| 2006-12-07 13:45:30 | A VARIANCE WILL NOT BE REQUIRED AS LONG AS THE |
| | FOLLOWING CRITERIA ARE MET.THE EMERGENCY GENERATOR |
| | NEEDS TO HAVE A MINIMUM OF 3 FOOT CLEARANCE IN FRONT OF |
| | THE ELECTRICAL SERVICE/CONNECTION, IN ACCORDANACE WITH |
| | NFPA 70 TABLE 110.26(A) (1).THIS CAN BE ACCOMPLISHED |
| | BY MOVING THE GENERATOR 3 FEET FROM THE CONCRETE WALL. |
| | PLEASE MAINTAIN 2 FEET FROM THE BUILDING STRUCTURE. |
| | |
| | PLEASE PROVIDE THE FOLLOWING TO THE CONSTRUCTION |
| | SERVICES DEPARTMENT FOR REVIEW AND APPROVAL. |
| | |
| | 1. REVISED SITE PLAN INDICATE THE FOLLOWING: |
| | A) DISTANCE FROM THE PROPERTY LINE TO THE GENERATOR |
| | B) DISTANCE FROM THE INSIDE OF THE WALL TO THE |
| | GENERATOR (3 FEET REQUIRED) |
| | C) DISTANCE FROM THE HOUSE STRUCTURE TO THE GENERATOR |
| | (2 FEET REQUIRED) |
| | D) OVER ALL MEASUREMENT BETWEEN THE PRIVACY WALL & THE |
| | BUILDING STRUCTURE |
| | |
| | 2. PROVIDE A REVISION TO THE CONCRETE SLAB BY THE |
| | ENGINEER OF RECORD: |
| | A) INDICATE EXTENDED SLAB (DIMENSION) |
| | B) INDICATE HOW THE EXTENSION IS TIED INTO THE EXISTING |
| | SLAB |
| | C) PROVIDE REBAR SIZE AND LAYOUT, PLEASE NOTE THE |
| | EXTENSION SHALL BE NO LESS THAN WHAT WAS REQUIRED FOR |
| | THE INITIAL SLAB. |
| | D) A FORM INSPECTION WILL BE REQUIRED |
| | |
| | 3. PROVIDE A REVISION TO THE ELECTRICAL PLANS SHOWING |
| | THE PROPER LOCATION OF THE ELECTRICAL CONNECTIONS.THE |
| | CURRENT SUBMITTAL INDICATES THE ELECTRICAL CONNECTION |
| | TO THE GENERATOR TOWARDS THE HOUSE STRUCTURE WHEN IN |
| | REALITY IT IS TOWARD THE CONCRETE WALL.THE PLANS MUST |
| | SHOW THE ELECTRICAL CONNECTION ORIENTATION AS INSTALLED |
| | IN THE FIELD. |
| | |
| | 4. GAS REVISIONS IF ANY ALTERATIONS ARE TO BE DONE. |
| | |