| Plan Review Stops For Permit 05051450 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2006-08-21 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-08-21 |
Time |
13:21 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2006-08-21 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2006-08-21 00:00:00 | FLOOR PLAN REVISION OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2006-05-04 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-05-04 |
Time |
11:23 |
Rev Time |
0.66 |
| Received By |
alange |
Date |
2006-05-04 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2006-05-04 00:00:00 | BEAM REVISION OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-02-03 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-02-03 |
Time |
14:29 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2006-02-03 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2006-02-03 00:00:00 | MIRROR IMAGE PLANS OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-10-07 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-10-07 |
Time |
13:41 |
Rev Time |
2.50 |
| Received By |
alange |
Date |
2005-10-07 |
Time |
11:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-09-06 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-09-06 |
Time |
13:29 |
Rev Time |
2.00 |
| Received By |
alange |
Date |
2005-09-06 |
Time |
11:37 |
Sent To |
ENG |
|
| Notes |
| 2005-09-06 00:00:00 | DENIED | | | SECOND REVIEW: | | | | | | 4.SHOW GUARDRAIL DETAIL COMPLYING WITH | | | FBC 1015.3SHOW DETAIL ON PLANS AND | | | HAVE PAGES SIGNED AND SEALED BY THE | | | ARCHITECT OF RECORD. | | | | | | 5. | | | **ALL PRODUCT APPROVALS SUBMITTED SHALL | | | HAVE THE FOLLOWING ATTACHED.** | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 6.SMOKE DETECTORS ARE REQUIRED AT | | | STAIRWELL LOCATIONS ON BOTH FLOORS | | | FBC905.2.2 | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-06-20 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-06-20 |
Time |
14:41 |
Rev Time |
4.00 |
| Received By |
alange |
Date |
2005-06-17 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2005-06-20 00:00:00 | DENIED | | | | | | 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 2.PLEASE SIGN OWNER/AGENT ON ENERGY | | | CALCS. | | | | | | 3.SUBMIT SPECS FOR FIREPLACE. | | | | | | 4.SHOW GUARDRAIL DETAIL COMPLYING WITH | | | FBC 1015.3 | | | | | | 5.SUBMIT 2 COPIES OF PRODUCT APPROVALS | | | FOR ROOFING, STRAPS AND LINTELS. | | | | | | **ALL PRODUCT APPROVALS SUBMITTED SHALL | | | HAVE THE FOLLOWING ATTACHED.** | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 6.SMOKE DETECTORS ARE REQUIRED AT | | | STAIRWELL LOCATIONS ON BOTH FLOORS | | | FBC905.2.2 | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2007-01-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-21 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-21 |
Time |
12:00 |
Sent To |
PC |
|
| Notes |
| 2007-01-21 12:04:09 | REVISONS FOR FINAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2007-01-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-13 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-13 |
Time |
13:34 |
Sent To |
PC |
|
| Notes |
| 2007-01-13 14:05:28 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE CIRCUITS AND OVER CURRENT | | | PROTECTION IS NOW SHOWN FOR ITEMS ON PANEL SCHEDULES, | | | PLEASE SEE THE CIRCUITS FOR THE WHIRLPOOL TUB AND | | | WHIRLPOOL HEAT ARE BOTH SHOWN AT 15A CIRCUITS AND #14 | | | WIRE, HOWEVER THE LOAD ON EACH OF THESE AS STATED ON | | | THE LOAD CALCULATIONS IS 2000 WATTS FOR EACH WHICH | | | EXCEEDS THE RATINGS OF THESE CIRCUITS. PLEASE CORRELATE | | | LOADS, CIRCUIT, AND BREAKER ETC. | | | 240.4, 310.16, 408.4, 220.14 ETC. | | | | | | 2) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW; PLEASE | | | SEE 210.52B1, 210.11C1 AND 220.16 FOR CIRCUITING OF | | | DINING ROOM. IF ON ONE OR MORE OF THE SMALL APPLIANCE | | | CIRCUITS THEN PLEASE ADJUST AS BEING SHOWN ON THEIR OWN | | | CIRCUIT. | | | PREVIOUS REVIEW NOTE. | | | | | | 3) NOTE: PLEASE SEE GFI DESIGNATION FOR EACH OF THE | | | CIRCUITS FEEDING THE JACUZZI/WHIRLPOOL TUB.680.71./ | | | PLEASE LIST EITHER ON PANEL SCHEDULE IF THE PROTECTION | | | IS THE BREAKER OR LIST ON THE PLANS IF AT THE TUB. | | | PREVIOUS REVIEW NOTE. | | | | | | 4) NOTE: PLEASE VERIFY LOAD CALCULATIONS AS SHOWN AS | | | THE LOAD SHOWN AFTER DE-RATING AS SHOWN PLACES LOAD AT | | | 198+ AMPS. PLEASE SEE NEC 220.31 AND 90.8 FOR ALLOWANCE | | | AND SIZING SERVICE FOR FUTURE EQUIPMENT. THIS IS | | | EXPLAINED IN THE HANDBOOK IN COMMENTARY. | | | PLEASE SEE SERVICE TOTAL WATTAGE IS BEING DIVIDED BY | | | 230V?S, PLEASE VERIFY THE VOLTAGE AND USE THE ACTUAL | | | VOLTAGE PRESENT. IS THIS VOLTAGE NOT 240V? | | | PLEASE SEE NOTES ABOVE AS THE LOADS ON THE WHIRLPOOL | | | HEATER AND PUMP NEED TO BE VERIFIED ALONG WITH THE | | | ADDITIONAL LOAD FOR DINING ROOM CIRCUIT. | | | PLEASE VERIFY PUMP, POOL EQUIPMENT LOADS ETC AND | | | CORRELATE. | | | FBC ADMIN SECTION 106.3.5.4 (8). | | | | | | | | | ** IF THERE ARE NAY QUESTIONS, PLEASE DO NOT HESITATE | | | IN CONTACTING THIS OFFICE TO GO OVER COMMENTS OR | | | QUESTIONS. THIS MAY HELP TO CLEAR UP ANY ITEMS IN | | | QUESTION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | DPALMER @WPB.ORG |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2007-01-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-01 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-01 |
Time |
14:13 |
Sent To |
PC |
|
| Notes |
| 2007-01-01 15:21:36 | | | | | | | ** UNSAT ** | | | | | | ** PLEASE SEE NOTES FROM PREVIOUS REVIEWS DONE IN AUG | | | AND OCT OF 06 STILL NEED TO BE ADDRESSED. | | | | | | 1) NOTE: PLEASE SUBMIT COMPLETED PANEL SCHEDULE(S). | | | PLEASE KNOW IT HAS COME TO THIS OFFICE ATTENTION THAT | | | IN FACT A METER/MAIN COMBO PANEL HAS BEEN INSTALLED | | | INSTEAD OF WHAT IS SHOWN ON RISER SUBMITTED. PLEASE | | | SUBMIT THE PANEL SCHEDULE FOR ALL BRANCH CIRCUITS BEING | | | FED FROM THIS OUTSIDE PANEL. | | | PLEASE SEE THE PANEL WHICH IS BEING SHOWN AS INSIDE | | | LISTS THE CONDENSING UNITS WHICH ARE OUTSIDE.IF THIS | | | WERE THE CASE THEN DISCONNECTS PER 440.11 WOULD BE | | | REQUIRED TO BE INSTALLED BACK OUTSIDE. | | | PLEASE KNOW THAT THE PANEL SCHEDULES SHALL BE COMPLETE | | | AND DETAILED FOR EACH CIRCUIT. | | | PLEASE SEE PREVIOUS COMMENTS STATED THAT ALL ROOMS AND | | | AREAS IN WHICH EACH BRANCH CIRCUIT FEEDS SHALL BE | | | SPECIFIC. IE: BEDRM#3 LTS, LIVING RM RECEPTS, LIBRARY | | | RECEPTS/LTS ETC ETC. | | | 310.16, 240.4, 408.4. | | | PLEASE SUBMIT THE PANEL SCHEDULE AND THE EQUIPMENT | | | BEING FED FROM ANY OUTSIDE PANEL. | | | FBC 104.2.1.2 | | | PLEASE KNOW THERE ARE MANY ITEMS FOR COMPLETE CODE | | | COMPLIANCE CAN NOT BE DONE AS THE PANEL SCHEDULE IS NOT | | | YET COMPLETE WITH THE INFORMATION AS PREVIOUSLY | | | REQUESTED. | | | PLEASE ALSO KNOW THIS WAS A TOPIC WHICH WAS BROUGHT UP | | | BY THE CODE MAKING PANELIST AT THE LAST IAEI STATE | | | SECTION MEETING IN MAY OF 06 WHICH REINFORCEDTHAT OF | | | STATED ABOVE AND WHAT IS ALREADY IN THE CODE. | | | ALL PUBLIC AND OFFICIAL RECORD DOCUMENTS SHALL ALSO BE | | | SPECIFIC TO DESIGN, TECHNICAL SPECIFICATIONS AND | | | CODES. | | | | | | 2) NOTE: PLEASE SEE AS NOTED ABOVE IN NOTE #1, PLEASE | | | SEE 210.52B1, 210.11C1 AND 220.16 FOR CIRCUITING OF | | | DINING ROOM. IF ON ONE OR MORE OF THE SMALL APPLIANCE | | | CIRCUITS AND HOW LOADS ARE REQUIRED TO BE SHOWN. | | | | | | 3) NOTE: PLEASE SEE GFI DESIGNATION FOR EACH OF THE | | | CIRCUITS FEEDING THE JACUZZI/WHIRLPOOL TUB.680.71./ | | | PLEASE LIST EITHER ON PANEL SCHEDULE IF THE PROTECTION | | | IS THE BREAKER OR LIST ON THE PLANS IF AT THE TUB. | | | | | | 4) NOTE: PLEASE KNOW, IF INDEED A METER/MAIN PANEL IS | | | INSTALLED OUTSIDE THEN PLEASE SEE 250.6, 250.24B, | | | 250.110 AND 250.122 FOR THE MISSING EQUIPMENT GROUNDING | | | CONDUCTOR FROM THE MAIN TO THE SUB PANEL. | | | PLEASE ADJUST RISER FOR ALL OF THE ABOVE. | | | | | | 5) NOTE: PLEASE VERIFY LOAD CALCULATIONS AS SHOWN AS | | | THE LOAD SHOWN AFTER DE-RATING AS SHOWN PLACES LOAD AT | | | 198+ AMPS. PLEASE SEE NEC 220.31 AND 90.8 FOR ALLOWANCE | | | AND SIZING SERVICE FOR FUTURE EQUIPMENT. THIS IS | | | EXPLAINED IN THE HANDBOOK IN COMMENTARY. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-12 |
Time |
17:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-12 |
Time |
17:42 |
Sent To |
P |
|
| Notes |
| 2006-10-12 17:49:01 | *** UNSAT **** | | | | | | | | | 1) NOTE: PLEASE SEE NOTE'S FROM PREVIOUSREVIEW, | | | PLEASE SEE PLANS WERE NOT REVISED PER NOTES PLEASE SEE | | | PLANS MUST CONTAIN THE PRINTED NAME AND SIGNATURE OF | | | THE ORIGINAL DESIGNER OF RECORD. | | | PLEASE SEE ELECTRICAL NOTES FROM PREVIOUS REVIEW ARE | | | BEING ATTACHED. | | | | | | PLEASE SUBMIT TWO COMPLETE SETS. | | | PLEASE DO NOT SUBMIT OLD/VOIDED SHEETS IN SETS WITH | | | NEW SHEETS AND SETS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2006-08-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-10 |
Time |
19:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-10 |
Time |
18:29 |
Sent To |
M |
|
| Notes |
| 2006-08-10 00:00:00 | **** UNSAT *** | | | | | | 1) NOTE:PLEASE SEE MIN CLEARENCES PER | | | 110.26 FOR A/C CU'S . | | | | | | 2) NOTE: PLEASE KNOW A COMPLETE PANEL | | | SCHEDULE INDICATING ALL CIRCUITS | | | SPECIFIC TO ALL AREAS AND ROOMS WILL BE | | | REQUIRED TO BE SUBMITTED AND REVIEWED | | | FOR FINAL. | | | ** IF THIS IS FOR ROUGH, THIS IS OK, | | | | | | 3) NOTE: PLEASE SEE PLANS SHALL CONTAIN | | | THE PRINTED NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR PLANS AND DESIGN. | | | DRAWN BY: ,,,,,,ETC | | | ** PLEASE SEE ONE SET OF ELECTRICAL | | | PLANS WERE STAMPED IN ERROR AND NOW BEEN | | | VOIDED. PLEASE PROVIDE A CLEAN PRINTED | | | SET FOR STAMPING. | | | | | | 4) NOTE: PLEASE SEE SWITCHES IN MASTER | | | BATHRM ARE SHOWN IN THE MIDDLE OF THE | | | ROOM/HALL. | | | PLEASE SEE MISPRINT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2005-10-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-10-04 |
Time |
10:00 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2005-10-04 |
Time |
09:16 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-08-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-31 |
Time |
19:05 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2005-08-31 |
Time |
18:54 |
Sent To |
P |
|
| Notes |
| 2005-08-31 00:00:00 | ******** UNSAT 2ND REVIEW ********* | | | | | | PLEASE SEE SOME NOTES FROM PREVIOUS | | | REVIEW STILL NEED TO BE ADDRESSED. | | | PLEASE ALSO SEE SOME NOTES FROM CHANGES | | | MADE TO PLANS. | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | PLEASE KNOW, THIS IS REQUIRED ON PLANS | | | FOR RATINGS OF EQUIPMENT. | | | RESPONSE LTR MENTIONS, BY OTHERS? | | | FPL LTR IN PACKAGE MENTIONS AVAILABLE | | | FAULT CURRENT AT 29,000 + AFC. | | | THIS IS REQUIRED ON PLANS AT THIS TIME. | | | PREVIOUS NOTES; | | | | | | 2)NOTE: PLEASE SEE LOCATION OF PANEL | | | WHICH WAS IN LAUNDRY RM HAS NOW BEEN | | | MOVED INTO STORAGE ROOM. PLEASE SEE THE | | | ELECTRICAL PANEL CONTAINING OVERCURRENT | | | DEVICES SHALL NOT BE INSTALLED IN | | | STORAGE/ CLOSET AREAS WITH COMBUSTIBLES. | | | 110.26,408.7,240.24 ETC. | | | | | | 3)NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210.8A-6 | | | THIS WAS ON PREVIOUS NOTES. | | | | | | 4)NOTE: PLEASE CORRELATE LOAD | | | CALCULATIONS AND PANEL SCHEDULE | | | SUBMITTED FOR AHU'S AND # OF CIRCUITS. | | | PLEASE SEE ONLY ONE AHU IS INDICATED ON | | | PANEL SCHEDULE. | | | PLEASE SEE THE NUMBER OF POLES ON PANEL | | | SCHEDULE FOR CIRCUITS, SEEMS TO EXCEED | | | THE MAXIMUM OF 42 POLES. | | | 408.15 | | | PLEASE ADJUST. | | | PREVIOUS NOTE; | | | | | | 5)NOTE: PLEASE SEE DISPOSAL IS SHOWN | | | WITH A 2KW LOAD. PLEASE SEE A MAX OF 80% | | | LOAD SHALL BE FIGURED FOR A 1-POLE 20A | | | CIRCUIT. (1920VA). | | | PLEASE VERIFY KW RATING FOR DISPOSAL.?? | | | | | | 6)NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | *** PLEASE KNOW, THESE PLANS OR PREVIOUS | | | PLANS DO NOT CONTAIN AN DEVICE OR | | | FIXTURE LEGEND FOR ELECTRICAL PLANS. | | | PLEASE SUBMIT. | | | | | | 7)NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ON EACH LEVEL OF A MULTI-LEVEL DWELLING | | | UNIT. | | | IN CLOSE PROXIMITY OF STAIRWAYS LEADING | | | TO FLOORS ABOVE AND IN THE VICINITY OF | | | BEDROOMS. | | | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE | | | A MIN OF 3' FROM BATHROOM DOORS AND | | | KITCHENS. | | | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 | | | NFPA-72 8-1.4.1.6.2 | | | PREVIOUS NOTES. | | | | | | 8)NOTE: PLEASE SEE FBC 104.2.1, CITY OF | | | WEST PALM BEACH ADMINISTRATIVE | | | AMENDMENTS, WHICH REQUIRES THE PRINTED | | | NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR PLANS AND DESIGN. | | | | | | 9)NOTE: PLEASE PLACE ROOM/AREA | | | DESIGNATIONS ON ELECTRICAL PLANS. | | | PLEASE CLARIFY "GALLERY" AS NOTED ON | | | ARCH SHEETS. THIS AREA SEEMS TO BE A | | | "HALLWAY" ? PLEASE SEE 210.52H FOR | | | RECEPT SPACING. | | | | | | 10)NOTE: PLEASE SEE HWH SEEMS TO | | | INDICATE A 220V RECEPT FOR "PLUGGING-IN" | | | OF WATER HEATER? | | | PLEASE INDICATE A DISCONNECT AS | | | REQUIRED.422.31B ETC. | | | WATER HEATERS ARE NOTE "LISTED" FOR CORD | | | AND PLUG CONNECTIONS. | | | | | | 11)NOTE: PLEASE INDICATE THE REQUIRED | | | CONNECTIONS FOR GROUNDING ELECTRODE PER | | | 250.50. | | | FOOTER STEEL AND COLD WATER PIPE(IF | | | METAL). | | | | | | 12)NOTE; PLEASE SEE RECEPT IN LAUNDRY RM | | | UPSTAIRS SHALL BE INDICATED AS GFI. | | | 210.8A | | | | | | 13)NOTE: PLEASE SEE TWO A/C SYSTEMS ARE | | | SHOWN ON PANEL SCHEDULE AND LOADS, | | | HOWEVER ONLY ONE COND UNIT COULD BE | | | LOCATED ON PLANS? | | | PLEASE SHOE AND PLEASE INDICATE DISC PER | | | 440.1, AND WP GFI PER 210.63. | | | | | | 14)NOTE: PLEASE SEE COPY OF FS | | | 553.80(2)(B) WITH RESPECT TO DESIGN | | | PROFESSIONALS AND PLANS WITH REPEAT CODE | | | COMPLIANCE COMMENTS. THIS IS ONLY A | | | NOTICE GIVEN AT THIS TIME. | | | | | | PLEASE BE SURE ANY VOIDED SHEETS ARE | | | REMOVED FROM SETS AND INSERT NEW SHEETS. | | | THIS WAS DONE FROM PREVIOUS SUBMITTED | | | AND ONLY A NOTICE FOR SHEETS TO BE | | | CHANGED OUT. | | | | | | PLEASE SEE ANY POSSIBEL COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-06-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-06-09 |
Time |
13:30 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-06-09 |
Time |
11:36 |
Sent To |
M |
|
| Notes |
| 2005-06-09 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} INDICATE THE LOCATION OF THE SERVICE | | | EQUIPMENT PER 215.5. | | | | | | 2} INDICATE THE A.I.C. RATING OF THE | | | SERVICE EQUIPMENT PER 110.9 & 10. | | | | | | 3} THE KITCHEN COUNTERTOP RECEPTACLES | | | MUST COMPLY WITH 210.52(C), SPACING , | | | AND 210.8 (A)(6), GFI. | | | | | | 4} RECEPTACLES IN THE GALLERY MUST | | | COMPLY WITH 210.52(A), SPACING. | | | | | | 5} PLEASE SEE THE HEAT STRIPS INDICATED | | | IN THE CALCULATIONS @ 20,000, DO NOT | | | CORRELATE WITH THE PANEL SCHEDULE. | | | | | | 6} PLEASE LIST THE REQUIRED BATH | | | CIRCUITS ON THE PANEL SCHEDULE PER | | | 210.11(C)(3). | | | | | | 7} PLEASE LIST THE REQUIRED ARC FAULT | | | CIRCUITS ON THE PANEL SCHEDULE PER | | | 210.12. | | | | | | 8} A SMOKE DETECTOR IS REQUIRED AT THE | | | STAIRWELL ON BOTH LEVELS PER 905.2.2 | | | FBC. | | | | | | 7} MASTER AND BEDROOM #2 NEED ADDED | | | RECEPTACLES TO COMPLY WITH 210.52(A)(1) | | | & (2). SEE REVIEWED SET FOR APPROXIMATE | | | AREAS AND LOCATIONS. | | | | | | PLEASE REMOVE REVIEWED SET AND REPLACE | | | WITH CORRECTED SHEETS. ALSO PLEASE | | | FURNISH THE REVIEWED SET FOR REFERENCE, | | | AND RESUBMIT FOR REVIEW. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2006-02-03 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2006-02-03 |
Time |
08:39 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2006-02-03 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2006-02-03 00:00:00 | PASSED WITH PROVISOS: | | | | | | 1. MUST GRANT THE 9-FT EASEMENT AS | | | REQUESTED BY THE DEPARTMENT OF | | | ENGINEERING SERVICE, SEE LETTER BY LAURA | | | LE,P.E. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2005-10-13 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-10-13 |
Time |
16:07 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2005-10-13 |
Time |
16:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2005-09-06 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-09-06 |
Time |
15:08 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2005-09-06 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2005-09-06 00:00:00 | FAILED: | | | | | | 1. THE ISSUE REGARDING THE EXISTING 8" | | | VCP, CITY SEWER LINE AND THE UTILITIY | | | EASEMENT AT EAST SIDE OF THE PROPERTY | | | MUST BE RESOLVED WITH THE PUBLIC | | | UTILITIES AND ENGINEERING PRIOR TO | | | OBTAINING A CONSTUCTION PERMIT. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-05-20 |
|
|
Cont ID |
|
| Sent By |
ptjomsto |
Date |
2005-05-20 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
ptjomsto |
Date |
2005-05-20 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2005-05-20 00:00:00 | HISTORIC APPROVED 4/6/05 BY F MITTNER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2007-01-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-20 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-20 |
Time |
13:14 |
Sent To |
E |
|
| Notes |
| 2007-01-20 13:14:44 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2007-01-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-12 |
Time |
13:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-12 |
Time |
13:13 |
Sent To |
E |
|
| Notes |
| 2007-01-12 13:14:26 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2006-12-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-28 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-28 |
Time |
16:08 |
Sent To |
E |
|
| Notes |
| 2006-12-28 16:09:20 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2006-12-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-08 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-08 |
Time |
08:59 |
Sent To |
Z |
|
| Notes |
| 2006-12-08 09:00:10 | TO "Z" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-02 |
Time |
12:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-02 |
Time |
12:43 |
Sent To |
E |
|
| Notes |
| 2006-10-02 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-08 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-08 |
Time |
16:24 |
Sent To |
E |
|
| Notes |
| 2006-08-08 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-05-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-03 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-03 |
Time |
10:13 |
Sent To |
B |
|
| Notes |
| 2006-05-03 00:00:00 | TO "ALANGE" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-02-03 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-02-03 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-02-03 |
Time |
10:03 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-09-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-30 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-30 |
Time |
09:44 |
Sent To |
E |
|
| Notes |
| 2005-09-30 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-08-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-25 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-25 |
Time |
11:31 |
Sent To |
E |
|
| Notes |
| 2005-08-25 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-08-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-16 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-16 |
Time |
16:45 |
Sent To |
Z |
|
| Notes |
| 2005-08-16 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-06-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-09 |
Time |
07:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-09 |
Time |
07:05 |
Sent To |
E |
|
| Notes |
| 2005-06-09 00:00:00 | TO RES RACK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-06-20 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-06-20 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2005-05-24 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2005-05-24 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2006-12-05 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-12-05 |
Time |
08:37 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-12-05 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2006-12-05 08:38:21 | REVISION TO MECH. PLANS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-10-17 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-10-17 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2006-10-17 13:19:39 | REVISED ENERGY CALCULATIONS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-08-11 |
Time |
09:07 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-08-11 |
Time |
09:07 |
Sent To |
P |
|
| Notes |
| 2006-08-11 00:00:00 | *** DENIED *** | | | **FIRST FLOOR** | | | 1) NEED TO SHOW CFM'S AT THE KITCHEN | | | SUPPLY AIR GRILL. | | | | | | 2) NEED RETURN AIR DUCTS SIZED TO | | | STORAGE ROOM #115, LIBRARY #109, AND | | | LIVING ROOM #101. | | | | | | 3) RETURN AIR GRILL NEAR THE T-STAT. | | | NEEDS TO BE SIZED. | | | | | | 4) 8X13 SUPPLY AIR TRUNK LINE IS TO | | | SMALL FOR A 4 TON SYSTEM, PLEASE CORRECT | | | OR SUBMIT MANUAL D CALCULATIONS FOR | | | RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R | | | M1601.1 AND FBC 13-610.1.ABC.1 . | | | | | | ** SECOND FLOOR ** | | | 5) RTURN AIR TRANSFER DUCT TO MASTER | | | BEDROOM SUITE NEEDS TO BE 18", SEE NOTE | | | #7. | | | | | | 6) THERE IS NO SUPPLY AIR DUCT TO THE | | | GRILL IN BEDROOM #2, IF NEED CORRECT THE | | | RETURN AIR TRANSFER DUCT, SEE NOTE #7. | | | | | | 7) BALANCED RETURN AIR. | | | THIS MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | (B)TRANSFER GRILLES SHALL USE 50 | | | SQUARE INCHES (OF GRILLE AREA) TO 100 | | | CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH-THE-WALL TRANSFER GRILLES AND | | | USING AN UNRESTRICTED 1-INCH | | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER | | | RETURN AIR BALANCE | | | (C)HABITABLE ROOMS ONLY SHALL BE | | | REQUIRED TO MEET THESE REQUIREMENTS FOR | | | PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND | | | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | | AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED. PER 2001 FBC/M 601.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-09-06 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-09-06 |
Time |
10:09 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2005-09-06 |
Time |
10:09 |
Sent To |
B |
|
| Notes |
| 2005-09-06 00:00:00 | *** PROVISO *** | | | 1) MASTER BEDROOM RETURN AIR DUCT TO | | | A.H.U. NEEDS TO BE 12" . | | | 2) 2ND. FLOOR HALL RETURN AIR DUCT TO | | | A.H.U. NEEDS TO BE 14" . | | | 3) MASTER BATHROOM NEEDS AN EXHAUST FAN, | | | IF THERE IS NO WINDOW OPENING OF 3 FT. | | | PER. FBC/M 402.3.1. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6712. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-06-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-06-16 |
Time |
08:04 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2005-06-16 |
Time |
07:50 |
Sent To |
P |
|
| Notes |
| 2005-06-16 00:00:00 | DENIED: | | | 1.RETURN AIR JUMPERS ARE NOT SIZED | | | PROPERLY.PER 2001 FBC(M)601.4 | | | EXCEPTION #1 & 3, RETURN AIR JUMPERS | | | SHALL BE A MINIMUM OF 1 1/2 TIMES | | | (SQUARE INCHES) LARGER THAN THE SUPPLY | | | AIR TO THAT AREA.ALL AIR INTO THE | | | MASTER SUITE IS TO BE INCLUDED: | | | LIBRARY 7" SUPPLY = 9" R/A JUMPER | | | GUEST RM 8" SUPPLY = 10" R/A JUMPER | | | BEDRM 2 & 3 8" SUPPLY = 10" R/A JUMPER | | | MASTER SUITE 10" & 8" SUPPLY=16" R/A | | | | | | 2.TWO COPIES OF ALL SPECIFICATIONS | | | REQUIRED PER 2001 FBC 104.2.1.TWO SETS | | | OF PLANS WERE SUBMITTED BUT NOT THE | | | PRODUCT APPROVALS OR ENERGY | | | CALCULATIONS. | | | | | | 3.PROVIDE MANUAL J CALCULATIONS IN | | | ACCORDANCE WITH 2001 FBC CHATPER 6. | | | | | | 4.PROVIDE VENTING LAYOUT & MATERIAL | | | FOR THE DRYER EXHAUST VENT. | | | | | | 5.CONDENSATE SHALL TERMINATE A MINIMUM | | | OF 12" FROM THE BUILDING STRUCTURE PER | | | 2001 FBC 1503.4.4. | | | | | | 6.PROVIDE AUXILIARY DRAIN PAN WITH | | | OVER FLOW PROTECTION.INDICATE WHICH | | | METHOD OF OVERFLOW PROTECTION WILL BE | | | USED.2001 FBC(M)307.2.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2006-12-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-12-01 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-12-01 |
Time |
13:37 |
Sent To |
M |
|
| Notes |
| 2006-12-01 13:40:32 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | ****FROM THE PREVIOUS REVIEW: | | | | | | 1. OK | | | | | | 2. SHT 18 OF 18 INDICATE ALL PIPE SIZES | | | ON THE RISER DIAGRAM. TABLES 710.1(1) & | | | 710.1(2). | | | ****NO RESPONSE. COMMENT NOT ADDRESSED | | | | | | 3. OK | | | | | | *****NEW COMMENT**** | | | PLUMBING RISER WOULD HAVE BEEN APPROVED, BUT IT IS ON | | | THE SAME SHEET AS THE ELECTRICAL REVISION SO COMMENT | | | NUMBER 2 CAN BE ADDRESSED WITH THE ELECTRICAL | | | COMMENTS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2006-08-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-08-19 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-08-19 |
Time |
08:26 |
Sent To |
B |
|
| Notes |
| 2006-08-19 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | 1. SHT 18 0F 18 SANT. RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN. PLEASE MAKE | | | CHANGES TO RISER DIAGRAM THAT ARE SHOWN | | | ON THE FLOOR PLAN. SECTION 106.3.5.1.3. | | | | | | 2. SHT 18 OF 18 INDICATE ALL PIPE SIZES | | | ON THE RISER DIAGRAM. TABLES 710.1(1) & | | | 710.1(2). | | | | | | 3. ALL SHEETS SHALL BEAR THE NAME AND | | | SIGNATURE OF THE PERSON DESIGNING THE | | | PLANS. 106.1.2. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2005-10-04 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-10-04 |
Time |
14:49 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2005-10-04 |
Time |
14:49 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2005-09-01 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-09-01 |
Time |
07:55 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-09-01 |
Time |
07:55 |
Sent To |
M |
|
| Notes |
| 2005-09-01 00:00:00 | DENIED; | | | SEE ELECTRICAL PLAN REVIEW NOTE # 8. | | | PRINTED NAME AND SIGNITURE REQUIRED ON | | | DRAWINGS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-06-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-16 |
Time |
13:31 |
Rev Time |
0.55 |
| Received By |
kstevens |
Date |
2005-06-16 |
Time |
13:31 |
Sent To |
B1 |
|
| Notes |
| 2005-06-16 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1. SHT 18 OF 18 SANT. RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. CORRECT THE | | | FOLLOWING: | | | A. TUB NOT VENTED 2ND FLOOR GUEST ROOM | | | BATHROOM. | | | B. KITCHEN SINK SHALL NOT DRAIN THRU | | | THE HORIZONTAL WET VENT FOR THE POWDER | | | ROOM FIXTURES. SECTION 909.1. - KITCHEN | | | SINKS SHALL DISCHARGE DOWNSTREAM OF THE | | | POWDER ROOM FIXTURES. | | | C. KITCHEN SINK IN THE ISLAND. INDICATE | | | HOW THIS CAN BE VENTED THRU THE ROOF | | | WITH NO WALL NEXT TO THE SINK. SUGGEST | | | USE OF AN AIR ADMITTENCE VALVE, OR AN | | | ISLAND VENT. SECTIONS 913, OR 917. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2006-12-16 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-12-16 |
Time |
06:40 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-12-16 |
Time |
06:40 |
Sent To |
|
|
| Notes |
| 2006-12-16 06:41:16 | REVISION: DECORATIVE PAVERS UNSEALED WITHIN THE FRONT | | | SETBACK FOR DRIVEWAY AND WALKWAY.OK PER KELLY | | | FREEMAN, PLANNER 822-1435 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2006-02-03 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-02-03 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-02-03 |
Time |
13:45 |
Sent To |
B |
|
| Notes |
| 2006-02-03 00:00:00 | NOTE: MUST PULL A SEPERATE PERMIT FOR | | | FENCE/WALL/GATE/COLUMNS WITH EASEMENT | | | APPROVAL FROM THE CITY OF WEST PALM | | | BEACH. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-08-24 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-08-24 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-08-24 |
Time |
16:37 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-06-08 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-06-08 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-06-08 |
Time |
16:59 |
Sent To |
I |
|
| Notes |
| 2005-06-08 00:00:00 | DENIED, | | | 1. DRIVEWAY EXCEEDS THE ZONING | | | REQUIREMENTS. | | | 2. MUST REDUCE THE WIDTH OF DRIVEWAY. | | | 3. ROOF OVERHANG CAN ONLY HANG 3FT INTO | | | ANY SETBACK.(NO ROOF PLANS PROVIDED.) | | | | | | **MUST HAVE 1000SQ FT OR 75% OF | | | LANDSCAPE WITHIN THE FIRST 25FT FRONT | | | SETBACK** | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|