Plan Review Details - Permit 05051816
Plan Review Stops For Permit 05051816
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-21 Cont ID  
Sent By btrobaug Date 2005-07-21 Time 16:50 Rev Time 0.50
Received By btrobaug Date 2005-07-21 Time 16:33 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-11 Cont ID  
Sent By btrobaug Date 2005-06-11 Time 08:38 Rev Time 0.33
Received By btrobaug Date 2005-06-11 Time 08:26 Sent To M
Notes
2005-06-11 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A RISER DIAGRAM
 INDICATING WHERE THE TRANSFER SWITCH
 INTEGRATES IN THE SERVICE. THE NEMA-1
 SWITCH APPEARS TO BE LOCATED OUTDOORS
 AND DOES NOT APPEAR TO BE SERVICE RATED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-19 Cont ID  
Sent By adarroug Date 2005-07-19 Time 15:06 Rev Time 0.00
Received By adarroug Date 2005-07-19 Time 15:06 Sent To E
Notes
2005-07-19 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 15:10 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 15:10 Sent To Z
Notes
2005-07-07 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-09 Cont ID  
Sent By shill Date 2005-06-09 Time 07:09 Rev Time 0.00
Received By shill Date 2005-06-09 Time 07:09 Sent To E
Notes
2005-06-09 00:00:00TO ELEC BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-31 Cont ID  
Sent By adarroug Date 2005-05-31 Time 12:59 Rev Time 0.00
Received By adarroug Date 2005-05-31 Time 12:59 Sent To Z
Notes
2005-05-31 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-06-14 Cont ID  
Sent By pkrauss Date 2005-06-14 Time 15:43 Rev Time 0.20
Received By pkrauss Date 2005-06-14 Time 15:12 Sent To  
Notes
2005-06-14 00:00:00PROVISO:
 MANUFACTURER'S SUBMITTAL DATA DOES NOT
 INDICATE LOCATION OF THE EXHAUST IN
 RELATION TO THE ADJACENT BUILDING, FRESH
 AIR INTAKES I.E., DOORS, WINDOWS,
 GRILLES IN SOFFITS, ETC.
  
 SEE PERMIT 05051816 FOR LP GAS TANK &
 PIPE INSTALLATION; COMPLY WITH NFPA 58
 FOR REQUIRED CLEARANCES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-07-18 Cont ID  
Sent By mmclean Date 2005-07-18 Time 16:58 Rev Time 0.00
Received By mmclean Date 2005-07-18 Time 16:58 Sent To I
Notes
2005-07-18 00:00:00GENERATOR CAN ONLY ENROACH 4FT INTO
 SETBACK.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-07 Cont ID  
Sent By mmclean Date 2005-06-07 Time 13:10 Rev Time 0.00
Received By mmclean Date 2005-06-07 Time 13:10 Sent To I
Notes
2005-06-07 00:00:00DENIED,
 1. NEED TO PROVIDE THE SETBACKS OF THE
 GENERATOR FROM STRUCTURE AND PROPERTY
 LINE.
 2. SETBACKS MUST BE WRITTEN ON TWO COPY
 OF SURVEY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720