| 2005-08-15 00:00:00 | ******* UNSAT 3RD REVIEW ************ |
| | |
| | PLEASE SEE ALL NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | PLEASE SEENO COMMENTS SEEMED TO HAVE |
| | BEEN ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL SCHEDULES |
| | SUBMITTED. |
| | PLEASE SEE SOME CIRCUITING STILL MISSING |
| | ON PLANS. |
| | PLEASE SEE PLANS HAVE BEEN REDLINED FOR |
| | THESE ONPREVIOUS PLANS. |
| | |
| | 2)NOTE: PLEASE SEE MISSING RECEPTS |
| | REQUIRED PER 210.52. |
| | PLEASE SEE FBC 104.2.1, TECHNICAL CODES |
| | MAY NOT BE REFERENCED IN WHOLE OR IN |
| | PART. |
| | PLEASE SEE LOCATIONS REDLINED ON PLANS |
| | AT MISSING LOCATIONS. |
| | |
| | 3)NOTE: PLEASE SEE CIRCUITING OF SD'S. |
| | PLEASE ALSO SEE NOTES IN REF TO ARC |
| | FAULT PROTECTION. PLEASE SEE NOTES |
| | MENTIONS ARC FAULT FOR RECEPTS ONLY. |
| | PLEASE SEE NFPA-72 8-1.4.2.1 FOR |
| | PLACEMENT OF SD'S. PLEASE SEE KITCHEN |
| | SD: AND ACCORD TO NFPA 8-1.4.2, PLEASE |
| | SEE SD'S WITH/IN 3' OF BATH DRS, 20 ' OF |
| | COOKING APPLIANCE. |
| | PLEASE SEE THESE ITEMS WERE REDLINED ON |
| | PREVIOUS PLANS. |
| | |
| | 4)NOTE: PLEASE SEE 210.12 2002 NEC, |
| | WHICH REQUIRES ALL "OUTLETS" IN BEDRMS |
| | TO BE ARC FAULT PROTECTED. PLEASE SEE |
| | "ELECTRICAL NOTES" ON PLANS MENTIONS |
| | ONLY RECEPTS. NOTED ON SD COMMENT. |
| | PLEASE ALSO VERIFY CIRCUITING, SD'S LTS, |
| | FANS ETC. SEE REDLINED PLANS. |
| | |
| | 5)NOTE: PLEASE SEE 100A OCP SHOWN FOR |
| | RANGE ON #8 AWG. PLEASE SEE 240.4,310.16 |
| | ETC FOR MAX OCP FOR 8KW RANGE. |
| | SAME COMMENT, NO CHANGE. |
| | |
| | 6)NOTE: PLEASE SEE MAX OCP (60A) FOR |
| | WATER HEATER SHALL BE 150%. PLEASE SEE |
| | 60A OCP SHOWN ON #10 AWG AND ON A 4.5KA |
| | UNIT. |
| | 240.4,310.16,422.11E |
| | SAME COMMENT, NO CHANGE. |
| | |
| | 7)NOTE: PLEASE SEE 240.4,310.16 ETC FOR |
| | MAX OCP FOR A/C UNITS ON #12. PANEL |
| | SCHEDULES SHOWS 40A OCP ON #12 AWG. |
| | PLEASE ADJUST. |
| | SAME COMMENT, NO CHANGE |
| | |
| | 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | PLEASE SEE NEW PANEL AND MAINS NOW |
| | SHOWN. |
| | NO CHANGES. |
| | |
| | 9)NOTE: PLEASE VERIFY NEW GROUNDING |
| | ELECTRODE SYSTEM FOR NEW PANELS??? |
| | PLEASE VERIFY IF GROUNDING ELECTRODE |
| | SYSTEM ALREADY EXISTS? |
| | PLEASE SEE 250.6,250.24 ETC FOR LOCATION |
| | OF GROUDING ELECTRODE SYSTEM. |
| | PREVIOUS NOTES MENTIONED TO CLARIFY |
| | EXISTING AND NOW PLANS SHOW A NEW SYSTEM |
| | ONLY TO NEW MAINS??? |
| | 250.6,250.24. |
| | ONLY "EQUIPMENT GROUNDING CONDUCOTRS" |
| | ARE REQUIRED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 10)NOTE: PLEASE SEE A GUTTER? IS NOW |
| | SHOWN FROM DISCONNECT TO SUB PANEL IN |
| | UNIT UPSTAIRS? |
| | PLEASE VERIFY IF GUTTER WILL INDEED BE |
| | INSTALLED. IF SO, PLEASE INCLUDE SIZE OF |
| | GUTTER ON RISER DIAGRAM. |
| | 215.5,366 |
| | |
| | 11)NOTE: PLEASE SEE GARBAGE DISPOSAL IS |
| | SHOWN ON SMALL APPLIANCE CIRCUIT. THIS |
| | IS NOT PERMITTED. 210.52B1 |
| | |
| | 12)NOTE: PLEASE SEE NOTES WHICH WERE |
| | REDLINED ON PREVIOUS PLANS: "NOTES TO |
| | ELECTRICAL PLANS", REFERENCE WRONG NEC |
| | CODES FOR REQUIREMENTS. |
| | NOTE MENTIONS, ARC FAULT FOR RECEPTS, |
| | PREVIOUS NOTES: |
| | NOTE MENTIONS SPACING IN KITCHEN COUNTER |
| | PER 210.8, THIS IS PER 210.52C1, 210.8A6 |
| | IS FOR GFI PROTECTION OF KITCHEN |
| | COUNTERSPACE RECEPTS. |
| | NOTE MENTIONS, LIGHTING OUTLETS PER |
| | 210.72? THIS SHOUDL BE 210.70. |
| | THESE WERE CIRCILED AND REDLINE DON |
| | PREVIOUS PLANS. |
| | |
| | |
| | 13)NOTE: PLEASE SEE ATTACHED COPY OF |
| | FS 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONAL AND PLANS BEING REVIEWED |
| | WITH THE SAME COMMENTS. THIS WAS GIVEN |
| | AS ONLY A NOTICE ON PREVIOUS REVIEW, |
| | HOWEVER DUE TO PLANS WITH REPEATED |
| | COMMENTS, A 4X FEE HAS NOW BEEN ASSESSED |
| | IN THE AMOUNT OF $480.00 TO THE DESIGN |
| | PROFESSIONAL. |
| | PLEASE SEE ONE SET OF EACH SUBMITTED |
| | ELECTRICAL/BLDG PLANS HAVE NOW BEEN |
| | RETAINED FOR FILE AND POSSIBLE REVIEW BY |
| | THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEER'S FOR CODE COMPLIANCE AND SAID |
| | REPEAT COMMENTS. |
| | PLEASE SEE THIS FEE IS THE |
| | RESPONSIBILITY OF THE DESIGN |
| | PROFESSIONAL AND NOT OF THE OWNER OR |
| | CONTRACTOR. THIS FEE WHICH IS REQUIRED |
| | UNDER FS MUST BE PAID BEFORE PLANS MAY |
| | BE RE-SUBMITTED. |
| | IF PLANS COME BACK IN AGAIN WITH ANY OF |
| | THE SAME COMMENTS AS PREVIOUS REVIEWED, |
| | A4X FEE SHALL BE ASSCESSED. |
| | IT IS SUGGESTED, IF THERE ARE ANY |
| | QUESTIONS, A MEETING BE SET UP WITH THE |
| | DESIGNER, ENGINEER, CONTRACTOR AND CITY |
| | OF WEST PALM BEACH PLAN REVIEW STAFF. |
| | |
| | PLEASE CALL TO SET UP ANY MEETINGS WITH |
| | PLANS REVIEWER(S) WITH |
| | MR. JIM WITMER(INTERIM CHEIF PLANS |
| | EXAMINER). |
| | 561-805-6715 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF OLD SHEETS SHALL BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |