Plan Review Details - Permit 05051272
Plan Review Stops For Permit 05051272
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-28 Cont ID  
Sent By jwitmer Date 2005-08-28 Time 07:07 Rev Time 0.44
Received By jwitmer Date 2005-08-28 Time 06:58 Sent To PC
Notes
2005-08-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051272
 ADD: 735 PALM ST
 CONT: POOLS, SPAS & BEYOND
 TEL: (561)722-9386
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 POOL RESTAMP
 BUILDING PROVISO:
  
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE
 PROVIDED WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH
 424.2.17.1.14.
 424.2.17.1.5 CHILD SAFETY BARRIER
  
 2)13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-07-07 Cont ID  
Sent By lsmith Date 2005-07-07 Time 17:01 Rev Time 0.00
Received By lsmith Date 2005-07-07 Time 17:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-08 Cont ID  
Sent By lsmith Date 2005-06-08 Time 16:29 Rev Time 0.50
Received By lsmith Date 2005-06-08 Time 16:29 Sent To  
Notes
2005-06-08 00:00:00BUILDING PLAN REVIEW: FAILED
  
  
 1.104.6.5 BUILDING PERMIT VALUATION.
 IF IN THE OPINION OF THE BUILDING
 OFFICIAL THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED ESTIMATES AND/OR BONA FIDED
 SIGNED CONTRACTS (EXCLUDING LAND VALUE)
 TO MEET THE APPROVAL OF THE BUILDING
 OFFICIAL. FOR PERMITTING PURPOSES,
 VALUATION FOR BUILDINGS AND SYSTEMS
 SHALL BE FOUND IN MARSHALL AND SWIFT OR
 THE SOUTHERN BUILDING CODE CONGRESS
 INTERNATIONAL VALUATION TABLES, LATEST
 EDITION, AND SHALL BE BASED ON TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, OVERHEAD AND PROFIT,
 EXCLUDING ONLY LAND VALUE.
  
 SUBMIT A SIGNED CONTRACT TO VERIFY VALUE
 OF POOL.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-08-25 Cont ID  
Sent By btrobaug Date 2005-08-25 Time 09:29 Rev Time 0.33
Received By btrobaug Date 2005-08-25 Time 09:13 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-08 Cont ID  
Sent By jleahy Date 2005-07-08 Time 09:40 Rev Time 0.30
Received By jleahy Date 2005-07-08 Time 09:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-22 Cont ID  
Sent By jleahy Date 2005-06-22 Time 21:57 Rev Time 0.30
Received By jleahy Date 2005-06-22 Time 21:57 Sent To P
Notes
2005-06-22 00:00:00WHAT SIZE IS THE BRANCH CIRCUIT THAT
 FEEDS THE POOL PANEL?
  
 WHAT SIZE WIRE WILL BE USED TO FEED POOL
 PANEL?
  
 WHAT SIZE BREAKER WILL BE USED TO FEED
 POOL PANEL?

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-31 Cont ID  
Sent By jleahy Date 2005-05-31 Time 13:16 Rev Time 0.45
Received By jleahy Date 2005-05-31 Time 13:16 Sent To P
Notes
2005-05-31 00:00:00NEED TO SHOW SIZE OF SERVICE
  
 NEED TO SHOW BRANCH CIRCUIT SIZE FEEDING
 POOL PANEL
  
 SHOW PANEL SCHEDULE FOR HOUSE PANEL
  
  
 JAKE LEAHY
  
 644-7291

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 12:23 Rev Time 0.00
Received By shill Date 2005-06-20 Time 12:23 Sent To E
Notes
2005-06-20 00:00:00TO JL DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-26 Cont ID  
Sent By adarroug Date 2005-05-26 Time 11:38 Rev Time 0.00
Received By adarroug Date 2005-05-26 Time 11:38 Sent To E
Notes
2005-05-26 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-19 Cont ID  
Sent By adarroug Date 2005-05-19 Time 10:54 Rev Time 0.00
Received By adarroug Date 2005-05-19 Time 10:54 Sent To Z
Notes
2005-05-19 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-08-25 Cont ID  
Sent By jleech Date 2005-08-25 Time 07:46 Rev Time 0.25
Received By jleech Date 2005-08-25 Time 07:46 Sent To E
Notes
2005-08-25 00:00:00RE-STAMP ON COPY OF PLANS FOR JOB.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-30 Cont ID  
Sent By jleech Date 2005-06-30 Time 10:10 Rev Time 0.50
Received By jleech Date 2005-06-30 Time 10:10 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-07 Cont ID  
Sent By jleech Date 2005-06-07 Time 17:45 Rev Time 0.75
Received By jleech Date 2005-06-07 Time 17:45 Sent To B
Notes
2005-06-07 00:00:00DENIED;
 POOL SCHMATIC SHOWS MORE EQUIPMENT AND
 PIPING THAN THE POOL DATA & EQUIPMENT &
 CRITERIA SHOWS. NO VAC LINE NO HEATER
 INFORMATION, AND ROSETTIES. MAIN DRAIN
 RELIEF VENTS ARE 1 1/2 OR 1'. PLEASE
 PROVIDE HEATER INFORMATION AND SHOW VAC
 LOCK TO BE USED.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-05-25 Cont ID  
Sent By mmclean Date 2005-05-25 Time 15:41 Rev Time 0.00
Received By mmclean Date 2005-05-25 Time 15:41 Sent To I
Notes
***NONE***