Plan Review Details - Permit 05051368
Plan Review Stops For Permit 05051368
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-08-20 Cont ID  
Sent By rbrown Date 2006-08-20 Time 15:38 Rev Time 0.00
Received By rbrown Date 2006-08-20 Time 15:38 Sent To  
Notes
2006-08-20 00:00:00STRUCTURAL SUBMITTAL ON 8/14/06 FOR
 COVERED WALKWAY SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-06-10 Cont ID  
Sent By rbrown Date 2006-06-10 Time 20:50 Rev Time 0.00
Received By rbrown Date 2006-06-10 Time 20:50 Sent To  
Notes
2006-06-10 00:00:00REVISION SUBMITTED 4/24/06 FOR SITE
 ELECTRICAL AND SITE LIGHTING INCLUDING
 LIGHT POLES WIND DESIGN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-11-21 Cont ID  
Sent By rbrown Date 2005-11-21 Time 08:30 Rev Time 0.00
Received By rbrown Date 2005-11-21 Time 08:30 Sent To  
Notes
2005-11-21 00:00:00RE-SUBMITTED PLANS SHOW NO CHANGES FOR
 BUILDING PLAN REVIEW. PROVISO STILL
 APPLIES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-18 Cont ID  
Sent By rbrown Date 2005-08-18 Time 16:35 Rev Time 0.00
Received By rbrown Date 2005-08-18 Time 16:35 Sent To  
Notes
2005-08-18 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 -- PROVISO --
 SHEET A-1.02, A SEPARATE PERMIT
 APPLICATION IS REQUIRED FOR THE MONUMENT
 SIGN.NOTE THAT CITY OF WEST PALM BEACH
 CODE OF ORDINANCES SEC. 78-6(3) MONUMENT
 SIGNS, REQUIRES ALL MONUMENT SIGNS FOR
 MULTIPLE RESIDENTIAL, COMMERCIAL,
 INDUSTRIAL, OR INSTITUTIONAL
 DEVELOPMENTS TO POST THE ADDRESS RANGE
 FOR THE DEVELOPMENT.THE ADDRESS RANGE
 FOR THIS PROJECT IS (4826 TO 4888).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-29 Cont ID  
Sent By rbrown Date 2005-06-29 Time 17:00 Rev Time 0.00
Received By rbrown Date 2005-06-28 Time 12:47 Sent To  
Notes
2005-06-29 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
  
 1) FBC 1606.1.7WIND LOAD FOR DUMPSTER
 ENCLOSURE, MONUMENT SIGN AND LIGHT
 POLES.THE PLANS SHALL STATE THE BASIC
 WIND SPEED, WIND IMPORTANCE FACTOR, WIND
 EXPOSURE CATEGORY AND DESIGN WIND
 PRESSURES.ADD THIS INFORMATION TO THE
 PLANS.
  
 2) PROVISO -- SHEET A-1.02, A SEPARATE
 PERMIT APPLICATION IS REQUIRED FOR THE
 MONUMENT SIGN.NOTE THAT CITY OF WEST
 PALM BEACH CODE OF ORDINANCES SEC.
 78-6(3) MONUMENT SIGNS, REQUIRES ALL
 MONUMENT SIGNS FOR MULTIPLE RESIDENTIAL,
 COMMERCIAL, INDUSTRIAL, OR INSTITUTIONAL
 DEVELOPMENTS TO POST THE ADDRESS RANGE
 FOR THE DEVELOPMENT.THE ADDRESS RANGE
 FOR THIS PROJECT IS (4826 TO 4888).
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-11-16 Cont ID  
Sent By dpalmer Date 2006-11-16 Time 08:30 Rev Time 0.00
Received By dpalmer Date 2006-11-16 Time 08:17 Sent To PC
Notes
2006-11-16 08:31:49REDLINED.
  
  
  
 LT POLES REVIEWED FOR ELEC ONLY. WIND LOAD REVIEW NIC.
  
 LIGHTNING PROTECTIONAS NOTED NIC.
  
 GATES AND GATE CONTROLLERS WILL BE FUTURE AND UNDER
 SEPARATE PERMITS AT A LATER DATE.(WILL NEED FIRE REVIEW
 AT THAT TIME ALSO).

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 16:09 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 16:06 Sent To B
Notes
2006-05-14 00:00:00REVS TO SITE PLANS OK, ROUTED TO
 BUILDING REVIEWER FOR REVIEW OF WIND
 LOAD CALCS.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-03-16 Cont ID  
Sent By dpalmer Date 2006-03-16 Time 19:24 Rev Time 0.00
Received By dpalmer Date 2006-03-16 Time 19:15 Sent To  
Notes
2006-03-16 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE SEE RISER STILL SHOWS AN
 "EQUIPMENT GROUNDING CONDUCTOR" FROM
 METER TO THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE THIS WAS NOTED ON FIRST TWO
 REVIEWS, AND REDLINED ON LAST REVIEW TO
 ISSUE PERMIT. THIS HAS STILL NOT BEEN
 CORRECTED. PLEASE SEE PLANS INDICATE 5
 CONDUCTORS FROM METER.
 PLEASE KNOW, IF PLANS COME BACK WITH
 SAME COMMENT NOT ADDRESSED THIS OFFICE
 WILL HAVE NOT CHOICE BUT TO ISSUE A 4X
 FEE FOR THE PLAN REVIEW PORTION OF THE
 PERMIT FEE AS REQUIRED PER FS
 553.80(2)(B).
  
 2)NOTE: PLEASE SEE WIND LOADS AND
 CALCULATIONS SHALL BE SHOWN FOR LIGHT
 POLES TO MEET FBC 140MPH. THIS WAS ALSO
 REDLINED, HOWEVER PLANS DO NOTY REFLECT
 THIS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-09-29 Cont ID  
Sent By dpalmer Date 2005-09-29 Time 18:40 Rev Time 0.00
Received By dpalmer Date 2005-09-29 Time 18:03 Sent To  
Notes
2005-09-29 00:00:00REDLINED ,,
  
 RISER STILL SHOWS AND "EQUIPMENT
 GROUNDING CONDUCTOR" FROM METER TO
 MAINS/ FIRST MEANS OF DISCONNECT.
 THIS SAHLL NOT BE INSTALLED,
 250.6,250.24

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-07-26 Cont ID  
Sent By dpalmer Date 2005-07-26 Time 13:21 Rev Time 0.50
Received By dpalmer Date 2005-07-26 Time 13:21 Sent To  
Notes
2005-07-26 00:00:00*********** UNSAT 2ND REVIEW **********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND ONE NEW NOTE.
  
 1)NOTE: PLEASE SEE LETTER FROM
 CONTRACTOR FOR CHNAGE IN SCOPE OF WORK
 IS STILL REQUIRED TO BE CORRECTLY
 NOTORIZED PER FS 117 WITH ALL
 INFORMATION SET UP AS SET-FORTH IN FS
 ABOVE.
  
 2)NOTE: PLEASE SEE RISER DIAGRMA HAS NOW
 BEEN CHANGED TO INCREASE MAIN TO 125A'S,
 HOWEVER METER IS STILL SHOWN AS 100A'S.
 OLD MAIN WAS 100A'S
 PLEASE CORRELATE.
 215.5,240.4,310.16 ETC.
  
 3)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTOR FROMM METER TO MAIN/FIRST
 MEANS OF DISCONNECT. PLEASE SEE 250.6,
 250.24, AN "EQUIPMENT GROUNDING
 CONDUCTOR" IS ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
  
 4)NOTE: PLEASE SEE CA NUMBER WHICH
 APPEARS TO BE ON TITLE BLOCK WHICH NOT
 NOT VISABLE.
 PLEASE INCREASE FONT IN CAD OR ? TO MAKE
 THIS READABLE.
  
 5)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONAL AND PLANS WITH
 REPEAT COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-01 Cont ID  
Sent By dpalmer Date 2005-07-01 Time 19:12 Rev Time 0.50
Received By dpalmer Date 2005-07-01 Time 19:00 Sent To B
Notes
2005-07-01 00:00:00********** UNSAT ***************
  
 1)NOTE: PLEASE SEE LETTER FROM
 CONTRACTOR CHANGING SCOPE OF WORK SHALL
 BE PROPERLY NOTORIZED PER FS 117 BEFORE
 IT CAN BECOME LEGAL AND LEGAL FOR PUBLIC
 RECORD. LETTER AS SUBMITTED IS NOT LEGAL
 AND CAN NOT BE ACCEPTED.
 PLEASE SEE FS 117.05
  
 2)NOTE: PLEASE SUBMIT WINDING LOAD FOR
 ALL SITE -LIGHTING POLES TO MEET FBC
 140MPH. PLEASE SEE BLD REVIEW COMMENTS.
  
 3)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANEL SCHEDULE SUBMITTED. PLEASE
 SEE RISER SHOWS 100A MCB AND PANEL
 SCHEDULE INDICATES 125A MCB. PLEASE SEE
 240.4 AND 310.16 FOR ANY POSSIBLE AWG
 CHANGES AND CONDUIT SIZE CHANGES.
  
 4)NOTE: PLEASE SEE 250.122 FOR MIN
 EQUIPMENT GROUNDING CONDUCTOR SIZING.
 PLEASE SEE GATE MOTOR CIRCUIT, 30A W.
 #12 AWG EQUIPMENT GROUNDING.
  
 5)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 INFROAMTION REQUIRED ON TITLE BLOCKS.
 PLEASE SEE CA # APPEARS TO BE SHOWN,
 HOWEVER IT IS NOT VISABLE.
 PLEASE CORRECT.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-13 Cont ID  
Sent By dpalmer Date 2005-06-13 Time 10:36 Rev Time 0.25
Received By dpalmer Date 2005-06-13 Time 10:36 Sent To B
Notes
2005-06-13 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE CORRELATE PERMIT
 APPLICATION SUBMITTED ALONG WITH PLANS
 SUBMITTED.
 PLEASE SEE PERMIT APPL ORIGINALLY
 INDICATED SITE ELECTRICAL, SITE
 AMENITIES ETC ALONG WITH A VALUE OF
 $380,000, HOWEVER PERMIT APPLICATION
 CHANGED TO SAY DUMPSTER ENCLOSURE , AND
 VALUE CHANGED TO $20K.
  
 PLEASE SEE PLANS SUBMITTEDDO NOT
 CORRELATE FOR DUMPSTER ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-06-07 Cont ID  
Sent By mamini Date 2005-06-07 Time 08:17 Rev Time 0.50
Received By mamini Date 2005-06-07 Time 08:17 Sent To E
Notes
2005-06-07 00:00:00PASSED WITH PROVISOS:
  
 1. PLEASE NOTE THAT A 12'-6" CLEAR
 OPENING BETWEEN THE GATE POSTS PER CITY
 OF WPB IS REQUIRED, SHEETS A-1.02 OF
 THIS SUBMITTAL MARKED.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-19 Cont ID  
Sent By nmccray Date 2005-08-19 Time 10:54 Rev Time 0.00
Received By nmccray Date 2005-08-19 Time 10:54 Sent To  
Notes
2005-08-19 00:00:00PROVISO:
  
 PASSED ONLY IF THERE IS "NO" CURB
 SEPARATING THE LANES AT THE ENTRANCE.
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-06-28 Cont ID  
Sent By mwennerg Date 2005-06-28 Time 13:39 Rev Time 0.00
Received By mwennerg Date 2005-06-28 Time 13:39 Sent To  
Notes
2005-06-28 00:00:00******DENIED******
  
 1) PLEASE NOTE THAT THE ENTRANCE
 ARRANGEMENT INTO THE PROPERTY APPEARS
 DIFFERENT FROM THE ORIGINAL PLAN REVIEW.
 IN ACCORDANCE WITH NFPA 1, A MINIMUM OF
 20' CLEAR AND UNOBTRUCTED ACCESS MUST BE
 PROVIDED FOR EMERGENCY VEHICLE TRAFFIC.
 PLEASE ILLUSTRATE APPROPRIATE DIMENSIONS
 ON THE DRAWINGS FOR REVIEW.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-11-09 Cont ID  
Sent By adarroug Date 2006-11-09 Time 15:41 Rev Time 0.00
Received By adarroug Date 2006-11-09 Time 15:41 Sent To E
Notes
2006-11-09 15:42:19TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 13:46 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 13:46 Sent To B
Notes
2006-08-14 00:00:00TO "RBROWN" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-04-25 Cont ID  
Sent By adarroug Date 2006-04-25 Time 13:50 Rev Time 0.00
Received By adarroug Date 2006-04-25 Time 13:50 Sent To Z
Notes
2006-04-25 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-04-25 Cont ID  
Sent By adarroug Date 2006-04-25 Time 13:48 Rev Time 0.00
Received By adarroug Date 2006-04-25 Time 13:48 Sent To E
Notes
2006-04-25 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 17:12 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 17:12 Sent To E
Notes
2006-03-09 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 18:53 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 18:53 Sent To  
Notes
2005-09-28 00:00:00TO "COMM" BD#5
2005-09-23 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 16:17 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 16:17 Sent To  
Notes
2005-07-25 00:00:00TO "COMM" BD#4
2005-07-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-01 Cont ID  
Sent By dpalmer Date 2005-07-01 Time 18:59 Rev Time 0.00
Received By dpalmer Date 2005-07-01 Time 18:59 Sent To  
Notes
2005-07-01 00:00:00PLANS RE-ROUTED, TO ELEC DP'S.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-06 Cont ID  
Sent By mjacobs Date 2005-06-06 Time 16:02 Rev Time 0.00
Received By mjacobs Date 2005-06-06 Time 16:02 Sent To ENG
Notes
2005-06-06 00:00:00TO 'MAMINI' DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-19 Cont ID  
Sent By adarroug Date 2005-06-29 Time 16:13 Rev Time 0.00
Received By rbrown Date 2005-05-19 Time 16:13 Sent To Z
Notes
2005-07-01 00:00:00NOTARIZED LETTER REC'D.APPLICATION
 ROUTED BACK TO D. PALMER FOR REVIEW. RB
  
  
2005-05-20 00:00:00ROUTE TO R BROWN AFTER ZONING REVIEW.
  
  
2005-05-19 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 4 Status P Date 2006-05-05 Cont ID  
Sent By eschneid Date 2006-05-05 Time 14:53 Rev Time 0.00
Received By eschneid Date 2006-05-05 Time 14:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-01-04 Cont ID  
Sent By eschneid Date 2006-01-04 Time 17:39 Rev Time 0.00
Received By eschneid Date 2006-01-04 Time 17:37 Sent To  
Notes
2006-01-04 00:00:00PROVISO: TREES ARE REQUIRED TO BE ADDED
 IN ACCORDANCE WITH THE REDLINES ON THE
 APPROVED LANDSCAPE PLANS.

Review Stop Z ZONING
Rev No 2 Status F Date 2005-11-22 Cont ID  
Sent By eschneid Date 2005-11-22 Time 09:00 Rev Time 0.00
Received By eschneid Date 2005-11-22 Time 09:00 Sent To  
Notes
2005-11-22 00:00:00THE BUILDING PERMIT PLANS DO NOT MATCH
 THE PLANS APPROVED BY ORD. NO. 3513-02.
 PERMIT PLANS SHALL BE CHANGED TO MATCH
 APPROVED PLANS, OR AN AMENDMENT TO THE
 APPROVED SITE PLAN IS REQUIRED.
 CONTACT ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2005-06-03 Time   Rev Time  
Received By   Date 2005-06-03 Time   Sent To I
Notes
***NONE***