Plan Review Details - Permit 05051520
Plan Review Stops For Permit 05051520
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-06-03 Cont ID  
Sent By jhiggins Date 2005-06-03 Time 08:40 Rev Time 0.00
Received By jhiggins Date 2005-06-03 Time 08:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-10-18 Cont ID  
Sent By jwitmer Date 2005-10-18 Time 07:28 Rev Time 0.55
Received By jwitmer Date 2005-10-18 Time 07:28 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-08-27 Cont ID  
Sent By jwitmer Date 2005-08-27 Time 11:40 Rev Time 0.77
Received By jwitmer Date 2005-08-27 Time 11:19 Sent To  
Notes
2005-08-27 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051520
 ADD: 217 BUTLER ST
 CONT: CREATIVE BUILDING&
 RESTORATION
  
 TEL: (561)735-1110
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)NOTE,
 EGRESS WINDOWS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 PROVIDE FLORIDA COVER PAGE W/
 ASSOCIATED PRODUCT APPROVAL REPORT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-24 Cont ID  
Sent By jwitmer Date 2005-07-24 Time 15:13 Rev Time 1.11
Received By jwitmer Date 2005-07-24 Time 15:13 Sent To PC
Notes
2005-07-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051520
 ADD: 217 BUTLER ST
 CONT: CREATIVE BUILDING&
 RESTORATION
  
 TEL: (561)735-1110
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)NOTE,
 EGRESS WINDOWS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-21 Cont ID  
Sent By jwitmer Date 2005-06-21 Time 11:53 Rev Time 1.22
Received By jwitmer Date 2005-06-21 Time 11:53 Sent To  
Notes
2005-06-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051520
 ADD: 217 BUTLER ST
 CONT: CREATIVE BUILDING&
 RESTORATION
  
 TEL: (561)735-1110
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 APARTMENT# 9 (NEW APARTMENT)SHEET A2:
  
 2A)INDICATES THE FLOOR FRAMING
 DETAIL WITH THE USE OF 5/8 " WEDGE
 ANCHORS, PROVIDE A SECTION DETAIL OF THE
 LEDGER, BUCKETS AND PROFILE OF TRUSS.
  
 2B) INDICATESTHE USES OF A 4X4 WOOD
 POST, LOCATION OF POST IS 9'-1" FROM
 WALL, IS THIS TO BE LOCATED IN THE FIRST
 FLOOR BEDROOM WALL?HOW WILL POST BE
 ANCHORED?
  
 2C) PLANS INDICATE THE USE OF A SIMPSON
 LUS212-2, SIMPSON 2005 CATALOG DOES NOT
 INDICATE SUCH A HANGER?
  
 2D) SIMPSON HANGER IDENTIFIED AS
 LUS212-2, DESIGNER TO PROVIDE WHAT TYPE
 OF ANCHOR SHALL BE USED TO SECURE THE
 HANGER INTO THE CONCRETE BEAM?
  
 3) PLANS DO NOT PROVIDE THE FLOOR PLAN
 INDICATING THE EXTERIOR BALCONY AND
 STAIRWAY, PLEASE PROVIDE, TWO ISSUES;
  
 3A)1006.2.4 EXTERIOR STAIRS SHALL BE
 SEPARATED FROM THE INTERIOR OF THE
 BUILDING BY WALLS WITH A FIRE
 RESISTANCE RATING OF NOT LESS THAN 1
 HOUR,WITH FIXED OR SELF-CLOSING
 OPENING PROTECTIVES AS REQUIRED FOR
 ENCLOSEDSTAIRS.THIS PROTECTION
 SHALL EXTEND VERTICALLY FROM THE GROUND
 TO A POINT 10 FT (3048 MM) ABOVE THE
 TOPMOST LANDING OR THE ROOF LINE,
 WHICHEVER IS LOWER, AND HORIZONTALLY 10
 FT (3048 MM) FROM EACH SIDE OF
 THE STAIRWAY.OPENINGS WITHIN THE 10 FT
 (3048 MM) HORIZONTAL EXTENSION
 OF THE PROTECTED WALLS BEYOND THE
 STAIRWAY SHALL BE EQUIPPED WITH FIXED
 3/4 HOUR ASSEMBLIES.
  
 3B)1006.2.2 EXTERIOR STAIRWAYS SHALL BE
 PERMITTED WHERE AT LEAST ONE DOOR
 FROM EACH TENANT OPENS ONTO A
 ROOFED-OVER OPEN BALCONY, PORCH, OR
 GALLERY, OR SIMILAR SPACE SERVED BY AT
 LEAST TWO STAIRWAYS LOCATED TO PROVIDE A
 CHOICE OF INDEPENDENT, UNOBSTRUCTED
 MEANS OF EGRESS DIRECTLY TO THE
 GROUND, EXCEPT A SINGLE STAIRWAY SHALL
 BE ALLOWED WHEN A SINGLE EXIT IS
 PERMITTED BY1026.
  
 4) NEW PROPOSED BEDROOM:
 4A) PROVIDE INFORMATION ON THE CLEAR
 OPENING OF THE REQUIRED EGRESS WINDOW.
 1005.4.1 EVERY SLEEPING ROOM LOCATED ON
 THE FIRST, SECOND AND THIRD
 STORY OR WITHIN BASEMENTS OF GROUP R
 OCCUPANCIES SHALL HAVE AT LEAST ONE
 EXTERIOR EMERGENCY ESCAPE AND RESCUE
 OPENING.THE EMERGENCY ESCAPE AND
 RESCUE OPENING SHALL BE PERMITTED TO
 OPEN INTO A SCREEN ENCLOSURE, OPEN
 TO THE ATMOSPHERE, WHERE A SCREEN DOOR
 IS PROVIDED LEADING AWAY FROM THE
 RESIDENCE.
  
 4B) 905.2.1 APPROVED SINGLE-STATION OR
 MULTIPLE STATION SMOKE DETECTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 72,
 CHAPTER 2, WITHIN EVERY DWELLING UNIT
 WITHIN AN APARTMENT HOUSE, CONDOMINIMUM,
 OR TOWNHOUSE AND EVERY GUEST OR SLEEPING
 ROOM IN A MOTEL, HOTEL, OR DORMITORY &
 SLEEPING ROOMS IN RESIDENTIAL CARE/
 ASSISTED LIVING OCCUPANCIES. WHERE MORE
 THAN ONE DETECTOR IS REQUIRED TO BE
 INSTALLED WITHIN INDIVIDUAL DWELLING
 UNIT, THE DETECTOR SHALL BE WIRED IN
 SUCH A MANNER THAT THE ACTUATION OF ONE
 ALARM WILL ACTIVATE ALL THE ALARMS IN
 THE INDIVIDUAL UNIT.
  
 5)PLANS DO NOT INDICATE HOW THE 1HR
 TENANT SEPERATION WILL BE MET VERTICALLY
  
 OR HORIZONTALLY? 704.3.1.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-09-27 Cont ID  
Sent By dpalmer Date 2005-09-27 Time 21:14 Rev Time 0.30
Received By dpalmer Date 2005-09-27 Time 21:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-08-15 Cont ID  
Sent By dpalmer Date 2005-08-15 Time 18:40 Rev Time 1.50
Received By dpalmer Date 2005-08-15 Time 18:37 Sent To  
Notes
2005-08-15 00:00:00******* UNSAT 3RD REVIEW ************
  
 PLEASE SEE ALL NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE SEENO COMMENTS SEEMED TO HAVE
 BEEN ADDRESSED.
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 SUBMITTED.
 PLEASE SEE SOME CIRCUITING STILL MISSING
 ON PLANS.
 PLEASE SEE PLANS HAVE BEEN REDLINED FOR
 THESE ONPREVIOUS PLANS.
  
 2)NOTE: PLEASE SEE MISSING RECEPTS
 REQUIRED PER 210.52.
 PLEASE SEE FBC 104.2.1, TECHNICAL CODES
 MAY NOT BE REFERENCED IN WHOLE OR IN
 PART.
 PLEASE SEE LOCATIONS REDLINED ON PLANS
 AT MISSING LOCATIONS.
  
 3)NOTE: PLEASE SEE CIRCUITING OF SD'S.
 PLEASE ALSO SEE NOTES IN REF TO ARC
 FAULT PROTECTION. PLEASE SEE NOTES
 MENTIONS ARC FAULT FOR RECEPTS ONLY.
 PLEASE SEE NFPA-72 8-1.4.2.1 FOR
 PLACEMENT OF SD'S. PLEASE SEE KITCHEN
 SD: AND ACCORD TO NFPA 8-1.4.2, PLEASE
 SEE SD'S WITH/IN 3' OF BATH DRS, 20 ' OF
 COOKING APPLIANCE.
 PLEASE SEE THESE ITEMS WERE REDLINED ON
 PREVIOUS PLANS.
  
 4)NOTE: PLEASE SEE 210.12 2002 NEC,
 WHICH REQUIRES ALL "OUTLETS" IN BEDRMS
 TO BE ARC FAULT PROTECTED. PLEASE SEE
 "ELECTRICAL NOTES" ON PLANS MENTIONS
 ONLY RECEPTS. NOTED ON SD COMMENT.
 PLEASE ALSO VERIFY CIRCUITING, SD'S LTS,
 FANS ETC. SEE REDLINED PLANS.
  
 5)NOTE: PLEASE SEE 100A OCP SHOWN FOR
 RANGE ON #8 AWG. PLEASE SEE 240.4,310.16
 ETC FOR MAX OCP FOR 8KW RANGE.
 SAME COMMENT, NO CHANGE.
  
 6)NOTE: PLEASE SEE MAX OCP (60A) FOR
 WATER HEATER SHALL BE 150%. PLEASE SEE
 60A OCP SHOWN ON #10 AWG AND ON A 4.5KA
 UNIT.
 240.4,310.16,422.11E
 SAME COMMENT, NO CHANGE.
  
 7)NOTE: PLEASE SEE 240.4,310.16 ETC FOR
 MAX OCP FOR A/C UNITS ON #12. PANEL
 SCHEDULES SHOWS 40A OCP ON #12 AWG.
 PLEASE ADJUST.
 SAME COMMENT, NO CHANGE
  
 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SEE NEW PANEL AND MAINS NOW
 SHOWN.
 NO CHANGES.
  
 9)NOTE: PLEASE VERIFY NEW GROUNDING
 ELECTRODE SYSTEM FOR NEW PANELS???
 PLEASE VERIFY IF GROUNDING ELECTRODE
 SYSTEM ALREADY EXISTS?
 PLEASE SEE 250.6,250.24 ETC FOR LOCATION
 OF GROUDING ELECTRODE SYSTEM.
 PREVIOUS NOTES MENTIONED TO CLARIFY
 EXISTING AND NOW PLANS SHOW A NEW SYSTEM
 ONLY TO NEW MAINS???
 250.6,250.24.
 ONLY "EQUIPMENT GROUNDING CONDUCOTRS"
 ARE REQUIRED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 10)NOTE: PLEASE SEE A GUTTER? IS NOW
 SHOWN FROM DISCONNECT TO SUB PANEL IN
 UNIT UPSTAIRS?
 PLEASE VERIFY IF GUTTER WILL INDEED BE
 INSTALLED. IF SO, PLEASE INCLUDE SIZE OF
 GUTTER ON RISER DIAGRAM.
 215.5,366
  
 11)NOTE: PLEASE SEE GARBAGE DISPOSAL IS
 SHOWN ON SMALL APPLIANCE CIRCUIT. THIS
 IS NOT PERMITTED. 210.52B1
  
 12)NOTE: PLEASE SEE NOTES WHICH WERE
 REDLINED ON PREVIOUS PLANS: "NOTES TO
 ELECTRICAL PLANS", REFERENCE WRONG NEC
 CODES FOR REQUIREMENTS.
 NOTE MENTIONS, ARC FAULT FOR RECEPTS,
 PREVIOUS NOTES:
 NOTE MENTIONS SPACING IN KITCHEN COUNTER
 PER 210.8, THIS IS PER 210.52C1, 210.8A6
 IS FOR GFI PROTECTION OF KITCHEN
 COUNTERSPACE RECEPTS.
 NOTE MENTIONS, LIGHTING OUTLETS PER
 210.72? THIS SHOUDL BE 210.70.
 THESE WERE CIRCILED AND REDLINE DON
 PREVIOUS PLANS.
  
  
 13)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL AND PLANS BEING REVIEWED
 WITH THE SAME COMMENTS. THIS WAS GIVEN
 AS ONLY A NOTICE ON PREVIOUS REVIEW,
 HOWEVER DUE TO PLANS WITH REPEATED
 COMMENTS, A 4X FEE HAS NOW BEEN ASSESSED
 IN THE AMOUNT OF $480.00 TO THE DESIGN
 PROFESSIONAL.
 PLEASE SEE ONE SET OF EACH SUBMITTED
 ELECTRICAL/BLDG PLANS HAVE NOW BEEN
 RETAINED FOR FILE AND POSSIBLE REVIEW BY
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEER'S FOR CODE COMPLIANCE AND SAID
 REPEAT COMMENTS.
 PLEASE SEE THIS FEE IS THE
 RESPONSIBILITY OF THE DESIGN
 PROFESSIONAL AND NOT OF THE OWNER OR
 CONTRACTOR. THIS FEE WHICH IS REQUIRED
 UNDER FS MUST BE PAID BEFORE PLANS MAY
 BE RE-SUBMITTED.
 IF PLANS COME BACK IN AGAIN WITH ANY OF
 THE SAME COMMENTS AS PREVIOUS REVIEWED,
 A4X FEE SHALL BE ASSCESSED.
 IT IS SUGGESTED, IF THERE ARE ANY
 QUESTIONS, A MEETING BE SET UP WITH THE
 DESIGNER, ENGINEER, CONTRACTOR AND CITY
 OF WEST PALM BEACH PLAN REVIEW STAFF.
  
 PLEASE CALL TO SET UP ANY MEETINGS WITH
 PLANS REVIEWER(S) WITH
 MR. JIM WITMER(INTERIM CHEIF PLANS
 EXAMINER).
 561-805-6715
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD SHEETS SHALL BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-20 Cont ID  
Sent By dpalmer Date 2005-07-20 Time 12:48 Rev Time 1.33
Received By dpalmer Date 2005-07-20 Time 12:48 Sent To  
Notes
2005-07-20 00:00:00******* UNSAT 2ND REVIEW ************
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE SOME NEW NOTES DUE TO
 INFORMATION NOW SHOWN ON PLANS.
  
 1)NOTE: PLEASE SHOW ALL CIRCUTING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 SUBMITTED.
 PLEASE SEE SOME CIRCUITING STILL MISSING
 ON PLANS.
  
 2)NOTE: PLEASE SEE MISSING RECEPTS
 REQUIRED PER 210.52.
  
 3)NOTE: PLEASE SEE CIRCUITING OF SD'S.
 PLEASE ALSO SEE NOTES IN REF TO ARC
 FAULT PROTECTION.
 PLEASE SEE NFPA-72 8-1.4.2.1 FOR
 PLACEMENT OF SD'S. PLEASE SEE KITCHEN
 SD: AND ACCORD TO NFPA.
  
 4)NOTE: PLEASE SEE 210.12 2002 NEC,
 WHICH REQUIRES ALL "OUTLETS" IN BEDRMS
 TO BE ARC FAULT PROTECTED. PLEASE SEE
 "ELECTRICAL NOTES" ON PLANS MENTIONS
 ONLY RECEPTS.
 PLEASE ALSO VERIFY CIRCUITING, SD'S LTS,
 FANS ETC.
  
 5)NOTE: PLEASE SEE OCP SHOWN FOR RANGE
 ON #8 AWG. PLEASE SEE 240.4,310.16 ETC
 FOR MAX OCP FOR 8KW RANGE.
  
 6)NOTE: PLEASE SEE MAX OCP FOR WATER
 HEATER SHALL BE 150%. PLEASE SEE 60A OCP
 SHOWN ON #10 AWG AND ON A 4.5KA UNIT.
 240.4,310.16,422.11E
  
 7)NOTE: PLEASE SEE 240.4,310.16 ETC FOR
 MAX OCP FOR A/C UNITS ON #12. PANEL
 SCHEDULES SHOWS 40A OCP ON #12 AWG.
 PLEASE ADJUST.
  
 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SEE NEW PANEL AND MAINS NOW
 SHOWN.
  
 9)NOTE: PLEASE VERIFY NEW GROUNDING
 ELECTRODE SYSTEM FOR NEW PANELS???
 PLEASE VERIFY IF GROUNDING ELECTRODE
 SYSTEM ALREADY EXISTS?
 PLEASE SEE 250.6,250.24 ETC FOR LOCATION
 OF GROUDING ELECTRODE SYSTEM.
 PREVIOUS NOTES MENTIONED TO CLARIFY
 EXISTING AND NOW PLANS SHOW A NEW SYSTEM
 ONLY TO NEW MAINS???
 250.6,250.24.
 ONLY "EQUIPMENT GROUNDING CONDUCOTRS"
 ARE REQUIRED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 10)NOTE: PLEASE SEE A GUTTER? IS NOW
 SHOWN FROM DISCONNECT TO SUB PANEL IN
 UNIT UPSTAIRS?
 PLEASE VERIFY IF GUTTER WILL INDEED BE
 INSTALLED. IF SO, PLEASE INCLUDE SIZE OF
 GUTTER ON RISE DIAGRAM.
 215.5
  
 11)NOTE: PLEASE SEE ATTACHE DCOPY OF
 FS553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL AND PLANS BEING REVIEWED
 WITH THE SAME COMMENTS. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD SHEETS SHALL BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-13 Cont ID  
Sent By dpalmer Date 2005-06-13 Time 18:04 Rev Time 0.30
Received By dpalmer Date 2005-06-13 Time 18:04 Sent To  
Notes
2005-06-13 00:00:00***********UNSAT **************
  
 1)NOTE: PLEASE CORRELATE PLANS , PERMIT
 APPLICATION AND SCOPE OF WORK TO BE
 DONE.
 PLEASE SEE PLANS MENTIONS, APTS, 7,9,1
 AND 2??
 215.5
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 TO BE SUBMITTED.
 PLEASE INDICATE ALL ELECTRICAL WHICH IS
 EXISTING. MUST MEET 2002 NEC, OR WILL BE
 REQUIRED TO BE BROUGHT UP TO CODE.
 PLEASE SHOW ALL MIN CIRCUITING PER 2002
 210.52,210.52D,210.11C1,C2,C3 ETC.
 NEC.215.5
  
 3)NOTE: PLEASESEE BLDG REVIEW COMMENTS
 FOR CHANGING ONE UNIT INOT TWO AND
 POSSIBILITY OF TWO PERMITS REQUIRED FOR
 PERMITTING AND ADDRESSING OF EACH UNIT?
  
 4)NOTE: PLEASE SEE NFPA-72 8-1.4.1.6.2
 FOR MISSING SD'S REQUIRED.
  
 5)NOTE: PLEASE INCLUDE A RISER DIAGRAM
 SHOWING NEW PANELS/DISC'S ETC.
 FEEDERS, OCP, CONDUITS, GROUNDING ETC.
  
 6)NOTE: PLEASE INCLUDE LOAD CALCUALTIONS
 FOR ADDED LOAD TO EXISTING? SERVICE?
 220
  
 PLEASE SEE DUE TO PLANS NOT BEING
 COMPLETE AT THIS TIME, THERE MAY BE
 COMMENTS FOR FOLLOWING REVIEW.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-09-30 Cont ID  
Sent By mwennerg Date 2005-09-30 Time 10:17 Rev Time 0.00
Received By mwennerg Date 2005-09-30 Time 10:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2005-09-01 Cont ID  
Sent By mwennerg Date 2005-09-01 Time 15:10 Rev Time 0.00
Received By mwennerg Date 2005-09-01 Time 15:10 Sent To  
Notes
2005-09-01 00:00:00******DENIED******
  
 1) PLEASE SEE ELECTRICAL COMMENTS
 REGARDING SMOKE DETECTOR LOCATION TO
 BATHROOM DOORS. IN ADDITION, THEY SHALL
 BE PLACED A MINIMUM OF 3' FROM HVAC
 DIFFUSERS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-03 Cont ID  
Sent By mwennerg Date 2005-08-03 Time 14:19 Rev Time 0.00
Received By mwennerg Date 2005-08-03 Time 14:19 Sent To  
Notes
2005-08-03 00:00:00******PROVISO******
  
 PLEASE SEE ELECTRICAL NOTE IN REGARDS TO
 SMOKE ALARM PLACEMENT. PLANS WILL BE
 STAMPED AT TIME OF RESUBMITTAL FOR OTHER
 REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-06-15 Cont ID  
Sent By mwennerg Date 2005-06-15 Time 14:50 Rev Time 0.00
Received By mwennerg Date 2005-06-15 Time 14:49 Sent To  
Notes
2005-06-15 00:00:00****DENIED****
  
 1) PLEASE SHOW ALL THE LOCATIONS OF
 SMOKE DETECTORS. THEY SHALL BE ARRANGED
 SO THAT THE ACTIVATION OF ONE SMOKE
 DETECTOR WILL CAUSE ALL IN THE UNIT OR
 APT. TO OPERATE.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 3) PLEASE PROVIDE CLARIFICATION AS TO
 SCOPE OF WORK AND WHAT APARTMENTS ARE
 UNDER THIS APPLICATION.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 16:02 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 16:02 Sent To  
Notes
2005-10-05 00:00:00TO "COMM" BD#19
2005-09-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 09:46 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 09:46 Sent To  
Notes
2005-08-09 00:00:00WAITING FOR "COMM" BD
 TO "COMM" BD#26

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-03 Cont ID  
Sent By adarroug Date 2005-08-03 Time 13:47 Rev Time 0.00
Received By adarroug Date 2005-08-03 Time 13:47 Sent To FIRE
Notes
2005-08-03 00:00:00TO "MWENNEGREN" DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-11 Cont ID  
Sent By adarroug Date 2005-07-11 Time 14:09 Rev Time 0.00
Received By adarroug Date 2005-07-11 Time 14:09 Sent To  
Notes
2005-07-19 00:00:00TO "COMM" BD#5
2005-07-11 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-09 Cont ID  
Sent By shill Date 2005-06-09 Time 11:44 Rev Time 0.00
Received By shill Date 2005-06-09 Time 11:44 Sent To B
Notes
2005-06-09 00:00:00SUBMITTAL TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 09:00 Rev Time 0.00
Received By shill Date 2005-06-08 Time 09:00 Sent To B
Notes
2005-06-08 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-21 Cont ID  
Sent By jwitmer Date 2005-06-21 Time 07:38 Rev Time 0.00
Received By jwitmer Date 2005-05-24 Time 09:56 Sent To  
Notes
2005-06-06 00:00:00TO COMM BD#14
2005-05-24 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-06-20 Cont ID  
Sent By hmoser Date 2005-06-20 Time 14:44 Rev Time 0.00
Received By hmoser Date 2005-06-20 Time 14:44 Sent To  
Notes
2005-06-20 00:00:00PLEASE HAVE AIRCONDITIONING CONTRACTOR
 SUBMIT PLANS WITH APPLICATION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-10-18 Cont ID  
Sent By kstevens Date 2005-10-18 Time 09:03 Rev Time 0.25
Received By kstevens Date 2005-10-18 Time 09:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-10 Cont ID  
Sent By kstevens Date 2005-09-10 Time 21:08 Rev Time 0.60
Received By kstevens Date 2005-09-10 Time 21:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-20 Cont ID  
Sent By pschmitz Date 2005-06-20 Time 14:28 Rev Time 0.00
Received By pschmitz Date 2005-06-20 Time 14:27 Sent To M
Notes
***NONE***