Plan Review Details - Permit 05051254
Plan Review Stops For Permit 05051254
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 16:49 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 16:49 Sent To M
Notes
2005-05-24 00:00:00TO "PKRAUSS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2005-05-20 Cont ID  
Sent By adarroug Date 2005-05-19 Time 11:35 Rev Time 1.00
Received By prafter Date 2005-05-20 Time 14:13 Sent To M
Notes
2005-05-20 00:00:00MECH. PLAN REVIEW:
  
 1. A/C PLAN TO VAGE AND QUESTIONS.
  
 2. WHAT SIZE IS R/A OUT OF ROOM #1?
  
 3. R/A OUT OF ROOM #8 ?
  
 4. R/A OUT OF ROOM #12 ?
  
 5. R/A OUT OF ROOM #11 REQUIRED TO BE
 9" FBC/M 601.4 EXCEPTION 1. .
 6. A/C GRILL REQUIRED CFM RATING .
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.
  
2005-05-19 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-06-28 Cont ID  
Sent By pkrauss Date 2005-06-28 Time 15:01 Rev Time 0.25
Received By pkrauss Date 2005-06-28 Time 13:46 Sent To  
Notes
2005-06-28 00:00:00AS BUILT DWG

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-05-30 Cont ID  
Sent By pkrauss Date 2005-05-30 Time 19:33 Rev Time 0.35
Received By pkrauss Date 2005-05-30 Time 19:26 Sent To  
Notes
2005-05-30 00:00:00PROVISO:
 PER 2001 FBC/M 601.4 EXCEPTION #2 & 3,
 TRANSFER GRILLES SHALL BE A MINIMUM OF
 50 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM OF SUPPLY AIR FOR THROUGH THE WALL
 TRANSFER GRILLES.ALL SUPPLY AIR INTO
 THE MASTER SUITE SHALL BE INCLUDED FOR
 PROPER SIZING OF THE RETURN AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.