Plan Review Details - Permit 05051818
Plan Review Stops For Permit 05051818
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-07-20 Cont ID  
Sent By rmcdouga Date 2005-07-20 Time 12:51 Rev Time 0.00
Received By rmcdouga Date 2005-07-20 Time 12:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-27 Cont ID  
Sent By rmcdouga Date 2005-06-27 Time 11:00 Rev Time 0.00
Received By rmcdouga Date 2005-06-27 Time 11:00 Sent To  
Notes
2005-06-27 00:00:00DENIED
  
 1) EXISTING STAIRS ARE REQUIRED TO HAVE
 HAND RAILS AND GUARDRAILS THAT COMPLY
 WITH FBC 1007.5, 1015 AND 1026.5.
  
 2) THE TYPE OF CONSTRUCTION SPECIFIED ON
 SHEET A0 IS TYPE IV. THE EXTERIOR
 BEARING WALLS, INTERIOR BEARING WALLS,
 FLOOR/CEILING ASSEMBLIES AND
 ROOF/CEILING ASSEMBLIES ARE REQUIRED TO
 BE NON-COMBUSTIBLE FOR THIS CONSTRUCTION
 TYPE. THE MINIMUM ALLOWABLE IS TYPE VI
 CONSTRUCTION.
  
 3) THE FLOOD ZONE ON SHEET AO IS
 SPECIFIED AS X500. THIS PROPERTY IS
 DESIGNED ON THE FEMA FLOOD INSURANCE
 RATE MAP (FIRM) AS A "B" ZONE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-05-26 Cont ID  
Sent By btrobaug Date 2006-05-26 Time 13:41 Rev Time 0.50
Received By btrobaug Date 2006-05-26 Time 13:16 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-04-20 Cont ID  
Sent By btrobaug Date 2006-04-20 Time 10:03 Rev Time 1.00
Received By btrobaug Date 2006-04-20 Time 07:47 Sent To PC
Notes
2006-04-20 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PANEL DESIGNATIONS HAVE CHANGED
 AND THEIR LOCATIONS HAVE CHANGED. PANEL
 "A" WAS A NEW PANEL, NOW SHOWN AS
 EXISTING. PLEASE PROVIDE A PANEL
 SCHEDULE FOR ALL PANELS. PANEL "D" IS
 DESIGNATED AS THE "POOL PANEL", BUT THE
 POOL EQUIPMENT IS NOW LISTED IN PANEL
 "C".
  
 2} THE PANEL/CIRCUIT NUMBERS WERE NOT
 SHOWN AT THE DEVICES AS IN PREVIOUS
 PLANS, PLEASE PUT THEM BACK ON THE PLAN,
 THIS WILL ALSO HELP CLARIFY THE PANEL
 CHANGE SITUATION.
  
 3} THE TANKLESS WATER HEATER THAT WAS
 ADDED TO THE LOAD CALCULATION AT 36000
 WATTS, IS ON A 60 AMP BREAKER,
 36000/240=150 AMPS. THERE IS ANOTHER
 WATER HEATER IN WHAT IS NOW DESIGNATED
 AS PANEL "A" ALSO SHOWN AT 60 AMPS, BUT
 ON A SINGLE POLE BREAKER. PLEASE CLARIFY
 LOADS.
  
 4} THE "EXISTING POOL PANEL 'D' ", NOW
 SHOWN AT A SEPERATE LOCATION ON A WALL,
 MUST COMPLY WITH 225.31 DISCONNECTING
 MEANS AND 2580.32 GROUNDING. THESE WOULD
 BE INDICATED ON THE RISER DIAGRAM.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-02-21 Cont ID  
Sent By btrobaug Date 2006-02-21 Time 15:24 Rev Time 0.50
Received By btrobaug Date 2006-02-21 Time 14:14 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-29 Cont ID  
Sent By btrobaug Date 2005-09-29 Time 12:08 Rev Time 0.50
Received By btrobaug Date 2005-09-29 Time 10:24 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-12 Cont ID  
Sent By btrobaug Date 2005-07-12 Time 10:51 Rev Time 0.50
Received By btrobaug Date 2005-07-12 Time 07:03 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-10 Cont ID  
Sent By btrobaug Date 2005-06-10 Time 08:25 Rev Time 0.75
Received By btrobaug Date 2005-06-10 Time 05:53 Sent To P
Notes
2005-06-07 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LOAD CALCULATION NOTES INDICATE
 USING EXISTING 200 AMP SERVICE. THE
 RISER INDICATES A NEW SERVICE. PLEASE
 CORRELATE.
  
 2} INDICATE HOW THE 200 AMP DISCONNECTS
 A,B&C ARE FED. THERE ARE ONLY 3
 CONDUCTORS FROM THE METER, BUT NO FEED
 THROUGH LUGS OR GUTTER INDICATED.
  
 3} THE PANELS AT THE MAIN HOUSE MUST
 HAVE DISCONNECTING MEANS PER 225.31-36.
 AND GROUNDING PER 250.32. PLEASE SHOW
 COMPLIANCE ON RISER.
  
 4} THE EQUIPMENT GROUND MUST NOT
 PARALLEL THE GROUNDING CONDUCTOR TO THE
 FIRST MEANS OF DISCONNECT PER 250.6.
  
 5}THE "SITTING ROOM" IS STILL PART OF
 THE MASTER BEDROOM AND THEREFORE MUST BE
 ARC FAULT PROTECTED PER 210.12.
  
 6} PANEL "C" CIRCUITS 21 & 23 ARE
 MISLABELED.
  
 IF THERE ARE ANY QUESTIIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-24 Cont ID  
Sent By adarroug Date 2006-05-24 Time 18:24 Rev Time 0.00
Received By adarroug Date 2006-05-24 Time 18:24 Sent To E
Notes
2006-05-24 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-18 Cont ID  
Sent By adarroug Date 2006-04-18 Time 10:08 Rev Time 0.00
Received By adarroug Date 2006-04-18 Time 10:08 Sent To E
Notes
2006-04-18 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 11:21 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 11:21 Sent To E
Notes
2006-02-15 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 16:33 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 16:33 Sent To E
Notes
2005-07-07 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 12:41 Rev Time 0.00
Received By adarroug Date 2005-05-31 Time 12:41 Sent To E
Notes
2005-05-31 00:00:00TO "E" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-07-19 Cont ID  
Sent By jleech Date 2005-07-19 Time 14:56 Rev Time 0.50
Received By jleech Date 2005-07-19 Time 14:56 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-14 Cont ID  
Sent By kstevens Date 2005-06-14 Time 14:48 Rev Time 1.25
Received By kstevens Date 2005-06-14 Time 14:48 Sent To B
Notes
2005-06-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P.2 SANITARY RISER DIAGRAMS DO
 NOT RELFECT THE FLOOR PLANS, NOR DO THEY
 MEET CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 SECOND FLOOR RISER DIAGRAM: (MISLABELED
 AS FIRST FLOOR)
 A. WATER CLOSETS SHALL NOT BE TRAPPED.
 THE W/C HAS AN INTEGRAL TRAP. SECTION
 1002.1.
 B. 11 FIXTURES SHOWN ON THE FLOOR PLAN,
 BUT ONLY 10 FIXTURES ON RISER DIAGRAM.
 SECTION 104.2.1.
 C. LAVS MISLABELD AS SINKS. SECTION
 104.2.1.
 D. SHOWER, TUB, & W/C FIXTURES ARE NOT
 VENTED. SECTION 901.2.1. DOUBLE LAVS
 SHOULD BE CONNECTED BETWEEN THE W/C AND
 THE TUB ON THE BRANCH LINE TO CORRECT
 THIS CODE REQUIREMENT. SECTION 104.2.1.
 E. TUB NOT VENTED IN BATH #3. MAXIMUM
 DISTANCE FOR TRAP FROM VENT IS 6' AND
 TUB TRAP SCALES OUT TO 10'. TABLE 906.1.
 F. WASH MACHINE SHALL NOT DRAIN THRU THE
 HORIZONTAL WET VENT OF THE BATHROOM
 FIXTURES. SECTION 909.1. - WASH MACHINE
 REQUIRES A STANDPIPE. SECTION 1002.1.
 WASH MACHINE REQUIRES A CLEANOUT 4'
 ABOVE THE FLOOR. SECTION 708.10.
 G. SHOWER IN BATH #3 NOT VENTED PER
 TABLE 906.1.
 FIRST FLOOR RISER DIAGRAM:
 A. LAVS MISLABELED AS SINKS. SECTION
 104.2.1.
 B. KITCHEN SINK IN ISLAND, TRAP SHALL
 BE ABOVE THE FLOOR ON A RISER NOT UNDER
 THE SLAB AS SHOWN. SECTION 104.2.1.
 C. KITCHEN SINK RISER SHALL VTR
 DIRECTLY TO STAY IN THE WALL. SECTION
 104.2.1.
 D. TUB IN BATHROOM NOT VENTED. SECTION
 901.2.1.
 E. LAV IN POWDER ROOM SHALL BE
 CONNECTED TO STACK RISER, NOT UNDER SLAB
 AS SHOWN. SECTION 104.2.1.
 F. STACK RISER FOR LAV IN TUB BATHROOM
 SHALL VTR DIRECTLY TO STAY IN THE WALL.
 SECTION 104.2.1.
 2. SEE RED LINE EXAMPLES OF CORRECTIONS
 TO THESE CODE REQUIREMENTS ON ONE SET OF
 PLANS. MAKE CORRECTIONS FOR EACH COMMENT
 AND RESUBMIT FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  