Plan Review Details - Permit 05051168
Plan Review Stops For Permit 05051168
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-28 Cont ID  
Sent By jwitmer Date 2005-08-28 Time 12:14 Rev Time 0.55
Received By jwitmer Date 2005-08-28 Time 12:14 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-21 Cont ID  
Sent By jwitmer Date 2005-06-21 Time 08:00 Rev Time 0.00
Received By jwitmer Date 2005-06-21 Time 08:00 Sent To  
Notes
2005-06-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051168
 ADD: 4905 N FLAGLER DR
 CONT: JANSSEN CONSTRUCTION
 TEL: (561)718-4222
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PLANS DO NOT INDICATE WHICH WINDOWS
 ARE TO BE REPLACED, THESE ARE CONCERNS
 FOR,
 2A) WINDOWS AT EXTERIOR STAIRS:
 1006.2.4 EXTERIOR STAIRS SHALL BE
 SEPARATED FROM THE INTERIOR OF THE
 BUILDING BY WALLS WITH A FIRE
 RESISTANCE RATING OF NOT LESS THAN 1
 HOUR,WITH FIXED OR SELF-CLOSING
 OPENING PROTECTIVES AS REQUIRED FOR
 ENCLOSEDSTAIRS.THIS PROTECTION
 SHALL EXTEND VERTICALLY FROM THE GROUND
 TO A POINT 10 FT (3048 MM) ABOVE THE
 TOPMOST LANDING OR THE ROOF LINE,
 WHICHEVER IS LOWER, AND HORIZONTALLY 10
 FT (3048 MM) FROM EACH SIDE OF
 THE STAIRWAY.OPENINGS WITHIN THE 10 FT
 (3048 MM) HORIZONTAL EXTENSION
 OF THE PROTECTED WALLS BEYOND THE
 STAIRWAY SHALL BE EQUIPPED WITH FIXED
 3/4 HOUR ASSEMBLIES.
 2B) BEDROOMS : 1005.4.3 MAXIMUM HEIGHT
 FROM FLOOR. THE EMERGENCY ESCAPE AND
 RESCUE OPENING SHALL HAVE A SILL HEIGHT
 OF NOT MORE THAN 44 INCHES (1118 MM)
 ABOVE THE FLOOR.
 1005.4.4 MINIMUM SIZE. THE MINIMUM NET
 CLEAR OPENING HEIGHT DIMENSION
 SHALL BE 24 INCHES (610 MM).THE
 MINIMUM NET CLEAR OPENING WIDTH
 DIMENSION SHALL BE 20 INCHES (508 MM).
 THE MINIMUM NET CLEAR OPENING
 AREA SHALL BE 5.7 SQ FT (0.53 M^2).
 EXCEPTION: GROUND FLOOR OPENINGS
 SHALL BE PERMITTED TO HAVE A MINIMUM
 NET CLEAR OPENING OF 5.0 SQ FT (0.47
 M^2).
  
 3)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) DOORS
 C) STORM SHUTTERS
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4)3401.7.2.4 THE REPLACEMENT OF GARAGE
 DOORS, EXTERIOR DOORS,
 SKYLIGHTS, OPERATIVE AND INOPERATIVE
 WINDOWS SHALL BE DESIGNED &
 CONSTRUCTED TO COMPLY WITH CHAPTER 16 OF
 THIS CODE.
  
 OPENING PROTECTION EXCEPTION: FOR ONE-
 AND TWO-FAMILY DWELLINGS CONSTRUCTED
 UNDER CODES OTHER THAN THE FLORIDA
 BUILDING CODE AND LOCATED IN WINDBORNE
 DEBRIS REGIONS, THE REPLACEMENT OF
 GARAGE DOORS AND EXTERIOR DOORS WITH
 GLAZING, SLIDING GLASS DOORS, GLASS
 PATIODOORS, SKYLIGHTS, AND OPERABLE
 AND INOPERABLE WINDOWS WITHIN ANY 12
 MONTH PERIOD SHALL NOT BE REQUIRED TO
 HAVE OPENING PROTECTION, BUT SHALL BE
 DESIGNED FOR WIND PRESSURES FOR ENCLOSED
 BUILDINGS PROVIDED THE AGGREGATE AREA OF
 THE GLAZING IN THE REPLACED COMPONENTS
 DOES NOT EXCEED 25 PERCENT OF THE
 AGGREGATE AREA OF THE GLAZED OPENINGS IN
 THE DWELLING OR DWELLING UNIT.
  
 5) 905.2.1 APPROVED SINGLE-STATION OR
 MULTIPLE STATION SMOKE DETECTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 72,
 CHAPTER 2, WITHIN EVERY DWELLING UNIT
 WITHIN AN APARTMENT HOUSE, CONDOMINIMUM,
 OR TOWNHOUSE AND EVERY GUEST OR SLEEPING
 ROOM IN A MOTEL, HOTEL, OR DORMITORY &
 SLEEPING ROOMS IN RESIDENTIAL CARE/
 ASSISTED LIVING OCCUPANCIES. WHERE MORE
 THAN ONE DETECTOR IS REQUIRED TO BE
 INSTALLED WITHIN INDIVIDUAL DWELLING
 UNIT, THE DETECTOR SHALL BE WIRED IN
 SUCH A MANNER THAT THE ACTUATION OF ONE
 ALARM WILL ACTIVATE ALL THE ALARMS IN
 THE INDIVIDUAL UNIT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
2005-06-02 00:00:00TO "COMM" BD#10

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-10 Cont ID  
Sent By jleahy Date 2005-11-10 Time 19:26 Rev Time 0.45
Received By jleahy Date 2005-11-10 Time 19:22 Sent To  
Notes
2005-11-10 00:00:00SEE PLANS FOR NOTES
  
 1) A/C DISC. AND SERVIE DISC TO MEET
 110.26.
  
 2) RISER DIAGRAM SHOWS 100/3 POLE
 DISC.
  
 3) SMOKE DETECTOR NOT SHOWN IN BDRM.S
  
 4) SERVICE AND HOUSE PANEL LOCATION
 NOT SHOWN.
  
  
 JAKE LEAHY11/10/05

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-19 Cont ID  
Sent By dpalmer Date 2005-08-19 Time 19:05 Rev Time 0.50
Received By dpalmer Date 2005-08-19 Time 19:04 Sent To  
Notes
2005-08-19 00:00:00*** REDLINED****
  
  
 1) EXISTING GROUNDING ELECTRODE SYSTEM
 TO BE VIF.
 2) PLEASE SEE DINING RM RECEPTS TO BE
 CIRCUITED TO SMALL APPLIANCE CIRCUIT.
 210.52B1
 3)A/C DISC'S TO MEET 110.26

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-06 Cont ID  
Sent By dpalmer Date 2005-06-06 Time 13:40 Rev Time 0.75
Received By dpalmer Date 2005-06-06 Time 13:40 Sent To  
Notes
2005-06-06 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL
 SCHEDULE(S).
 215.5
  
 2)NOTE: PLEASE SEE 210.12 2002 NEC FOR
 ARC FAULT PROTECTION FOR "ALL OUTLET" IN
 BEDRMS INCLUDING SD'S.
  
 3)NOTE: PLEASE INCLUDE CONDUCTOR SIZES
 AND OCP ON PANEL SCHEDULE.
 ALLL MUST MEET 2002 NEC,
 210.11C1,C3,424.3B,22
 PLEASE CORRELATE PANEL SCHEDULE WITH
 ITEMS SHOWN ON LOAD CALCULATIONS.
 215.5
  
 4)NOTE: PLEASE CLARIFY NEW OR EXISTING
 ELECTRICAL RISER SHOWN. IF NEW PLEASE
 COMPLETE RISER . SEC'S, CONDUITS, MAINS,
 OCP, AIC RATINGS, GROUNDING, ETC.
 110.9,250.50,310.16,240.3,,
  
 5)NOTE: PLEASE SEE RISER SHOWS ONE SUB
 PANEL? IS THIS HOUSE POWER? IS THIS THE
 PANEL TYPICAL FOR EACH UNIT?
 215.5
  
 6)NOTE: PLEASE SHOW PANEL LOCATIONS IN
 UNITS.
 215.5
  
 7)NOTE: PLEASE SHOW LOCATIONS OF ALL
 DISC'S FOR A/C EQUIPMENT.440.11
 PLEASE ALSO INLCUDE RECEPTS PER 210.63
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-06-15 Cont ID  
Sent By mwennerg Date 2005-06-15 Time 13:23 Rev Time 0.00
Received By mwennerg Date 2005-06-15 Time 13:04 Sent To  
Notes
2005-06-15 00:00:00****PROVISO****
  
 1) IT APPEARS THAT THE DOOR SWINGS AT
 THE SECOND LEVEL LIVING ROOMS COULD
 CAUSE A POTENTIAL EGRESS PROBLEM IF BOTH
 UNITS ARE EVACUATING AT THE SAME TIME.
 CAN THIS ARRANGEMENT BE MODIFIED?
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 3) ACTIVATION OF ONE SMOKE DETECTOR WILL
 CAUSE ALL SMOKE DETECTORS TO OPERATE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-18 Cont ID  
Sent By adarroug Date 2005-08-18 Time 17:09 Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 17:09 Sent To  
Notes
2005-08-18 00:00:00TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-21 Cont ID  
Sent By jwitmer Date 2005-06-21 Time 07:03 Rev Time 0.00
Received By jwitmer Date 2005-05-17 Time 16:47 Sent To  
Notes
2005-05-17 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-06-20 Cont ID  
Sent By hmoser Date 2005-06-20 Time 14:30 Rev Time 0.00
Received By hmoser Date 2005-06-20 Time 14:18 Sent To  
Notes
2005-06-20 00:00:00PASS PROVISO
 REFER TO SECTION 601.4 BALANCED RETURN
 AIR.2001 MECHANICAL CODE.MARKED ON PLAN.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-20 Cont ID  
Sent By pschmitz Date 2005-06-20 Time 14:12 Rev Time 0.00
Received By pschmitz Date 2005-06-20 Time 14:12 Sent To M
Notes
2005-06-20 00:00:00REPLACE PLUMBING FIXTURES ONLY.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved