time 0.00
Received By adarroug Date 2006-07-13 Time 10:18 Sent To B
Notes
2006-07-13 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-04-18 Cont ID  
Sent By adarroug Date 2006-04-18 Time 09:24 Rev Time 0.00
Received By adarroug Date 2006-04-18 Time 09:24 Sent To M
Notes
2006-04-18 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 17:36 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 17:36 Sent To B
Notes
2006-03-09 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-06 Cont ID  
Sent By adarroug Date 2005-10-06 Time 16:05 Rev Time 0.00
Received By adarroug Date 2005-10-06 Time 16:05 Sent To  
Notes
2005-10-14 00:00:00TO "COMM" BD#64
2005-10-06 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-23 Cont ID  
Sent By adarroug Date 2005-08-23 Time 16:58 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 16:57 Sent To  
Notes
2005-08-24 00:00:00TO "COMM" BD#36
2005-08-23 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-02 Cont ID  
Sent By adarroug Date 2005-06-02 Time 15:00 Rev Time 0.00
Received By adarroug Date 2005-06-02 Time 15:00 Sent To  
Notes
2005-06-02 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-04-18 Cont ID  
Sent By tgordon Date 2006-04-18 Time 13:58 Rev Time 0.20
Received By tgordon Date 2006-04-18 Time 13:58 Sent To  
Notes
2006-04-18 00:00:00MECH. REVISION TO PAGE M 2.1 .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-30 Cont ID  
Sent By pkrauss Date 2005-09-30 Time 12:47 Rev Time 0.50
Received By pkrauss Date 2005-09-30 Time 12:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-29 Cont ID  
Sent By pkrauss Date 2005-06-29 Time 09:09 Rev Time 0.55
Received By pkrauss Date 2005-06-29 Time 07:08 Sent To  
Notes
2005-06-29 00:00:00DENIED:PLAN CHECK
 1.PLAN SHEET M2.1, EXISTING DUCT
 PENETRATING OFFICE #802 AND ADJOINING
 SPACE, FIRE DAMPER REQUIRED.PLEASE
 VERIFY EXISTING FIRE DAMPER & ANNOTATE
 ON PLAN.
  
 2.PLAN SHEET M2.2, EXISTING DUCT
 PENETRATING ELEVATOR LOBBY & RECEPTION
 AREA WALL.PLEASE VERIFY FIRE DAMPER.
 PLAN DOES NOT INDICATE NEW OR EXISTING
 DAMPER.
  
 PLEASE NOTE, NO COMBUSTIBLES ALLOWED
 ABOVE THE CEILING IN THE RETURN AIR
 PLENUM PER 2001FBC(M)602.2.1.
  
 SEE COMMENT #1 BY PLUMBING & ELECTRICAL
 PLAN REVIEWERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-01-07 Cont ID  
Sent By pschmitz Date 2006-01-07 Time 12:47 Rev Time 0.00
Received By pschmitz Date 2006-01-07 Time 13:29 Sent To  
Notes
2006-01-07 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 PREVIEW.
 REVIEWED

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-10-01 Cont ID  
Sent By jleech Date 2005-10-01 Time 10:44 Rev Time 1.25
Received By jleech Date 2005-10-01 Time 10:44 Sent To  
Notes
2005-10-01 00:00:00DENIED;
 SHOW COMPLIANCE WITH FBC-2001 CHAPTER
 11, SEC. 11-4.1.6 (6) ACCESSIBLE
 BATHROOM FACILITIES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-25 Cont ID  
Sent By kstevens Date 2005-06-25 Time 08:56 Rev Time 0.00
Received By kstevens Date 2006-01-07 Time 13:50 Sent To  
Notes
2005-06-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS CS, AND A1.1 THRU A4.3 THE
 PRINTED NAME OF THE PERSON SEALING THE
 SHEETS SHALL BE ON THE TITLE BLOCK. FAC
 61G1-16.004(6) AND FS 481.2055
 2. ALL MEP SHEETS, CERTIFICATE OF
 AUTHORIZATION IS REQUIRED IN THE TITLE
 BLOCK OF THE ARCHITECTURAL BUSINESS. FAC
 61G1-16.004(2) AND FS 481.2055
 3. SHTS A1.1, A1.2, & A1.3 DEMOLITION
 KEY NOTES TO BE SPECIFIC TO EACH SHEET.
 WORK ON EACH SHEET IS DIFFERENT. SHT
 A1.2 DOES NOT APPEAR TO HAVE PLUMBING
 WORK, AND SHT A1.3 SHOWS PLUMBING WORK,
 BUT NO DEMO KEY NOTES OR DEMO KEY NOTE
 NUMBER IDENTIFYING THE WORK SHOWN.
 PLEASE CLARIFY. SECTION 104.2.1.
 4. SHT A2.1 SHOW THE CLEAR FLOOR SPACE
 FOR THE SINKS IN ROOMS 805 & 820. CLEAR
 FLOOR SPACE SHALL BE FORWARD APPROACH
 AND EXTEND A MAXIMUM OF 19" UNDERNEATH
 THE SINK. CABINET DOORS ARE NOT APPROVED
 IN THE CLEAR FLOOR SPACE. SECTION
 11-4.24.5.
 5. SHT A2.2 & A2.3 ROOMS 1112 AND 1224
 INDICATES NEW CABINETS. SINKS SHALL
 COMPLY WITH 11-4.24 AND ALL SUBSECTIONS.
 SHOW CLEAR FLOOR SPACE REQUIRED BY
 SECTION 11-4.24.5. CLEAR FLOOR SPACE
 SHALL BE FORWARD APPROACH AND SHALL
 EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK. CABINET DOORS ARE NOT APPROVED IN
 THE CLEAR FLOOR SPACE.
 7. SHT A4.1 DETAILS 3, 7, & 8. SINKS
 SHALL BE ACCESSIBLE PER SECTION 11-4.24.
 SHOW THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.4.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE
 E. 11-4.24.6 EXPOSED PIPES AND SURFACES
 F. 11-4.24.7 FAUCETS
 8. SHT P1.1 WATER ISOMETRIC. WATER
 HAMMER ARRESTORS ARE REQUIRED ON THE
 WATER LINES TO THE DISH WASHER AND THE
 ICE MAKER IN THE REF. SECTION 604.9.
 LOCATION OF THE WATER HAMMER ARRESTORS
 SHALL BE NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201.
 9. SHT P1.1 GENERAL NOTES: #16 AIR
 CHAMBERS ARE NOT APPROVED. SECTION 604.9
 DELETE NOTE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]