Plan Review Details - Permit 05051837
Plan Review Stops For Permit 05051837
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2005-07-20 Cont ID  
Sent By jleech Date 2005-07-20 Time 18:21 Rev Time 0.50
Received By jleech Date 2005-07-20 Time 18:21 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-06-15 Cont ID  
Sent By jleech Date 2005-06-15 Time 16:01 Rev Time 0.75
Received By jleech Date 2005-06-15 Time 16:01 Sent To  
Notes
2005-06-15 00:00:00DENIED;
 SHOW BTU LOAD FOR EACH APPIANCE AND
 TOTAL BTU'S LOAD ON SYSTEM.
  
 SHOW AN ISOMETRIC DRAWING THAT CLEARLY
 SHOWS ALL CUT SECTIONS OF PIPE, PER FBC
 FUIL GAS.
  
 SUBMIT MANUFACTURES SHEETS FOR GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH FBC
 GAS CODE SEC. 402.2.
  
 NO PERMIT PERTAINING TO A GENER ATOR
 SHALL BE ISSUED UNTIL AN RES- GEN
 APPLICATION IS APPLIED FOR , WITH REVIEW
 BY BUILDING, ELECTRIC,ZONING,
 MECHANICAL, AND PLUMBING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-30 Cont ID  
Sent By adarroug Date 2005-06-30 Time 16:22 Rev Time 0.00
Received By adarroug Date 2005-06-30 Time 16:22 Sent To G
Notes
2005-06-30 00:00:00TO "KSTEVENS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 11:13 Rev Time 0.00
Received By adarroug Date 2005-05-31 Time 11:13 Sent To G
Notes
2005-05-31 00:00:00TO "G" BOX