| Plan Review Stops For Permit 05051797 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2005-10-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-10-17 |
Time |
12:35 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-10-17 |
Time |
12:35 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2005-09-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-09-20 |
Time |
13:22 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-09-20 |
Time |
13:22 |
Sent To |
E |
|
| Notes |
| 2005-09-20 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)TWO IDENTICAL SETS ARE TO BE | | | SUBMITTED FOR PERMITTING.THE SETS | | | SUBMITTED HAVE SHEETS WHICH HAVE | | | DIFFERENT REVISION NUMBERS AND DIFFERENT | | | DATES ON THE ARCHITECT'S STAMPS.SOME | | | SHEETS CLEARLY DO NOT MATCH; OTHERS HAVE | | | NO CLOUDS BUT HAVE A REVISION INDICATED | | | ON ONE SET BUT NOT ON THE OTHER, SO WHAT | | | WAS REVISED? | | | | | | THE FOLLOWING SHEETS HAVE A DIFFERENT | | | SHEET IN EACH PACKAGE: | | | | | | A7.0C, A7.2, A7.3A, A7.3B, A7.4, A7.5, | | | A7.6 | | | | | | ALL CHANGES TO THE PLAN ARE TO BE | | | CLOUDED.THE TWO SETS ARE TO BE | | | IDENTICAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-09-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-09-02 |
Time |
10:28 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-09-02 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2005-09-02 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.) THE NEW SHEETS ON ONE SET HAS A SEAL | | | WHICH IS SIGNED BUT NOT DATED, | | | FAC61G1-15. | | | | | | 2.)YOU HAVE DECLARED A TYPE II | | | CONSTRUCTION.THIS REQUIRES | | | NONCOMBUSTIBLES IN CONCEALED SPACES OR | | | FIRE RETARDANT WOOD.THE PLANS WILL BE | | | STAMPED WITH THIS REQUIREMENT, FBC707.1. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-06-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-29 |
Time |
18:00 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2005-06-29 |
Time |
17:44 |
Sent To |
PC |
|
| Notes |
| 2005-06-30 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)PROVIDE INTERIOR FINISH | | | CLASSIFICATION FBC TABLE 803.3. | | | | | | 2.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED FS713.13.THE | | | LEGAL DESCRIPTION IS TO BE INCLUDED ON | | | THE NOC.ONLY AN ADDRESS WAS PROVIDED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-09-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-03 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-09-03 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2005-09-03 00:00:00 | NO NEW ELEC SHEETS, STAMPED ON PREVIOUS | | | REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-06-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-06-27 |
Time |
07:46 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-06-27 |
Time |
07:46 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-06-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-06-13 |
Time |
18:58 |
Rev Time |
0.30 |
| Received By |
dpalmer |
Date |
2005-06-13 |
Time |
18:58 |
Sent To |
|
|
| Notes |
| 2005-06-13 00:00:00 | STAMPED 4 SETS ELEC SHEETS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-09-08 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-09-08 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-09-08 |
Time |
10:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-06-14 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-06-14 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-06-14 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2005-06-14 00:00:00 | ****DENIED**** | | | | | | 1) DRAWINGS DON'T SHOW THE LOCATIONS OF | | | EXISTING AND OR NEW EXIT SIGNS AND | | | EMERGENCY LIGHTING FACILITIES. PLEASE | | | INDICATE THE LOCATIONS. | | | | | | 2) PLEASE SHOW THE LOCATIONS OF FIRE | | | EXTINGUISHER(S). | | | | | | 3) PLEASE ILLUSTRATE THE INTERIOR FINISH | | | CLASSIFICATION OF WALLS AND CEILINGS. | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL IF APPLICABLE. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 805-6722 OR 835-2951 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-10-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-14 |
Time |
17:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-14 |
Time |
17:33 |
Sent To |
B |
|
| Notes |
| 2005-10-14 00:00:00 | TO "SHILL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-09-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-20 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-20 |
Time |
10:22 |
Sent To |
B |
|
| Notes |
| 2005-09-20 00:00:00 | TO "SHILL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-08-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-17 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-17 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2005-08-17 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-05-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-06-29 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-27 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2005-06-07 00:00:00 | SENT TO COMM BOARD #58 | | 2005-05-27 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-06-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-06-29 |
Time |
13:35 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2005-06-29 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2005-06-29 00:00:00 | NO MECHANICAL WORK OR CONTRACTOR | | | INDICATED WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2005-06-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-25 |
Time |
10:28 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2005-06-25 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2005-06-25 00:00:00 | NO PLUMBING PLANS REQUIRED. - PLUMBING | | | PERMIT REQUIRED. |
|
|