Plan Review Details - Permit 05051674
Plan Review Stops For Permit 05051674
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-03 Cont ID  
Sent By jwitmer Date 2005-08-03 Time 17:19 Rev Time 0.33
Received By jwitmer Date 2005-08-03 Time 17:13 Sent To PC
Notes
2005-08-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051674
 ADD: 339 ALHAMBRA
 CONT:ATLAS SWIMMING POOLS
 TEL: (561)585-0005
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
  
  
 BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE
 PROVIDED WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH
 424.2.17.1.14.
  
  
 2)13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.
  
 EXCEPTION: OUTDOOR POOLS DERIVING OVER
 70 PERCENT OF THE ENERGY FOR HEATING
 FROM NON-DEPLETABLE ON SITE-RECOVERED
 SOURCES COMPUTED OVER AN OPERATING
 SEASON ARE EXEMPT FROM THIS
 REQUIREMENT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-14 Cont ID  
Sent By lsmith Date 2005-07-14 Time 09:05 Rev Time 0.50
Received By lsmith Date 2005-07-14 Time 09:05 Sent To  
Notes
2005-07-14 00:00:00BUILDING PLAN REVIEW: FAILED:
  
  
 COME ON SID:HELP ME HELP YOU:
  
 PLANS MUST BE "SIGNED, SEALED, DATED
 (NOT DATE STAMPED FROM LAST YEAR) AND
 "ANY" HAD WRITTEN NOTES ON THE PLANS
 MUST BE INITIALED BY THE ENGINEER.
  
 YOUR FIRM # & YOUR PE NUMBER MUST BE IN
 THE TITLE BLOCK.
  
 SEE THE COMMENTS FROM THE OTHER
 REVIEWERS.YOU ARE NOT ADDRESSING THEIR
 PRIOR COMMENTS.
  
 I DO NOT LIKE TO LOOK AT A PERMIT
 APPLICATION MORE THAN ONCE
  
 THANKS FOR YOUR HELP IN ADVANCE
 SINCERELY
 YOUR "FAVORITE PLAN REVIEWER" LEA

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-16 Cont ID  
Sent By lsmith Date 2005-06-16 Time 12:45 Rev Time 0.25
Received By lsmith Date 2005-06-16 Time 12:45 Sent To  
Notes
2005-06-16 00:00:00BUILDING PLAN REVIEW: FAILED
  
 SEE ELEC. & PLUMB. NOTES REGARDING
 LICENSE NUMBER INFORMATION REQUIRED ON
 PLANS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-14 Cont ID  
Sent By dpalmer Date 2005-07-14 Time 20:27 Rev Time 0.25
Received By dpalmer Date 2005-07-14 Time 20:27 Sent To P
Notes
2005-07-14 00:00:00CHANGES TO PLANS MADE BY
 ENGINEER/CONTRACTOR OF RECORD IN LOBBY.
  
  
  
 **
 NO NEW ELECTRICAL PANEL, SHOWN AS
 EXISITNG.
 ALL OVERHEAD ELECTRICAL LINES TO MEET
 680.8 NEC.
 NO ELECTRICAL HEAT-PUMP.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-28 Cont ID  
Sent By dpalmer Date 2005-06-28 Time 10:48 Rev Time 0.25
Received By dpalmer Date 2005-06-28 Time 10:46 Sent To P
Notes
2005-06-28 00:00:00********** UNSAT 2ND REVIEW **********
  
 PLEASE SEE NOTES 3&4 FROM PREVIOUS
 REVIEW.
  
 1)NOTE: PLEASE CORRELATE ALL EQUIPMENT
 WITH ELECTRICAL WIRING DIAGRAM.
 PLEASE SEE ONLY ONE PUMP IS SHOWN ON
 RISER?
 215.5
  
 2)NOTE: PLEASE SEE PLANS STILL INDICATE
 NEW PANEL, HOWEVER NO INFORMATION WAS
 SUBMITTED FOR THIS. PLEASE SEE PREVIOUS
 NOTE;#4.
  
 3)NOTE: PLEASE SEE FS 553.80(2)B) WITH
 RESPECT TO DESIGN PROFESSIONAL FOR
 REPEAT COMMENTS.
  
 ***** PLEASE NOTE***** PLANS MAY NOT BE
 ABLE TO STAMPED DUE TO PLUMB COMMENTS ON
 SAME PAGE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-08 Cont ID  
Sent By dpalmer Date 2005-06-08 Time 08:14 Rev Time 0.30
Received By dpalmer Date 2005-06-08 Time 08:14 Sent To P
Notes
2005-06-08 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE INCLUDE ALL LICENSE
 INFORMAION REQUIRED ON TITLE BLOCKS PER
 FAC 61G15-23.002. PLEASE ALSO SEE FS
 471.023
 THIS IS REQUIRED ON ALL SHEETS WHEATHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWERS.
  
 2)NOTE: PLEASE SEE OVERHEAD ELECTRICAL
 LINES ARE SHOWN WITHIN THE RESTRICATED
 AREA PER 680.8
  
 3)NOTE: PLEASE CORRELATE PERMIT
 APPLICATION AND PLANS.
 PLEASE SEE PLANS SHOW A NEW HEAT PUMP,
 NEW ELECTRICAL PANEL ETC.
 PLEASE SUBMIT COMPLETE LOAD CALCULATIONS
 FOR NEW HEAT PUMP.
 PLEASEINCLUDE ALL EXISTING LOADS AND
 SIZE OF EXISTING SERVICE.
  
 4)NOTE: PLEASE SEE PLANS INDICATE AN NEW
 PANEL. PLEASE SHOW FEEDERS,CONDUIT, OCP
 FROM EXISTINGETC.
 215.5
  
 5)NOTE: PLEASE INCLUDE MANUFACTURE SPECS
 FOR NEW HEATER SHOWING LISTING FROM A
 NRTL.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-14 Cont ID  
Sent By adarroug Date 2005-07-14 Time 16:46 Rev Time 0.00
Received By adarroug Date 2005-07-14 Time 16:46 Sent To E
Notes
2005-07-14 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-27 Cont ID  
Sent By adarroug Date 2005-06-27 Time 11:08 Rev Time 0.00
Received By adarroug Date 2005-06-27 Time 11:08 Sent To I
Notes
2005-06-27 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-06 Cont ID  
Sent By mjacobs Date 2005-06-06 Time 15:06 Rev Time 0.00
Received By mjacobs Date 2005-06-06 Time 15:06 Sent To E
Notes
2005-06-06 00:00:00TO 'E' BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-16 Cont ID  
Sent By lsmith Date 2005-06-16 Time 12:45 Rev Time 0.00
Received By lsmith Date 2005-05-26 Time 16:38 Sent To  
Notes
2005-05-26 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-07-30 Cont ID  
Sent By jleech Date 2005-07-30 Time 13:48 Rev Time 0.50
Received By jleech Date 2005-07-30 Time 13:48 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-07-13 Cont ID  
Sent By jleech Date 2005-07-13 Time 08:02 Rev Time 1.00
Received By jleech Date 2005-07-13 Time 08:02 Sent To B
Notes
2005-07-13 00:00:00DENIED;
 PREVIOUS PLAN REVIEW COMENTS NOT
 ADDRESSED.
 PIPING SCHEMATIC DOES NOT REFLECT THE
 SPECIFICATIONS OR PIPING DIAGRAM. PIPING
 DIAGRAM INDICATES 2 PUMPS AND SCHEMATIC
 SHOWS ONE. SCHEMATIC SHOWS A 1" VENT FOR
 MAIN DRAIN MAIN DRAIN DETAIL SHOWS
 1 1/2".
 SCHMATIC SHOWS A VACUUM, BUT
 SPECIFICATIONS AND PIPING DIAGRAM DO NOT
 SHOW A VACUUM LINE. PLEASE CORRELATE
 SCHMATIC WITH PIPING DIAGRAM AND
 SPECIFICATIONS. SECTION 104.2.1.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-14 Cont ID  
Sent By kstevens Date 2005-06-14 Time 07:49 Rev Time 0.50
Received By kstevens Date 2005-06-14 Time 07:49 Sent To B1
Notes
2005-06-14 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1.ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 2. PIPING SCHEMATIC DOES NOT REFLECT THE
 SPECIFICATIONS OR PIPING DIAGRAM. PIPING
 DIAGRAM INDICATES 2 PUMPS AND SCHEMATIC
 ONLY SHOWS ONE. SPECIFICATIONS DO NOT
 INDICATE A POOL HEATER, OR VACUUM LINE,
 BUT SCHEMATIC SHOWS BOTH. SCHEMATIC
 SHOWS A VACUUM LINE, BUT SPECIFICATIONS
 AND PIPING DIAGRAM DO NOT SHOW A VACUUM.
 PLEASE CORRELATE SCHEMATIC WITH PIPING
 DIAGRAM AND SPECIFICATIONS. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2005-06-03 Cont ID  
Sent By ebowers Date 2005-06-03 Time 11:54 Rev Time 0.00
Received By ebowers Date 2005-06-03 Time 11:54 Sent To I
Notes
***NONE***