Plan Review Details - Permit 05051234
Plan Review Stops For Permit 05051234
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-10-20 Cont ID  
Sent By jwitmer Date 2005-10-20 Time 10:42 Rev Time 0.77
Received By jwitmer Date 2005-10-20 Time 10:42 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-26 Cont ID  
Sent By jwitmer Date 2005-06-26 Time 12:30 Rev Time 1.77
Received By jwitmer Date 2005-06-26 Time 12:30 Sent To PC
Notes
2005-06-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051234
 ADD: 1665 PALM BEACH LAKES/ 700
 CONT: MJS CONSTR
 TEL: (561)722-1276
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3)412.6.2 OPENINGS IN THE ELEVATOR
 LOBBY SHALL BE LIMITED TO THOSE
 REQUIRED FOR ACCESS TO THE ELEVATORS AND
 FOR EGRESS FROM THE BUILDING.
 ALL ROOMS AND ENCLOSURES SHALL HAVE AT
 LEAST ONE REQUIRED EXIT ACCESSIBLE
 WITHOUT TRAVEL THROUGH THE ELEVATOR
 LOBBY.OPENINGS MAY BE PROVIDED WITH
 HORIZONTAL SLIDING DOORS CONFORMING TO
  
 4)1012.4.EXIT STAIRWAYS, CHUTES,
 JANITOR CLOSETS, GUEST ROOMS, SERVICE
 ROOMS, ETC., SHALL NOT OPEN INTO THE
 ELEVATOR LOBBY.
  
 5)412.6.3 EACH ELEVATOR LOBBY SHALL BE
 PROVIDED WITH AN APPROVED SMOKE
 DETECTOR LOCATED ON THE LOBBY CEILING.
 WHEN THE DETECTOR IS ACTIVATED,
 ELEVATOR DOORS SHALL NOT OPEN AND ALL
 CARS SERVING THAT LOBBY ARE TO RETURN TO
 THE MAIN FLOOR AND BE UNDER MANUAL
 CONTROL ONLY.IF THE MAIN FLOOR
 DETECTOR OR A TRANSFER FLOOR DETECTOR IS
 ACTIVATED, ALL CARS SERVING THE MAIN
 FLOOR OR TRANSFER FLOOR SHALL RETURN TO
 A LOCATION APPROVED BY THE FIRE
 DEPARTMENT AND BUILDING OFFICIAL AND BE
 UNDER MANUAL CONTROL ONLY.THE DETECTOR
 MAY SERVE TO CLOSE THE LOBBY DOORS.
  
 5) DOOR INTO OFFICE 725 DOESN'T MEET:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 6) UPDATE OR CHANGE SCOPE OF WORK ON THE
 PERMIT APPLICATION TO REFLECT WORK ON
 THE WHOLEOF THE 7TH FLOOR NOT JUST
 SIUTE 700.IF WORK IS TO BE COMPLETED
 UNDER THIS PERMIT IS ONLY SUITE 700 ALL
 OTHER WORK AREAS WILL BE STRUCK OFF THE
 PLANS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-28 Cont ID  
Sent By jleahy Date 2005-11-28 Time 07:05 Rev Time 0.45
Received By jleahy Date 2005-11-28 Time 07:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-21 Cont ID  
Sent By dpalmer Date 2005-09-21 Time 20:24 Rev Time 0.33
Received By dpalmer Date 2005-09-21 Time 20:18 Sent To  
Notes
2005-09-21 00:00:00REVISED ELECTRICAL SHEETS FOR FIRE
 COMMENTS.
  
 SHEETS NOW INCLUDE MORE OF EXISTING
 ELECTRICAL PANELS/SERVICE FOR SPACE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-06-06 Cont ID  
Sent By dpalmer Date 2005-06-06 Time 15:41 Rev Time 0.50
Received By dpalmer Date 2005-06-06 Time 15:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-28 Cont ID  
Sent By mwennerg Date 2005-09-28 Time 15:30 Rev Time 0.00
Received By mwennerg Date 2005-09-28 Time 15:30 Sent To  
Notes
2005-09-28 00:00:00******OK******
  
 PLEASE SEE DOOR MISSING FROM OFFICE 716.
 SHT A1.1 RED LINED ON PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-06-09 Cont ID  
Sent By mwennerg Date 2005-06-09 Time 15:51 Rev Time 0.00
Received By mwennerg Date 2005-06-09 Time 15:32 Sent To  
Notes
2005-06-09 00:00:00SEPARATE SHOP DRAWINGS AND PERMITS ARE
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-28 Cont ID  
Sent By adarroug Date 2006-01-28 Time 16:16 Rev Time 0.00
Received By adarroug Date 2006-01-28 Time 16:16 Sent To M
Notes
2006-01-28 00:00:00TO "HMOSER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-22 Cont ID  
Sent By adarroug Date 2005-11-22 Time 10:28 Rev Time 0.00
Received By adarroug Date 2005-11-22 Time 10:28 Sent To  
Notes
2005-11-22 00:00:00TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-14 Cont ID  
Sent By adarroug Date 2005-09-14 Time 14:46 Rev Time 0.00
Received By adarroug Date 2005-09-14 Time 14:46 Sent To  
Notes
2005-09-14 00:00:00TO "COMM" BD#20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-26 Cont ID  
Sent By jwitmer Date 2005-06-26 Time 12:31 Rev Time 0.00
Received By jwitmer Date 2005-05-20 Time 14:20 Sent To PC
Notes
2005-06-06 00:00:00TO COMM BD#6
2005-05-20 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-01-30 Cont ID  
Sent By hmoser Date 2006-01-30 Time 08:47 Rev Time 0.00
Received By hmoser Date 2006-01-30 Time 08:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-11-28 Cont ID  
Sent By hmoser Date 2005-11-28 Time 14:08 Rev Time 0.00
Received By hmoser Date 2005-11-28 Time 14:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-10-18 Cont ID  
Sent By hmoser Date 2005-10-18 Time 09:47 Rev Time 0.00
Received By hmoser Date 2005-10-18 Time 09:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-06-21 Cont ID  
Sent By hmoser Date 2005-06-21 Time 14:06 Rev Time 0.00
Received By hmoser Date 2005-06-21 Time 13:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-10-18 Cont ID  
Sent By pschmitz Date 2005-10-18 Time 08:41 Rev Time 0.00
Received By pschmitz Date 2005-10-18 Time 08:40 Sent To  
Notes
2005-10-18 00:00:00RE SUB

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-20 Cont ID  
Sent By pschmitz Date 2005-06-20 Time 13:34 Rev Time 0.00
Received By pschmitz Date 2005-06-20 Time 13:34 Sent To FIRE
Notes
2005-06-20 00:00:00PLUMBING PLAN REVIEW DENIED
 FBC 2001 FABC, CH 11 SEC.4.23.2
 (1) SHT A1.1 REST RM #760.
 DOORS SHALL NOT SWING INTO THE FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
 END OF COMMENTS.
 QUESTIONS PAUL SCHMITZ 561-8056692