Plan Review Details - Permit 05051279
Plan Review Stops For Permit 05051279
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-22 Cont ID  
Sent By alange Date 2005-06-22 Time 13:19 Rev Time 1.75
Received By alange Date 2005-06-22 Time 11:39 Sent To  
Notes
2005-06-22 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SHOW FINISH FLOOR HEIGHT ABOVE
 GRADE.FBC 1804.1.7 WPB AMMENDMENTS
  
 4.SHOW DETAIL OF EXISTING FOOTINGS.
  
 5.PLANS SPECIFY PGT WINDOWS.OTHER
 MANUFATURERS PRODUCT APPROVALS HAVE BEEN
 SUBMITTED.PLEASE CLEARIFY.
  
 6.SUBMIT 2 COMPLETE SETS OF MIAMI-DADE
 PRODUCT APPROVALS.
 ALL PRODUCT APPROVALS SHALL HAVE THE
 FOLLOWING STATE APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7.SUBMIT TWO COPIES OF TABLE 600
 ENERGY CALCS.
  
 8.BUILDING VALUATION IS TOO LOW.
 REVISE VALUE AND PAY ADDITIONAL PERMIT
 FEES PRIOR TO RESUBMITTING PLANS.
 FBC 104.6.5
  
 9.ALL PAGE SHALL BE SIGNED AND SEALED
 BY ARCHITECT PER FAC481 AND 61G1-16.003
 FAC.
  
 10.SHOW EXISTING USE AND NEW USE FOR
 BUILDING.
  
 11.SHOW DISTANCES BETWEEN BUILDINGS
 AND LOCATION AND SIZES OF OPENINGS ON
 EACH BUILDING FACING ONE ANOTHER.
 THIS IS NEEDED SO I CAN CHECK COMPLIANCE
 WITH TABLE 600 OF THE FBC.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-31 Cont ID  
Sent By btrobaug Date 2005-05-31 Time 17:31 Rev Time 0.50
Received By btrobaug Date 2005-05-31 Time 17:08 Sent To P
Notes
2005-05-31 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT A RISER DIAGRAM INDICATING HOW
 THE 100 AMP PANELIS BEING FED, INCLUDE
 CONDUIT AND CONDUCTOR NUMBER AND SIZES.
  
 2} SHOW GROUNDING PER 250.32.
  
 3} ALL SHEETS DRAWN BY THE ARCHITECT
 MUST COMPLY WITH 481 FBC AND BE SEALED
 PER 61G1-16.003 FAC.
  
 4} INCREASE THE PERMIT VALUE TO INCLUDE
 ALL LABOR AND MATERIAL, ALSO DESIGN
 COSTS PER 104.6.5. GIVE THE UPDATED
 INFORMATION TO THE PERMIT CLERK ATB TIME
 OF RESUBMITTAL SO ADJUSTMENTS CAAN BE
 MADE IN THE FEES PRIOR TO REVIEWS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-27 Cont ID  
Sent By adarroug Date 2005-05-27 Time 09:54 Rev Time 0.00
Received By adarroug Date 2005-05-27 Time 09:54 Sent To E
Notes
2005-05-27 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-22 Cont ID  
Sent By alange Date 2005-06-22 Time 13:19 Rev Time 0.00
Received By alange Date 2005-05-19 Time 16:38 Sent To  
Notes
2005-05-19 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-06-13 Cont ID  
Sent By pkrauss Date 2005-06-13 Time 12:15 Rev Time 0.25
Received By pkrauss Date 2005-06-13 Time 12:01 Sent To B
Notes
2005-06-13 00:00:00PROVISO:
 EXHAUST FAN SHALL BE A MINIMUM OF 50 CFM
 PER 2001 FBC(M)TABLE 403.3.
  
 NO MECHANICAL CONTRACTOR INDICATED WITH
 PERMIT APPLLICATION.SEPARATE
 MECHANICAL PERMIT REQUIED FOR DUCTWORK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-06-07 Cont ID  
Sent By jleech Date 2005-06-07 Time 18:47 Rev Time 0.33
Received By jleech Date 2005-06-07 Time 18:47 Sent To M
Notes
2005-06-07 00:00:00NOT ENOUGH INFORMATION TO DO A PLUMBING
 PLAN REVIEW.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-05-26 Cont ID  
Sent By mmclean Date 2005-05-26 Time 15:47 Rev Time 0.00
Received By mmclean Date 2005-05-26 Time 15:47 Sent To I
Notes
2005-05-26 00:00:00PER MR. FARRIS, ALL THE WORK IS
 INTERIOR, FOOTPRINT OF STRUCTURE WILL
 NOT CHANGE.