| 2005-07-14 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05051833 |
| | ADD: 2211 N FLAGLER DR |
| | CONT: PLAN REVIEW/ LIFE SAFETY |
| | MERCO GROUP |
| | TEL: (561)289-0276 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) NOE SEET OF PLANS IS MISSING THE |
| | LS0.01 UNDER GROUND TUNNEL/ EXIT |
| | PASSAGE. |
| | |
| | 2) THE SHEET LS0.01 SECTION OF THE EXIT |
| | PASSAGE INDICATES A HEIGHT OF 7'-0".SEE |
| | 1003.2.5 HEADROOM. MEANS OF EGRESS SHALL |
| | BE DESIGNED AND MAINTAINED TO |
| | PROVIDE A MINIMUM HEADROOM OF 7 FT 6 |
| | IN. (2.3 M) WITH PROJECTIONS FROM |
| | THE CEILING AT LEAST 6 FT 8 IN. (2 M) |
| | NOMINAL HEIGHT ABOVE THE FINISHED |
| | FLOOR.DOORWAYS IN A MEANS OF EGRESS |
| | SHALL PROVIDE A MINIMUM HEADROOM OF |
| | 6 FT 8 IN. (2 M).STAIRS IN A MEANS |
| | OF EGRESS SHALL COMPLY WITH 1007.7. |
| | |
| | 3) PLANS TO INDICATE COMPLIANCE WITH THE |
| | HEADROOM REQUIREMENTS ( PROJECTIONS) FOR |
| | LIGHTING, EMERGENCY LIGHTING, FIRE |
| | SPRINKLERS, EXIT SIGNAGE, ETC. |
| | |
| | 4) SHEET LS0.01INDICATES A TUNNEL |
| | EFFECT, PROVIDE HOW STAIRWELL |
| | PRESSURIZATION WILL TAKE PLACE IN EACH |
| | SEGMENT?1005.6.9.1 STAIR |
| | PRESSURIZATION SYSTEMS SHALL BE |
| | INDEPENDENT OF OTHER BUILDING |
| | VENTILATION SYSTEMS. |
| | |
| | 5) WILL THERE BE CO2 DETECTORS? |
| | |
| | 6) PROVIDE INFORMATION ON HOW THE FIRE |
| | DEPARTMENT WILL GAIN ACCESS TO THE |
| | UNDERGROUND EXIT PASSAGEWAYS FROM THE |
| | STREET? |
| | |
| | 7) PLANS DO NOT INDICATE THE RATING OF |
| | THE WALLS OR DOORS IN THE STAIRS AND |
| | EXIT PASSAGE WAY? |
| | |
| | 8) SHEET LS0.05 IS MISSING DOORS FROM |
| | CONDO TO EXIT STAIRWAY: |
| | 412.6.2 OPENINGS IN THE ELEVATOR LOBBY |
| | SHALL BE LIMITED TO THOSE |
| | REQUIRED FOR ACCESS TO THE ELEVATORS |
| | AND FOR EGRESS FROM THE BUILDING. |
| | ALL ROOMS AND ENCLOSURES SHALL HAVE AT |
| | LEAST ONE REQUIRED EXIT ACCESSIBLE |
| | WITHOUT TRAVEL THROUGH THE ELEVATOR |
| | LOBBY.OPENINGS MAY BE PROVIDED WITH |
| | HORIZONTAL SLIDING DOORS CONFORMING TO |
| | ?1012.4.EXIT STAIRWAYS, CHUTES, |
| | JANITOR CLOSETS, GUEST ROOMS, SERVICE |
| | ROOMS, ETC., SHALL NOT OPEN INTO THE |
| | ELEVATOR LOBBY. |
| | |
| | 9) PLEASE PROVIDE WHAT LEVELS RE-ENTRY |
| | WILL BE ALLOWED? WILL RE-ENTRY BE |
| | ALLOWED FOR THE POOL LEVEL DECK? |
| | 1012.1.11 EVERY DOOR IN A STAIR |
| | ENCLOSURE SERVING MORE THAN FOUR |
| | STORIES SHALL PERMIT RE-ENTRY FROM THE |
| | STAIR ENCLOSURE TO THE INTERIOR OF |
| | THE BUILDING, OR AN AUTOMATIC RELEASE |
| | SHALL BE PROVIDED TO UNLOCK ALL |
| | STAIR ENCLOSURE DOORS TO PERMIT |
| | RE-ENTRY.SUCH AUTOMATIC RELEASE SHALL |
| | BE |
| | ACTUATED WITH THE INITIATION OF THE |
| | BUILDING FIRE ALARM, FIRE DETECTION OR |
| | FIRE SPRINKLER SYSTEM. |
| | |
| | EXCEPTION: DOORS ON STAIR ENCLOSURES |
| | SHALL BE PERMITTED TO BE |
| | EQUIPPED WITH HARDWARE THAT PREVENTS |
| | RE-ENTRY INTO THE INTERIOR OF THE |
| | BUILDING, PROVIDED THAT THE |
| | FOLLOWING CONDITIONS ARE MET: |
| | |
| | 1. THERE ARE AT LEAST TWO LEVELS |
| | WHERE IT IS POSSIBLE TO LEAVE THE |
| | STAIR ENCLOSURE; AND |
| | |
| | 2. THERE ARE NOT MORE THAN FOUR |
| | STORIES INTERVENING BETWEEN STORIES |
| | WHERE IT IS POSSIBLE TO LEAVE THE |
| | STAIR ENCLOSURE; AND |
| | |
| | 3. RE-ENTRY IS POSSIBLE ON THE TOP |
| | OR NEXT TO TOP STORY PERMITTING |
| | ACCESS TO ANOTHER EXIT; AND |
| | |
| | 4. DOORS PERMITTING RE-ENTRY ARE |
| | IDENTIFIED AS SUCH ON THE STAIR SIDE |
| | OF THE DOOR; AND |
| | |
| | 5. DOORS NOT PERMITTING RE-ENTRY |
| | SHALL BE PROVIDED WITH A SIGN ON THE |
| | STAIR SIDE INDICATING THE |
| | LOCATION OF THE NEAREST DOOR, IN EACH |
| | DIRECTION OF TRAVEL, PERMITTING |
| | RE-ENTRY OR EXIT. |
| | |
| | 10) PLAZA DECK THERE WAS DISCUSSION AS |
| | TO HOW EXIT SIGNS WERE GOING TO BE |
| | PLACED AROUND THE PLAZA POOL DECK WITH |
| | THE CABANAS OBSSTRUCTING THE VIEW OF |
| | EXIT SIGNS, ONE ITEM THAT WAS NOT |
| | DISCUSSED WAS COMPLIANCE FOR THE BLIND, |
| | SEE 11-4.30.1-7. |
| | |
| | 11) WITHOUT HAVING A COMPLETE SET OF |
| | PLANS INDICATING VARIOUS SITUATIONS |
| | OTHER AREAS OF CONCERN WILL BE : |
| | 11-4.29.2 DETECTABLE WARNING ON WALKING |
| | SURFACES. |
| | 11-4.29.5 DETECTABLE WARNINGS AT |
| | HAZARDOUS VEHICULAR AREAS. |
| | 11-4.29.6 DETECTABLE WARNINGS AT |
| | REFLECTING POOLS. |
| | 11-4.28.1-4 AUDIBLE AND VISUAL ALARMS. |
| | |
| | THIS IS A REVIEW OF ONLY LIFE SAFETY, |
| | OTHER ISSUES MAY ARISE WHEN A COMPLETE |
| | SET OF PLANS ARE PROVIDED, AND IN NO WAY |
| | |
| | CONSTITUTES A PERMIT WOULD BE ISSUED |
| | WHEN THESE COMMENTS ARE MET. |
| | |
| | THE OTHER ISSUE WILL BE WHEN THE |
| | BUILDING WILL BE BROUGHT IN UNDER A |
| | PERMIT APPLICATION. BETWEEN JULY 1/05 & |
| | SEPT.30/05 THE DESIGNER MAY DESIGN TO |
| | EITHER THE 2001 OR 2004 FLORIDA CODE, |
| | THE PLANS MUST INDICATE AS TO WHICH CODE |
| | THE BUILDING WAS DESIGNED. AFTER |
| | SEPT.30/05 THE 2004 FLORIDA CODE MUST BE |
| | THE DESIGN CRITERIA. |
| | |
| | |
| | |
| | |