Plan Review Details - Permit 05051661
Plan Review Stops For Permit 05051661
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-10-12 Cont ID  
Sent By alange Date 2005-10-12 Time 09:19 Rev Time 1.00
Received By alange Date 2005-10-12 Time 07:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-07-14 Cont ID  
Sent By alange Date 2005-07-14 Time 12:38 Rev Time 1.50
Received By alange Date 2005-07-14 Time 10:59 Sent To  
Notes
2005-07-14 00:00:00DENIED
  
 1.SHOW SPACING OF BOLTS ON FRAMING AT
 CORNERS.AND FOR BOLTS HOLDING DOWN
 BOTOM PLATE.
  
 2.ENGINEER OF RECORD MUST SIGN AND
 SEAL ALL STRUCTURAL PAGES. FS 481.221
  
 3. DRAFT STOPPING IN FLOOR/CEILING
 ASSEMBLIES SHALL SEPERATE USEABLE SPACES
 INTO TWO OR MORE APPROXIMATE AREAS WITH
 NO AREA GREATER THAN 500 SQ. FT.
 SHOW HOW THIS WILL BE OBTAINED ON PLANS.
 FBC 2305.2.2 (1)
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-10-03 Cont ID  
Sent By btrobaug Date 2005-10-03 Time 14:33 Rev Time 0.50
Received By btrobaug Date 2005-10-03 Time 12:42 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-15 Cont ID  
Sent By btrobaug Date 2005-06-15 Time 12:48 Rev Time 0.50
Received By btrobaug Date 2005-06-15 Time 11:50 Sent To Z
Notes
2005-06-15 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ENGINEER OF RECORD MUST SIGN AND
 SEAL PLANS PER 481.221 FS.
  
 2} PROVIDE THE AIC RATING OF THE SERVICE
 EQUIPMENT PER 110.9 & 10.
  
 3} CORRECT THE NOTE REGARDING 21/2"
 CONDUIT W/3 #2/0 FOR THE GEC.@ RISER.
  
 4} THE 125AMP MAIN BREAKERS FOER APT.
 FEEDERS ARE SMALLER THAN THE CALCULATED
 LOAD. PLEASE CLARIFY.
  
 5} VERIFY AND SUPPLY SPECIFICATIONS FOR
 THE TANKLESS HEATER.
  
 6} THE SMOKE DETECTOR IN THE BATHROOM ON
 THE SECOND FLOOR IS IN VIOLATION OF
 8-1.4.2 NFPA-72.
  
 7} BEDROOM #1 NEEDS AN ADDED RECEPTACLE
 TO COMPLY WITH 210.52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2005-05-24 Cont ID  
Sent By ptjomsto Date 2005-05-24 Time 13:20 Rev Time 0.00
Received By ptjomsto Date 2005-05-24 Time 13:20 Sent To  
Notes
2005-05-24 00:00:00HISTORIC APPROVED 5/24/05 BY F MITTNER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-30 Cont ID  
Sent By adarroug Date 2005-09-30 Time 14:54 Rev Time 0.00
Received By adarroug Date 2005-09-30 Time 14:54 Sent To E
Notes
2005-09-30 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-23 Cont ID  
Sent By adarroug Date 2005-06-23 Time 10:52 Rev Time 0.00
Received By adarroug Date 2005-06-23 Time 10:52 Sent To M
Notes
2005-06-23 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-14 Cont ID  
Sent By alange Date 2005-07-14 Time 13:26 Rev Time 0.00
Received By alange Date 2005-05-24 Time 18:12 Sent To  
Notes
2005-05-24 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-07-05 Cont ID  
Sent By prafter Date 2005-07-05 Time 08:30 Rev Time 0.50
Received By prafter Date 2005-07-05 Time 08:30 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-10-03 Cont ID  
Sent By jleech Date 2005-10-03 Time 15:20 Rev Time 0.50
Received By jleech Date 2005-10-03 Time 15:20 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-07-06 Cont ID  
Sent By btrobaug Date 2005-10-03 Time 14:33 Rev Time 0.75
Received By jleech Date 2005-07-06 Time 18:05 Sent To B
Notes
2005-07-06 00:00:00DENIED;
 1.COMPLY WITH ELECTRICAL PLAN REVIW NOTE
 #1. ALSO PAGES 10 & 11 ARE NOT SEALED
 AND SIGNED.
 2.BACKFLOW PROTECTION IS REQUIRED AT
 WATER METER CITY ORD. # 2853-95.
 3.PLEASE REMOVE WATER HEATER CONNECTION
 DETAIL IF TANKLESS HEATERS ARE BEING
 USED. TANKES HEATERS SHOWN ON FLOOR PLAN
 AND PAGE 10.
 4.SHUTOFF VALVES ARE REQUIRED FOR EACH
 UNIT. PLEASE SHOW LOCATION ON PLANS.
 5. IS 2ND FLOOR SANITARY RISER RUN DOWN
 OUTSIDE WALL AS SHOWN ON DRAWINGS?
 6.IF CAST IRON IS BAD ON THE INSIDE THE
 BUILDING SEWER WILL ALSO REQUIRE
 REPLACEMENT. SEE NOTE ON SHT 11.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2005-06-22 Cont ID  
Sent By aaponte Date 2005-06-22 Time 11:29 Rev Time 0.00
Received By aaponte Date 2005-06-22 Time 11:29 Sent To  
Notes
***NONE***