Plan Review Details - Permit 05051450
Plan Review Stops For Permit 05051450
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-08-21 Cont ID  
Sent By alange Date 2006-08-21 Time 13:21 Rev Time 1.00
Received By alange Date 2006-08-21 Time 12:36 Sent To  
Notes
2006-08-21 00:00:00FLOOR PLAN REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-05-04 Cont ID  
Sent By alange Date 2006-05-04 Time 11:23 Rev Time 0.66
Received By alange Date 2006-05-04 Time 11:23 Sent To  
Notes
2006-05-04 00:00:00BEAM REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-02-03 Cont ID  
Sent By alange Date 2006-02-03 Time 14:29 Rev Time 1.00
Received By alange Date 2006-02-03 Time 14:20 Sent To  
Notes
2006-02-03 00:00:00MIRROR IMAGE PLANS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-10-07 Cont ID  
Sent By alange Date 2005-10-07 Time 13:41 Rev Time 2.50
Received By alange Date 2005-10-07 Time 11:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-06 Cont ID  
Sent By alange Date 2005-09-06 Time 13:29 Rev Time 2.00
Received By alange Date 2005-09-06 Time 11:37 Sent To ENG
Notes
2005-09-06 00:00:00DENIED
 SECOND REVIEW:
  
 4.SHOW GUARDRAIL DETAIL COMPLYING WITH
 FBC 1015.3SHOW DETAIL ON PLANS AND
 HAVE PAGES SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD.
  
 5.
 **ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING ATTACHED.**
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.SMOKE DETECTORS ARE REQUIRED AT
 STAIRWELL LOCATIONS ON BOTH FLOORS
 FBC905.2.2
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-20 Cont ID  
Sent By alange Date 2005-06-20 Time 14:41 Rev Time 4.00
Received By alange Date 2005-06-17 Time 16:45 Sent To  
Notes
2005-06-20 00:00:00DENIED
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 3.SUBMIT SPECS FOR FIREPLACE.
  
 4.SHOW GUARDRAIL DETAIL COMPLYING WITH
 FBC 1015.3
  
 5.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR ROOFING, STRAPS AND LINTELS.
  
 **ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING ATTACHED.**
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.SMOKE DETECTORS ARE REQUIRED AT
 STAIRWELL LOCATIONS ON BOTH FLOORS
 FBC905.2.2
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2007-01-21 Cont ID  
Sent By dpalmer Date 2007-01-21 Time 12:00 Rev Time 0.00
Received By dpalmer Date 2007-01-21 Time 12:00 Sent To PC
Notes
2007-01-21 12:04:09REVISONS FOR FINAL.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-01-13 Cont ID  
Sent By dpalmer Date 2007-01-13 Time 14:04 Rev Time 0.00
Received By dpalmer Date 2007-01-13 Time 13:34 Sent To PC
Notes
2007-01-13 14:05:28** UNSAT **
  
 1) NOTE: PLEASE SEE CIRCUITS AND OVER CURRENT
 PROTECTION IS NOW SHOWN FOR ITEMS ON PANEL SCHEDULES,
 PLEASE SEE THE CIRCUITS FOR THE WHIRLPOOL TUB AND
 WHIRLPOOL HEAT ARE BOTH SHOWN AT 15A CIRCUITS AND #14
 WIRE, HOWEVER THE LOAD ON EACH OF THESE AS STATED ON
 THE LOAD CALCULATIONS IS 2000 WATTS FOR EACH WHICH
 EXCEEDS THE RATINGS OF THESE CIRCUITS. PLEASE CORRELATE
 LOADS, CIRCUIT, AND BREAKER ETC.
 240.4, 310.16, 408.4, 220.14 ETC.
  
 2) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW; PLEASE
 SEE 210.52B1, 210.11C1 AND 220.16 FOR CIRCUITING OF
 DINING ROOM. IF ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS THEN PLEASE ADJUST AS BEING SHOWN ON THEIR OWN
 CIRCUIT.
 PREVIOUS REVIEW NOTE.
  
 3) NOTE: PLEASE SEE GFI DESIGNATION FOR EACH OF THE
 CIRCUITS FEEDING THE JACUZZI/WHIRLPOOL TUB.680.71./
 PLEASE LIST EITHER ON PANEL SCHEDULE IF THE PROTECTION
 IS THE BREAKER OR LIST ON THE PLANS IF AT THE TUB.
 PREVIOUS REVIEW NOTE.
  
 4) NOTE: PLEASE VERIFY LOAD CALCULATIONS AS SHOWN AS
 THE LOAD SHOWN AFTER DE-RATING AS SHOWN PLACES LOAD AT
 198+ AMPS. PLEASE SEE NEC 220.31 AND 90.8 FOR ALLOWANCE
 AND SIZING SERVICE FOR FUTURE EQUIPMENT. THIS IS
 EXPLAINED IN THE HANDBOOK IN COMMENTARY.
 PLEASE SEE SERVICE TOTAL WATTAGE IS BEING DIVIDED BY
 230V?S, PLEASE VERIFY THE VOLTAGE AND USE THE ACTUAL
 VOLTAGE PRESENT. IS THIS VOLTAGE NOT 240V?
 PLEASE SEE NOTES ABOVE AS THE LOADS ON THE WHIRLPOOL
 HEATER AND PUMP NEED TO BE VERIFIED ALONG WITH THE
 ADDITIONAL LOAD FOR DINING ROOM CIRCUIT.
 PLEASE VERIFY PUMP, POOL EQUIPMENT LOADS ETC AND
 CORRELATE.
 FBC ADMIN SECTION 106.3.5.4 (8).
  
  
 ** IF THERE ARE NAY QUESTIONS, PLEASE DO NOT HESITATE
 IN CONTACTING THIS OFFICE TO GO OVER COMMENTS OR
 QUESTIONS. THIS MAY HELP TO CLEAR UP ANY ITEMS IN
 QUESTION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 DPALMER @WPB.ORG

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-01-01 Cont ID  
Sent By dpalmer Date 2007-01-01 Time 15:19 Rev Time 0.00
Received By dpalmer Date 2007-01-01 Time 14:13 Sent To PC
Notes
2007-01-01 15:21:36 
  
 ** UNSAT **
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEWS DONE IN AUG
 AND OCT OF 06 STILL NEED TO BE ADDRESSED.
  
 1) NOTE: PLEASE SUBMIT COMPLETED PANEL SCHEDULE(S).
 PLEASE KNOW IT HAS COME TO THIS OFFICE ATTENTION THAT
 IN FACT A METER/MAIN COMBO PANEL HAS BEEN INSTALLED
 INSTEAD OF WHAT IS SHOWN ON RISER SUBMITTED. PLEASE
 SUBMIT THE PANEL SCHEDULE FOR ALL BRANCH CIRCUITS BEING
 FED FROM THIS OUTSIDE PANEL.
 PLEASE SEE THE PANEL WHICH IS BEING SHOWN AS INSIDE
 LISTS THE CONDENSING UNITS WHICH ARE OUTSIDE.IF THIS
 WERE THE CASE THEN DISCONNECTS PER 440.11 WOULD BE
 REQUIRED TO BE INSTALLED BACK OUTSIDE.
 PLEASE KNOW THAT THE PANEL SCHEDULES SHALL BE COMPLETE
 AND DETAILED FOR EACH CIRCUIT.
 PLEASE SEE PREVIOUS COMMENTS STATED THAT ALL ROOMS AND
 AREAS IN WHICH EACH BRANCH CIRCUIT FEEDS SHALL BE
 SPECIFIC. IE: BEDRM#3 LTS, LIVING RM RECEPTS, LIBRARY
 RECEPTS/LTS ETC ETC.
 310.16, 240.4, 408.4.
 PLEASE SUBMIT THE PANEL SCHEDULE AND THE EQUIPMENT
 BEING FED FROM ANY OUTSIDE PANEL.
 FBC 104.2.1.2
 PLEASE KNOW THERE ARE MANY ITEMS FOR COMPLETE CODE
 COMPLIANCE CAN NOT BE DONE AS THE PANEL SCHEDULE IS NOT
 YET COMPLETE WITH THE INFORMATION AS PREVIOUSLY
 REQUESTED.
 PLEASE ALSO KNOW THIS WAS A TOPIC WHICH WAS BROUGHT UP
 BY THE CODE MAKING PANELIST AT THE LAST IAEI STATE
 SECTION MEETING IN MAY OF 06 WHICH REINFORCEDTHAT OF
 STATED ABOVE AND WHAT IS ALREADY IN THE CODE.
 ALL PUBLIC AND OFFICIAL RECORD DOCUMENTS SHALL ALSO BE
 SPECIFIC TO DESIGN, TECHNICAL SPECIFICATIONS AND
 CODES.
  
 2) NOTE: PLEASE SEE AS NOTED ABOVE IN NOTE #1, PLEASE
 SEE 210.52B1, 210.11C1 AND 220.16 FOR CIRCUITING OF
 DINING ROOM. IF ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS AND HOW LOADS ARE REQUIRED TO BE SHOWN.
  
 3) NOTE: PLEASE SEE GFI DESIGNATION FOR EACH OF THE
 CIRCUITS FEEDING THE JACUZZI/WHIRLPOOL TUB.680.71./
 PLEASE LIST EITHER ON PANEL SCHEDULE IF THE PROTECTION
 IS THE BREAKER OR LIST ON THE PLANS IF AT THE TUB.
  
 4) NOTE: PLEASE KNOW, IF INDEED A METER/MAIN PANEL IS
 INSTALLED OUTSIDE THEN PLEASE SEE 250.6, 250.24B,
 250.110 AND 250.122 FOR THE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM THE MAIN TO THE SUB PANEL.
 PLEASE ADJUST RISER FOR ALL OF THE ABOVE.
  
 5) NOTE: PLEASE VERIFY LOAD CALCULATIONS AS SHOWN AS
 THE LOAD SHOWN AFTER DE-RATING AS SHOWN PLACES LOAD AT
 198+ AMPS. PLEASE SEE NEC 220.31 AND 90.8 FOR ALLOWANCE
 AND SIZING SERVICE FOR FUTURE EQUIPMENT. THIS IS
 EXPLAINED IN THE HANDBOOK IN COMMENTARY.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-10-12 Cont ID  
Sent By dpalmer Date 2006-10-12 Time 17:44 Rev Time 0.00
Received By dpalmer Date 2006-10-12 Time 17:42 Sent To P
Notes
2006-10-12 17:49:01*** UNSAT ****
  
  
 1) NOTE: PLEASE SEE NOTE'S FROM PREVIOUSREVIEW,
 PLEASE SEE PLANS WERE NOT REVISED PER NOTES PLEASE SEE
 PLANS MUST CONTAIN THE PRINTED NAME AND SIGNATURE OF
 THE ORIGINAL DESIGNER OF RECORD.
 PLEASE SEE ELECTRICAL NOTES FROM PREVIOUS REVIEW ARE
 BEING ATTACHED.
  
 PLEASE SUBMIT TWO COMPLETE SETS.
 PLEASE DO NOT SUBMIT OLD/VOIDED SHEETS IN SETS WITH
 NEW SHEETS AND SETS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-08-10 Cont ID  
Sent By dpalmer Date 2006-08-10 Time 19:44 Rev Time 0.00
Received By dpalmer Date 2006-08-10 Time 18:29 Sent To M
Notes
2006-08-10 00:00:00**** UNSAT ***
  
 1) NOTE:PLEASE SEE MIN CLEARENCES PER
 110.26 FOR A/C CU'S .
  
 2) NOTE: PLEASE KNOW A COMPLETE PANEL
 SCHEDULE INDICATING ALL CIRCUITS
 SPECIFIC TO ALL AREAS AND ROOMS WILL BE
 REQUIRED TO BE SUBMITTED AND REVIEWED
 FOR FINAL.
 ** IF THIS IS FOR ROUGH, THIS IS OK,
  
 3) NOTE: PLEASE SEE PLANS SHALL CONTAIN
 THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR PLANS AND DESIGN.
 DRAWN BY: ,,,,,,ETC
 ** PLEASE SEE ONE SET OF ELECTRICAL
 PLANS WERE STAMPED IN ERROR AND NOW BEEN
 VOIDED. PLEASE PROVIDE A CLEAN PRINTED
 SET FOR STAMPING.
  
 4) NOTE: PLEASE SEE SWITCHES IN MASTER
 BATHRM ARE SHOWN IN THE MIDDLE OF THE
 ROOM/HALL.
 PLEASE SEE MISPRINT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-10-04 Cont ID  
Sent By dpalmer Date 2005-10-04 Time 10:00 Rev Time 0.75
Received By dpalmer Date 2005-10-04 Time 09:16 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-31 Cont ID  
Sent By dpalmer Date 2005-08-31 Time 19:05 Rev Time 0.75
Received By dpalmer Date 2005-08-31 Time 18:54 Sent To P
Notes
2005-08-31 00:00:00******** UNSAT 2ND REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE SOME NOTES FROM CHANGES
 MADE TO PLANS.
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE KNOW, THIS IS REQUIRED ON PLANS
 FOR RATINGS OF EQUIPMENT.
 RESPONSE LTR MENTIONS, BY OTHERS?
 FPL LTR IN PACKAGE MENTIONS AVAILABLE
 FAULT CURRENT AT 29,000 + AFC.
 THIS IS REQUIRED ON PLANS AT THIS TIME.
 PREVIOUS NOTES;
  
 2)NOTE: PLEASE SEE LOCATION OF PANEL
 WHICH WAS IN LAUNDRY RM HAS NOW BEEN
 MOVED INTO STORAGE ROOM. PLEASE SEE THE
 ELECTRICAL PANEL CONTAINING OVERCURRENT
 DEVICES SHALL NOT BE INSTALLED IN
 STORAGE/ CLOSET AREAS WITH COMBUSTIBLES.
 110.26,408.7,240.24 ETC.
  
 3)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 THIS WAS ON PREVIOUS NOTES.
  
 4)NOTE: PLEASE CORRELATE LOAD
 CALCULATIONS AND PANEL SCHEDULE
 SUBMITTED FOR AHU'S AND # OF CIRCUITS.
 PLEASE SEE ONLY ONE AHU IS INDICATED ON
 PANEL SCHEDULE.
 PLEASE SEE THE NUMBER OF POLES ON PANEL
 SCHEDULE FOR CIRCUITS, SEEMS TO EXCEED
 THE MAXIMUM OF 42 POLES.
 408.15
 PLEASE ADJUST.
 PREVIOUS NOTE;
  
 5)NOTE: PLEASE SEE DISPOSAL IS SHOWN
 WITH A 2KW LOAD. PLEASE SEE A MAX OF 80%
 LOAD SHALL BE FIGURED FOR A 1-POLE 20A
 CIRCUIT. (1920VA).
 PLEASE VERIFY KW RATING FOR DISPOSAL.??
  
 6)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 *** PLEASE KNOW, THESE PLANS OR PREVIOUS
 PLANS DO NOT CONTAIN AN DEVICE OR
 FIXTURE LEGEND FOR ELECTRICAL PLANS.
 PLEASE SUBMIT.
  
 7)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 NFPA-72 8-1.4.1.6.2
 PREVIOUS NOTES.
  
 8)NOTE: PLEASE SEE FBC 104.2.1, CITY OF
 WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS, WHICH REQUIRES THE PRINTED
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS AND DESIGN.
  
 9)NOTE: PLEASE PLACE ROOM/AREA
 DESIGNATIONS ON ELECTRICAL PLANS.
 PLEASE CLARIFY "GALLERY" AS NOTED ON
 ARCH SHEETS. THIS AREA SEEMS TO BE A
 "HALLWAY" ? PLEASE SEE 210.52H FOR
 RECEPT SPACING.
  
 10)NOTE: PLEASE SEE HWH SEEMS TO
 INDICATE A 220V RECEPT FOR "PLUGGING-IN"
 OF WATER HEATER?
 PLEASE INDICATE A DISCONNECT AS
 REQUIRED.422.31B ETC.
 WATER HEATERS ARE NOTE "LISTED" FOR CORD
 AND PLUG CONNECTIONS.
  
 11)NOTE: PLEASE INDICATE THE REQUIRED
 CONNECTIONS FOR GROUNDING ELECTRODE PER
 250.50.
 FOOTER STEEL AND COLD WATER PIPE(IF
 METAL).
  
 12)NOTE; PLEASE SEE RECEPT IN LAUNDRY RM
 UPSTAIRS SHALL BE INDICATED AS GFI.
 210.8A
  
 13)NOTE: PLEASE SEE TWO A/C SYSTEMS ARE
 SHOWN ON PANEL SCHEDULE AND LOADS,
 HOWEVER ONLY ONE COND UNIT COULD BE
 LOCATED ON PLANS?
 PLEASE SHOE AND PLEASE INDICATE DISC PER
 440.1, AND WP GFI PER 210.63.
  
 14)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND PLANS WITH REPEAT CODE
 COMPLIANCE COMMENTS. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 PLEASE BE SURE ANY VOIDED SHEETS ARE
 REMOVED FROM SETS AND INSERT NEW SHEETS.
 THIS WAS DONE FROM PREVIOUS SUBMITTED
 AND ONLY A NOTICE FOR SHEETS TO BE
 CHANGED OUT.
  
 PLEASE SEE ANY POSSIBEL COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-09 Cont ID  
Sent By btrobaug Date 2005-06-09 Time 13:30 Rev Time 0.50
Received By btrobaug Date 2005-06-09 Time 11:36 Sent To M
Notes
2005-06-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE LOCATION OF THE SERVICE
 EQUIPMENT PER 215.5.
  
 2} INDICATE THE A.I.C. RATING OF THE
 SERVICE EQUIPMENT PER 110.9 & 10.
  
 3} THE KITCHEN COUNTERTOP RECEPTACLES
 MUST COMPLY WITH 210.52(C), SPACING ,
 AND 210.8 (A)(6), GFI.
  
 4} RECEPTACLES IN THE GALLERY MUST
 COMPLY WITH 210.52(A), SPACING.
  
 5} PLEASE SEE THE HEAT STRIPS INDICATED
 IN THE CALCULATIONS @ 20,000, DO NOT
 CORRELATE WITH THE PANEL SCHEDULE.
  
 6} PLEASE LIST THE REQUIRED BATH
 CIRCUITS ON THE PANEL SCHEDULE PER
 210.11(C)(3).
  
 7} PLEASE LIST THE REQUIRED ARC FAULT
 CIRCUITS ON THE PANEL SCHEDULE PER
 210.12.
  
 8} A SMOKE DETECTOR IS REQUIRED AT THE
 STAIRWELL ON BOTH LEVELS PER 905.2.2
 FBC.
  
 7} MASTER AND BEDROOM #2 NEED ADDED
 RECEPTACLES TO COMPLY WITH 210.52(A)(1)
 & (2). SEE REVIEWED SET FOR APPROXIMATE
 AREAS AND LOCATIONS.
  
 PLEASE REMOVE REVIEWED SET AND REPLACE
 WITH CORRECTED SHEETS. ALSO PLEASE
 FURNISH THE REVIEWED SET FOR REFERENCE,
 AND RESUBMIT FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2006-02-03 Cont ID  
Sent By mamini Date 2006-02-03 Time 08:39 Rev Time 0.50
Received By mamini Date 2006-02-03 Time 08:39 Sent To  
Notes
2006-02-03 00:00:00PASSED WITH PROVISOS:
  
 1. MUST GRANT THE 9-FT EASEMENT AS
 REQUESTED BY THE DEPARTMENT OF
 ENGINEERING SERVICE, SEE LETTER BY LAURA
 LE,P.E.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2005-10-13 Cont ID  
Sent By mamini Date 2005-10-13 Time 16:07 Rev Time 0.50
Received By mamini Date 2005-10-13 Time 16:07 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-09-06 Cont ID  
Sent By mamini Date 2005-09-06 Time 15:08 Rev Time 0.50
Received By mamini Date 2005-09-06 Time 15:08 Sent To  
Notes
2005-09-06 00:00:00FAILED:
  
 1. THE ISSUE REGARDING THE EXISTING 8"
 VCP, CITY SEWER LINE AND THE UTILITIY
 EASEMENT AT EAST SIDE OF THE PROPERTY
 MUST BE RESOLVED WITH THE PUBLIC
 UTILITIES AND ENGINEERING PRIOR TO
 OBTAINING A CONSTUCTION PERMIT.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2005-05-20 Cont ID  
Sent By ptjomsto Date 2005-05-20 Time 09:57 Rev Time 0.00
Received By ptjomsto Date 2005-05-20 Time 09:57 Sent To  
Notes
2005-05-20 00:00:00HISTORIC APPROVED 4/6/05 BY F MITTNER

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-01-20 Cont ID  
Sent By adarroug Date 2007-01-20 Time 13:14 Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 13:14 Sent To E
Notes
2007-01-20 13:14:44TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-01-12 Cont ID  
Sent By adarroug Date 2007-01-12 Time 13:13 Rev Time 0.00
Received By adarroug Date 2007-01-12 Time 13:13 Sent To E
Notes
2007-01-12 13:14:26TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-12-28 Cont ID  
Sent By adarroug Date 2006-12-28 Time 16:08 Rev Time 0.00
Received By adarroug Date 2006-12-28 Time 16:08 Sent To E
Notes
2006-12-28 16:09:20TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-12-08 Cont ID  
Sent By adarroug Date 2006-12-08 Time 08:59 Rev Time 0.00
Received By adarroug Date 2006-12-08 Time 08:59 Sent To Z
Notes
2006-12-08 09:00:10TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-10-02 Cont ID  
Sent By adarroug Date 2006-10-02 Time 12:43 Rev Time 0.00
Received By adarroug Date 2006-10-02 Time 12:43 Sent To E
Notes
2006-10-02 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 16:24 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 16:24 Sent To E
Notes
2006-08-08 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-05-03 Cont ID  
Sent By adarroug Date 2006-05-03 Time 10:13 Rev Time 0.00
Received By adarroug Date 2006-05-03 Time 10:13 Sent To B
Notes
2006-05-03 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-02-03 Cont ID  
Sent By alange Date 2006-02-03 Time 10:03 Rev Time 0.00
Received By alange Date 2006-02-03 Time 10:03 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-30 Cont ID  
Sent By adarroug Date 2005-09-30 Time 09:44 Rev Time 0.00
Received By adarroug Date 2005-09-30 Time 09:44 Sent To E
Notes
2005-09-30 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-25 Cont ID  
Sent By adarroug Date 2005-08-25 Time 11:31 Rev Time 0.00
Received By adarroug Date 2005-08-25 Time 11:31 Sent To E
Notes
2005-08-25 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 16:45 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 16:45 Sent To Z
Notes
2005-08-16 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-09 Cont ID  
Sent By shill Date 2005-06-09 Time 07:05 Rev Time 0.00
Received By shill Date 2005-06-09 Time 07:05 Sent To E
Notes
2005-06-09 00:00:00TO RES RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-20 Cont ID  
Sent By alange Date 2005-06-20 Time 14:41 Rev Time 0.00
Received By alange Date 2005-05-24 Time 11:42 Sent To  
Notes
2005-05-24 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-12-05 Cont ID  
Sent By tgordon Date 2006-12-05 Time 08:37 Rev Time 0.30
Received By tgordon Date 2006-12-05 Time 08:37 Sent To  
Notes
2006-12-05 08:38:21REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-10-17 Cont ID  
Sent By pkrauss Date 2006-10-17 Time 13:19 Rev Time 0.00
Received By pkrauss Date 2006-10-17 Time 13:19 Sent To  
Notes
2006-10-17 13:19:39REVISED ENERGY CALCULATIONS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-08-11 Cont ID  
Sent By tgordon Date 2006-08-11 Time 09:07 Rev Time 0.45
Received By tgordon Date 2006-08-11 Time 09:07 Sent To P
Notes
2006-08-11 00:00:00*** DENIED ***
 **FIRST FLOOR**
 1) NEED TO SHOW CFM'S AT THE KITCHEN
 SUPPLY AIR GRILL.
  
 2) NEED RETURN AIR DUCTS SIZED TO
 STORAGE ROOM #115, LIBRARY #109, AND
 LIVING ROOM #101.
  
 3) RETURN AIR GRILL NEAR THE T-STAT.
 NEEDS TO BE SIZED.
  
 4) 8X13 SUPPLY AIR TRUNK LINE IS TO
 SMALL FOR A 4 TON SYSTEM, PLEASE CORRECT
 OR SUBMIT MANUAL D CALCULATIONS FOR
 RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R
 M1601.1 AND FBC 13-610.1.ABC.1 .
  
 ** SECOND FLOOR **
 5) RTURN AIR TRANSFER DUCT TO MASTER
 BEDROOM SUITE NEEDS TO BE 18", SEE NOTE
 #7.
  
 6) THERE IS NO SUPPLY AIR DUCT TO THE
 GRILL IN BEDROOM #2, IF NEED CORRECT THE
 RETURN AIR TRANSFER DUCT, SEE NOTE #7.
  
 7) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2001 FBC/M 601.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-06 Cont ID  
Sent By tgordon Date 2005-09-06 Time 10:09 Rev Time 0.30
Received By tgordon Date 2005-09-06 Time 10:09 Sent To B
Notes
2005-09-06 00:00:00*** PROVISO ***
 1) MASTER BEDROOM RETURN AIR DUCT TO
 A.H.U. NEEDS TO BE 12" .
 2) 2ND. FLOOR HALL RETURN AIR DUCT TO
 A.H.U. NEEDS TO BE 14" .
 3) MASTER BATHROOM NEEDS AN EXHAUST FAN,
 IF THERE IS NO WINDOW OPENING OF 3 FT.
 PER. FBC/M 402.3.1.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6712.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-16 Cont ID  
Sent By pkrauss Date 2005-06-16 Time 08:04 Rev Time 0.40
Received By pkrauss Date 2005-06-16 Time 07:50 Sent To P
Notes
2005-06-16 00:00:00DENIED:
 1.RETURN AIR JUMPERS ARE NOT SIZED
 PROPERLY.PER 2001 FBC(M)601.4
 EXCEPTION #1 & 3, RETURN AIR JUMPERS
 SHALL BE A MINIMUM OF 1 1/2 TIMES
 (SQUARE INCHES) LARGER THAN THE SUPPLY
 AIR TO THAT AREA.ALL AIR INTO THE
 MASTER SUITE IS TO BE INCLUDED:
 LIBRARY 7" SUPPLY = 9" R/A JUMPER
 GUEST RM 8" SUPPLY = 10" R/A JUMPER
 BEDRM 2 & 3 8" SUPPLY = 10" R/A JUMPER
 MASTER SUITE 10" & 8" SUPPLY=16" R/A
  
 2.TWO COPIES OF ALL SPECIFICATIONS
 REQUIRED PER 2001 FBC 104.2.1.TWO SETS
 OF PLANS WERE SUBMITTED BUT NOT THE
 PRODUCT APPROVALS OR ENERGY
 CALCULATIONS.
  
 3.PROVIDE MANUAL J CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC CHATPER 6.
  
 4.PROVIDE VENTING LAYOUT & MATERIAL
 FOR THE DRYER EXHAUST VENT.
  
 5.CONDENSATE SHALL TERMINATE A MINIMUM
 OF 12" FROM THE BUILDING STRUCTURE PER
 2001 FBC 1503.4.4.
  
 6.PROVIDE AUXILIARY DRAIN PAN WITH
 OVER FLOW PROTECTION.INDICATE WHICH
 METHOD OF OVERFLOW PROTECTION WILL BE
 USED.2001 FBC(M)307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 5 Status F Date 2006-12-01 Cont ID  
Sent By kstevens Date 2006-12-01 Time 13:37 Rev Time 0.00
Received By kstevens Date 2006-12-01 Time 13:37 Sent To M
Notes
2006-12-01 13:40:32DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 ****FROM THE PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT 18 OF 18 INDICATE ALL PIPE SIZES
 ON THE RISER DIAGRAM. TABLES 710.1(1) &
 710.1(2).
 ****NO RESPONSE. COMMENT NOT ADDRESSED
  
 3. OK
  
 *****NEW COMMENT****
 PLUMBING RISER WOULD HAVE BEEN APPROVED, BUT IT IS ON
 THE SAME SHEET AS THE ELECTRICAL REVISION SO COMMENT
 NUMBER 2 CAN BE ADDRESSED WITH THE ELECTRICAL
 COMMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-08-19 Cont ID  
Sent By kstevens Date 2006-08-19 Time 08:26 Rev Time 0.00
Received By kstevens Date 2006-08-19 Time 08:26 Sent To B
Notes
2006-08-19 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT 18 0F 18 SANT. RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. PLEASE MAKE
 CHANGES TO RISER DIAGRAM THAT ARE SHOWN
 ON THE FLOOR PLAN. SECTION 106.3.5.1.3.
  
 2. SHT 18 OF 18 INDICATE ALL PIPE SIZES
 ON THE RISER DIAGRAM. TABLES 710.1(1) &
 710.1(2).
  
 3. ALL SHEETS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON DESIGNING THE
 PLANS. 106.1.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-10-04 Cont ID  
Sent By jleech Date 2005-10-04 Time 14:49 Rev Time 0.33
Received By jleech Date 2005-10-04 Time 14:49 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-09-01 Cont ID  
Sent By jleech Date 2005-09-01 Time 07:55 Rev Time 0.50
Received By jleech Date 2005-09-01 Time 07:55 Sent To M
Notes
2005-09-01 00:00:00DENIED;
 SEE ELECTRICAL PLAN REVIEW NOTE # 8.
 PRINTED NAME AND SIGNITURE REQUIRED ON
 DRAWINGS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-16 Cont ID  
Sent By kstevens Date 2005-06-16 Time 13:31 Rev Time 0.55
Received By kstevens Date 2005-06-16 Time 13:31 Sent To B1
Notes
2005-06-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHT 18 OF 18 SANT. RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 A. TUB NOT VENTED 2ND FLOOR GUEST ROOM
 BATHROOM.
 B. KITCHEN SINK SHALL NOT DRAIN THRU
 THE HORIZONTAL WET VENT FOR THE POWDER
 ROOM FIXTURES. SECTION 909.1. - KITCHEN
 SINKS SHALL DISCHARGE DOWNSTREAM OF THE
 POWDER ROOM FIXTURES.
 C. KITCHEN SINK IN THE ISLAND. INDICATE
 HOW THIS CAN BE VENTED THRU THE ROOF
 WITH NO WALL NEXT TO THE SINK. SUGGEST
 USE OF AN AIR ADMITTENCE VALVE, OR AN
 ISLAND VENT. SECTIONS 913, OR 917.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2006-12-16 Cont ID  
Sent By mmclean Date 2006-12-16 Time 06:40 Rev Time 0.00
Received By mmclean Date 2006-12-16 Time 06:40 Sent To  
Notes
2006-12-16 06:41:16REVISION: DECORATIVE PAVERS UNSEALED WITHIN THE FRONT
 SETBACK FOR DRIVEWAY AND WALKWAY.OK PER KELLY
 FREEMAN, PLANNER 822-1435

Review Stop Z ZONING
Rev No 3 Status P Date 2006-02-03 Cont ID  
Sent By mmclean Date 2006-02-03 Time 13:45 Rev Time 0.00
Received By mmclean Date 2006-02-03 Time 13:45 Sent To B
Notes
2006-02-03 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE/WALL/GATE/COLUMNS WITH EASEMENT
 APPROVAL FROM THE CITY OF WEST PALM
 BEACH.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-24 Cont ID  
Sent By mmclean Date 2005-08-24 Time 16:38 Rev Time 0.00
Received By mmclean Date 2005-08-24 Time 16:37 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-08 Cont ID  
Sent By mmclean Date 2005-06-08 Time 16:59 Rev Time 0.00
Received By mmclean Date 2005-06-08 Time 16:59 Sent To I
Notes
2005-06-08 00:00:00DENIED,
 1. DRIVEWAY EXCEEDS THE ZONING
 REQUIREMENTS.
 2. MUST REDUCE THE WIDTH OF DRIVEWAY.
 3. ROOF OVERHANG CAN ONLY HANG 3FT INTO
 ANY SETBACK.(NO ROOF PLANS PROVIDED.)
  
 **MUST HAVE 1000SQ FT OR 75% OF
 LANDSCAPE WITHIN THE FIRST 25FT FRONT
 SETBACK**
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved