| 2005-07-18 00:00:00 | DENIED |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT TWO COMPLETE SETS OF PLANS. |
| | |
| | 4) SUBMIT TWO COPIES OF A SURVEY |
| | INDICATING THE LOCATION OF THE ADDITION |
| | AND DISTANCE TO PROPERTY LINES. |
| | |
| | 5) THE ORIGINAL WET SIGNATURE OF THE |
| | ENGINEER IS REQUIRED ON THE PLANS. |
| | SIGNATURE STAMPS ARE NOT ACCEPTABLE. SEE |
| | FAC 61G15-23.002. |
| | |
| | 6) SUBMIT TWO COPIES OF PRODUCT |
| | APPROVALS FOR WINDOWS, DOORS, GLASS |
| | BLOCK, ROOFING MATERIAL, STORM PANELS |
| | AND HURRICANE ANCHORS. PRODUCT APPROVALS |
| | SUBMITTED WITH PERMIT APPLICATION AFTER |
| | OCTOBER 1, 2003 ARE REQUIRED TO COMPLY |
| | WITH THE FLORIDA PRODUCT APPROVAL |
| | SYSTEM. FOR INFORMATION PLEASE SEE THE |
| | STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 7) SUBMIT TWO COPIES OF ENERGY CALCS. |
| | SIGNED BY OWNER/AGENT. THE INSULATION OF |
| | THE EXTERIOR MASONRY WALLS IS REQUIRED |
| | TO HAVE AN VALUE OF R-5. SEE TABLE 6B-1 |
| | WHICH REQUIRES ALL "TO BE INSTALLED" |
| | VALUES TO BE EQUAL TO OR MORE EFFICIENT |
| | THAN THE REQUIRED LEVELS. |
| | |
| | 8) UNDER DESIGN PARAMETERS ON SHEET 1 |
| | REVISE MINIMUM ROOF HEIGHT TO MEAN ROOF |
| | HEIGHT. |
| | |
| | 9) THE TOTAL ROOF DEAD LOAD HAS BEEN |
| | LEFT BLANK ON SHEET 1. |
| | |
| | 10) SPECIFY THE TRUSS BOTTOM CORD LIVE |
| | LOAD. SEE FBC TABLE 1604.1. |
| | |
| | 11) ON SHEET 1 REVISE INTERIOR PRESSURE |
| | COEFFICIENT TO INTERNAL PRESSURE |
| | COEFFICIENT AND ADD PLUS AND MINUS SIGNS |
| | TO INDICATE POSITIVE AND NEGATIVE |
| | PRESSURES. SEE ASCE 7-98 TABLE 6-7. |
| | |
| | 12) REVISE THE ROOF SHEATHING FASTENER |
| | SPACING TO COMPLY WITH CITY OF WPB |
| | AMENDMENTS TO FBC TABLE 2306.1, WHICH |
| | REQUIRES 4" OC AT THE EDGES AND 6" OC IN |
| | THE FIELD IN ZONE 3. |
| | |
| | 13) SPECIFY THE LOCATION AND SIZE OF THE |
| | ATTIC ACCESS ON THE PLANS. SEE FBC |
| | 2309.6. |
| | |
| | 14) SPECIFY THE SIZE OF THE SOFFIT |
| | SCREEN VENTS ON SHEET 6. SEE FBC |
| | 2309.7.1. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |