Plan Review Details - Permit 05051417
Plan Review Stops For Permit 05051417
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2005-08-23 Cont ID  
Sent By spalmer Date 2005-08-23 Time 13:20 Rev Time 0.00
Received By spalmer Date   Time   Sent To  
Notes
2005-08-23 00:00:00SEE05080530

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-05-25 Cont ID  
Sent By alange Date 2005-05-25 Time 16:17 Rev Time 2.00
Received By alange Date 2005-05-24 Time 11:41 Sent To I
Notes
2005-05-25 00:00:00BUILDING PLAN REVIEW OK

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2005-08-23 Cont ID  
Sent By spalmer Date 2005-08-23 Time 13:20 Rev Time 0.00
Received By spalmer Date   Time   Sent To  
Notes
2005-08-23 00:00:00SEE 05080530

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-09 Cont ID  
Sent By dpalmer Date 2005-06-09 Time 09:16 Rev Time 1.50
Received By dpalmer Date 2005-06-08 Time 16:53 Sent To  
Notes
2005-06-09 00:00:00************ UNSAT *************
  
 **PLANS SUBMITTED FOR "PLAN REVIEW"
 ONLY.
 PLANS HAVE NOT BEEN SUBMITTED FOR PERMIT
 APPLICATION.
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITEL BLOCKS. PLEASE SEE FAC
 61G15-23.002, FS 471.023
  
 2)NOTE: PLEASE SEE FS 471.025, PLANS ARE
 REQUIRED TO BE SIGNED , DATED AND SEALED
 BY SAID ENGINEER OF RECORD.
  
 3)NOTE: PLEASE SEE FBC 104.2.1, ALL
 PLANSMUST CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLEFOR
 PLANS/DESIGN.
 PLEASE SEE THIS IS REQUIRED FOR ALL
 PLANS WHEATHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
  
 4)NOTE: PLEASE SEE NOTE #9 ON E-5
 MENTIONS, TO DEMO LPR AND REPLACE,
 HOWEVER RISER AND PLANS DO NOT SHOW/NOTE
 THIS AND BEING REPLACED OR NEW.
 215.5
  
 5)NOTE: PLEASE SEE MIN CLEARENCE
 REQUIREMENTS PER 110.26
 PLEASE SEE IF PANEL EXISTING DO NOT MEET
 MIN CLEARENCE, NEW PANELS MAY NOT BE
 INSTALLED IN SMAE LOCATION WITHOUT
 MEETING MIN CLEARENCE REQUIREMENTS.
 PLEASE ALSO SEE WALL BEING SHOWN
 DIRECTLY IN THE MIDDLE OF AN ELECTRICAL
 PANEL.
 PLEASE SEE ELECTRICAL PANEL DISCRIPTION
 MENTIONS PANEL LPS TO BE IN SHOWER AREA?
 PLEASE CLARIFY THIS. ELECTRICAL PANEL
 CONTAINING OCP SAHLL NOT BE INSTALL IN
 SHOWERS.
 PLEASE ALSO SEE NEW PANEL LPW.
  
 6)NOTE: PLEASE INDICATE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULES.
 215.5
  
  
 7)NOTE: PLEASE VERIFY OCP FOR NEW 80 GAL
 WH. THIS IS ONLY A NOTE TO VERIFY.
  
 8)NOTE: PLEASE SEE RISER DIAGRAM NOTE
 MENTIONS A 24HR AMP READING. PLEASE SEE
 220.35 FOR MIN REQUIREMENTS FOR EXISTING
 LOADS WHEN LOAD CALCULATIONS ARE NOT
 PERFORMED.
 PLEASE INCLUDE LOAD CALCAULTIONS THROUGH
 MDP FOR NEW ADDED LOADS.
  
 9)NOTE: PLEASE SEE RISER DIAGRAMS ARE
 NOTED AS BEING EXISTING. SOME DETAILS IN
 EACH RISER SHOWN NOTES ITEMS AS NEW AND
 SOME ARE NOTED AS EXISTING, SOME DO NOT
 CONTAIN ANY INFORMATION AS NEW OR
 EXISTING.???
 215.5
  
 10)NOTE: PLEASE CORRELATE NOTES AND
 PANELS ON RISER. SEE LPLM, ?LPM?
 PLEASE SEE NOTES WHICH MENTIOSN THAT
 EXISTING BRKRS DO NOT WORK, YET PLANS DO
 NOT SHOW NEW BRKRS ETC.??
 215.5
  
 11)NOTE: PLEASE VERIFY AND SHOW METHOD
 OF EQUIPMENT GORUNDING BETWEEN SOME
 PANELS WHERE NO EQUIPMENT GROUNDING
 CONDUCTORS ARE SHOWN.
 215.5,250.110,.250.122 ETC.
  
 PLEASE COMPLETE PLANS AND SUBMIT THE
 ABOVE INFORMATION FOR REVIEW. IF THERE
 ARE ANYQUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2005-08-23 Cont ID  
Sent By spalmer Date 2005-08-23 Time 13:20 Rev Time 0.00
Received By spalmer Date   Time   Sent To  
Notes
2005-08-23 00:00:00SEE 05080530

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-06-15 Cont ID  
Sent By mwennerg Date 2005-06-15 Time 15:46 Rev Time 0.00
Received By mwennerg Date 2005-06-15 Time 15:46 Sent To  
Notes
2005-06-15 00:00:00******DENIED******
  
 1) PLEASE SEE REVIEW COMMENTS IN REGARDS
 TO FS AND FAC REQUIREMENTS.
  
 2) DRAWINGS HAVE BEEN SUBMITTED FOR PLAN
 REVIEW ONLY.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-28 Cont ID  
Sent By adarroug Date 2006-06-28 Time 10:40 Rev Time 0.00
Received By adarroug Date 2006-06-28 Time 10:40 Sent To M
Notes
2006-06-28 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-05-20 Time 10:21 Sent To  
Notes
2005-05-20 00:00:00TO "COMM" BD#15

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-08-23 Cont ID  
Sent By spalmer Date 2005-08-23 Time 13:19 Rev Time 0.00
Received By spalmer Date   Time   Sent To  
Notes
2006-06-28 00:00:00SEE REVIEW UNDER VOIDED PERMIT #
 05080530.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-21 Cont ID  
Sent By hmoser Date 2005-06-21 Time 10:10 Rev Time 0.00
Received By hmoser Date 2005-06-21 Time 08:42 Sent To  
Notes
2005-06-21 00:00:00PLAN DENIED
 SEE ELRCTRICAL NOTES #1,#2,#3.
 PLEASE PROVIDE ENERGY CALCELATIONS AND
 MANUAL J.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status N Date 2005-08-23 Cont ID  
Sent By spalmer Date 2005-08-23 Time 13:19 Rev Time 0.00
Received By spalmer Date   Time   Sent To  
Notes
2005-08-23 00:00:00SEE 05080530

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-20 Cont ID  
Sent By pschmitz Date 2005-06-20 Time 08:58 Rev Time 0.00
Received By pschmitz Date 2005-06-20 Time 08:57 Sent To M
Notes
2005-06-20 00:00:00PLUMBING PLAN REVIEW FBC 2002 PROVISO:
 (1) PASS PENDING ELECTRICAL PLAN REVIEW
 NOTES #1, #2, #3.
 END OF COMMENTS
 QUESTIONS,
 PAUL SCHMITZ561-805-6692