Plan Review Details - Permit 05051300
Plan Review Stops For Permit 05051300
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-10-03 Cont ID  
Sent By jwitmer Date 2005-10-03 Time 10:33 Rev Time 0.66
Received By jwitmer Date 2005-10-03 Time 10:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-09-19 Cont ID  
Sent By jwitmer Date 2005-09-19 Time 14:07 Rev Time 0.55
Received By jwitmer Date 2005-09-19 Time 14:07 Sent To  
Notes
2005-09-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051300
 ADD: 4220 BROADWAY
 CONT:PCF CONSTRUCTION
 TEL: (561)312-7103
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
  
 1)PLANS INDICATE A CHANGE IN CUTTING IN
 NEW GLASS BLCK WINDOWS. PRODUCT
 APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:GLASS BLOCK.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-18 Cont ID  
Sent By pschmitz Date 2005-08-17 Time 17:14 Rev Time 0.88
Received By jwitmer Date 2005-08-18 Time 16:29 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-07-21 Cont ID  
Sent By jwitmer Date 2005-07-21 Time 07:06 Rev Time 0.55
Received By jwitmer Date 2005-07-20 Time 07:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-17 Cont ID  
Sent By jwitmer Date 2005-06-17 Time 16:25 Rev Time 1.55
Received By jwitmer Date 2005-06-17 Time 16:25 Sent To  
Notes
2005-06-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051300
 ADD: 4220 BROADWAY
 CONT: PCF CONSTRUCTION
 TEL: (561)346-8281
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, A
 SURVEY OR SITE PLAN WITH THE PLACEMENT
 OF BUILDING AND LOT LINES.
  
 3) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) PROVIDE DETAILS FOR FLOOR AND SEAL TO
 ROOF DECK ABOVE FOR THE 1HR TENANT
 SEPERATION. 705.7.1 JOINTS INSTALLED IN
 OR BE- TWEEN FIRE RESISTANT WALLS, FIRE
 RESIS- TANT FLOORS OR FLOOR/ CEILING
 ASSEMBLIES AND FIRE RESISTANT ROOFS OR
 ROOF/ CEIL- ING ASSEMBLIES SHALL BE
 PROTECTED BY AN APPROVED FIRE RESISTANT
 JOINT SYSTEM DESIGNED TO RESIST THE
 PASSAGE OF FIRE FOR A PERIOD NOT LESS
 THAN THE RE- QUIRED FIRE RESISTANCE
 RATING OF THE WALL, FLOOR OR FLOOR IN OR
 BETWEEN
 WHICH IT IS INSTALLED.
  
 5)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 6) PLANS INDICATE THE USE OF "C" LABEL
 DOORS, TABLE 705. 1.2 LIST OPENING
 PROTECTION IN MINUTES & HRS.
  
 7) THE RECEPTION AREA LOOKS AS IF THIS
 IS TO BE SEPERATED FROM THE 2
 BUSINESSES, BUT NO RATING ON WALLS OR
 WINDOW?
  
 8)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) BACK EXTERIOR DOOR
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 15:32 Rev Time 0.25
Received By dpalmer Date 2005-09-03 Time 15:32 Sent To  
Notes
2005-09-03 00:00:00**********UNSAT *********
  
  
 1)NOTE: PLEASE VERIFY SEC'S IN EXISTING
 RISER FOR 200A SERVICE SHOWN.
 240.4,310.16
  
 2)NOTE: PLEASE SEE PREVIOUS REDLINED
 NOTE FOR 700.12E.
 THIS WAS NOT CORRECTED FOR REVSIONS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 3)NOTE: PLEASE VERIFY 2/0'S SHOWN FOR
 100A PANELS. PLEASE ALSO VERIFY MCB'S
 SHOWN FOR BOTH INSIDE PANELS??
 PLEASE NOTE: EITHER ABOVE DOES NOT
 VIOLATE NEC, HOWEVER IF SHOWN THIS WAY,
 THEN 2/0'S AND MCB'S IN INTERIOR PANELS
 WILL BE REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-08-11 Cont ID  
Sent By dpalmer Date 2005-08-11 Time 18:04 Rev Time 0.50
Received By dpalmer Date 2005-08-11 Time 18:03 Sent To  
Notes
2005-08-11 00:00:00****** PLANS REDLINED.*******
  
 PREVIOUS REVIEWS MENTIONED ALL EM/ EXT
 LTS TO BE WIRED AHEAD OF ALL LOCAL
 BRANCH CIRCUIT FEEDING LIGHTING IN THOSE
 AREAS.
 PLEASE SEE PLANS CONTAIN A NOTE FOR
 THIS, HOWEVER PLANS FOR BOTH TENANT
 SPACES INDICATE EACH OF THESE PANELS
 PROVIDING A DEDICATE CIRCUIT FOR EACH
 AND NOT ON LOCAL BRANCH CIRCUIT?????
  
 PLEASE SEE THIS IS TO BE REVISED LONG
 WITH ANY OTHER CHANGES BEFORE ANY ROUGH
 ELECTRICAL INSPECTION.
  
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 NOC EXPIRED FS 713.13(2)
 PLEASE SEE IF WORK HAS NO TCOMMENCED
 WITH IN 90 DAYS OF RECORDING,NOC EXPIRES
 AND MUST BE RE-RECORDED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-15 Cont ID  
Sent By dpalmer Date 2005-07-15 Time 15:57 Rev Time 0.25
Received By dpalmer Date 2005-07-14 Time 20:52 Sent To  
Notes
2005-07-15 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE PLANS CAME BACK IN
 WITHOUT CORRECTIONS MADE.
 PLEASE SEE ONLY ONE SET WAS SUBMITTED
 WHEN A MIN OF TWO IS REQUIRED.
 PLEASE SEE PLANS ARE ALSO REQUIRED TO BE
 SIGNED, DATED AND SEALED BY THE ENGINEER
 OF RECORD.
 FS471.025
  
 2)NOTE: PLEASE SEE MIN SERVICE FOR
 TENANT IS 60A'S.
 230.79
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
2005-07-14 00:00:00IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-14 Cont ID  
Sent By dpalmer Date 2005-06-14 Time 06:51 Rev Time 0.00
Received By dpalmer Date 2005-07-20 Time 07:06 Sent To  
Notes
2005-06-14 00:00:00*********** UNSAT *********
  
 1)NOTE: PLEASE SEE PLANS APPEAR TO SHOW
 TO SEPARATE TENANTS SHARING THE SAME
 SPACE?
 PLANS CALL FOR BUS> "A" AND BUS>"B"??
 PLEASE SEE FIRE AND BLDG COMMENTS.
 PLEASE SEE PLANS INDICATE A 1HR TENANT
 SEPARATION.
 PLEASE SEE CIRCUITING FOR TWO SEPARATE
 TENANTS SHALL BE SEPARATED. PLEASE SEE
 THAT ELECTRICLA PANEL FOR CIRCUITING IN
 ONE BUSINESS CAN NOT BE LOCATED IN
 ANOTHERS TENANT SPACE.210.25
  
 2)NOTE: PLEASE CLARIFY FRONT WINDOW IS
 INDICATED ON PLANS AS "STOREFRONT
 WINDOW"? PLEASE SEE IF OCCUPANCY IS
 GOING TO BE MERCHANTILE OF ANY KIND,
 "SHOW WINDOW RECEPTS ABOVE WINDOW WILL
 BE REQUIRED.
 210.62
  
 3)NOTE: PLEASE SEE 700.12E FIR
 CIRCUITING OF EM/EXT LTS.THE BRANCH
 CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 4)NOTE: PLEASE INDICATE NEW OR EXISTING
 REQUIRED SIGN CIRCUIT(S).
 600.5
  
 PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OL/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABVOE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2005-09-30 Cont ID  
Sent By mwennerg Date 2005-09-30 Time 13:21 Rev Time 0.00
Received By mwennerg Date 2005-09-30 Time 13:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2005-09-30 Cont ID  
Sent By mwennerg Date 2005-09-30 Time 13:21 Rev Time 0.00
Received By mwennerg Date 2005-09-30 Time 13:21 Sent To  
Notes
2005-09-30 00:00:00REVISION DATED 9/21/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-09-23 Cont ID  
Sent By mwennerg Date 2005-09-23 Time 11:08 Rev Time 0.00
Received By mwennerg Date 2005-09-23 Time 11:08 Sent To  
Notes
2005-09-23 00:00:00REVISION DATED 8/20/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-08-09 Cont ID  
Sent By mwennerg Date 2005-08-09 Time 09:11 Rev Time 0.00
Received By mwennerg Date 2005-08-09 Time 09:11 Sent To  
Notes
2005-08-09 00:00:00******PASSED******
  
 AUDIBLE/VISUAL DEVICES TO BE WIRED INTO
 DUCT SMOKE DETECTORS WHERE PROVIDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-08-02 Cont ID  
Sent By mwennerg Date 2005-08-02 Time 13:06 Rev Time 0.00
Received By mwennerg Date 2005-08-02 Time 13:06 Sent To  
Notes
2005-08-02 00:00:00******DENIED******
  
 1) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS REQUIREMENTS FOR PLANS.
  
 2) PLEASE NOTE THAT PLANS WERE RETURNED
 WITHOUT ADDRESSING COMMENT #1 IN REGARDS
 TO SMOKE ALARMS.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-06-14 Cont ID  
Sent By mwennerg Date 2005-06-14 Time 10:08 Rev Time 0.00
Received By mwennerg Date 2005-06-14 Time 09:55 Sent To  
Notes
2005-06-14 00:00:00****DENIED****
  
 1) THE DRAWINGS SHOW SMOKE ALARMS WITH
 STROBES. IS THERE A FIRE ALARM SYSTEM OR
 ARE THE SMOKE ALARMS TIED INTO DUCT
 SMOKE DETECTORS?
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED TO BE MOUNTED AT LOCATIONS NOT
 TO EXCEED 75' TRAVEL DISTANCE.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE ALARM AND FIRE
 SPRINKLER REMODEL IF APPLICABLE.
  
 4) PLEASE INDICATE THE FIRE RATED DOORS
 IN TERMS OF HOURS OR MINUTES.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 20:00 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 20:00 Sent To  
Notes
2005-09-28 00:00:00TO "COMM" BD#14
2005-09-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-02 Cont ID  
Sent By adarroug Date 2005-09-02 Time 16:56 Rev Time 0.00
Received By adarroug Date 2005-09-02 Time 16:56 Sent To  
Notes
2005-09-02 00:00:00TO "COMM" BD#51

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-05 Cont ID  
Sent By adarroug Date 2005-08-05 Time 08:49 Rev Time 0.00
Received By adarroug Date 2005-08-05 Time 08:49 Sent To  
Notes
2005-08-08 00:00:00TO "COMM" BD#41
2005-08-05 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 12:38 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 12:38 Sent To  
Notes
2005-07-13 00:00:00TO "COMM" BD#8
2005-07-07 00:00:00WAITING FOR SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-24 Cont ID  
Sent By lmartine Date 2005-06-24 Time 10:18 Rev Time 0.00
Received By lmartine Date 2005-05-20 Time 10:52 Sent To  
Notes
2005-06-02 00:00:00TO "COMM" BD#48
2005-05-20 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-06-20 Cont ID  
Sent By hmoser Date 2005-06-20 Time 13:03 Rev Time 0.00
Received By hmoser Date 2005-06-20 Time 12:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-08-18 Cont ID  
Sent By pschmitz Date 2005-08-18 Time 14:46 Rev Time 0.00
Received By pschmitz Date 2005-08-18 Time 14:46 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2005-08-17 Cont ID  
Sent By pschmitz Date 2005-08-17 Time 15:41 Rev Time 0.00
Received By pschmitz Date   Time   Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-20 Cont ID  
Sent By pschmitz Date 2005-06-20 Time 11:03 Rev Time 0.00
Received By pschmitz Date 2005-06-20 Time 11:03 Sent To M
Notes
***NONE***