Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-07-07 Cont ID  
Sent By jgomez Date 2005-07-07 Time 15:00 Rev Time 0.33
Received By jgomez Date 2005-07-07 Time 15:00 Sent To  
Notes
2005-07-07 00:00:00FLAT ROOF SYSTEM REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-06-14 Cont ID  
Sent By mjacobs Date 2005-06-14 Time 14:19 Rev Time 0.50
Received By mjacobs Date 2005-06-14 Time 14:19 Sent To PC
Notes
2005-06-14 00:00:001) THE INFORMATION SUBMITTED IS
 INCOMPLETE.PROVIDE A COMPLETE TYPE OF
 SYSTEM TO BE USED SHOWIN THE PRESSURES
 AND GENERAL LIMITATIONS.
  
 2) FBC 1606.2.5THE SYSTEM SELECTED
 FROM THE SUBMITTED FLAT ROOF PRODUCT
 APPROVAL NOA HAS A MAXIMUM DESIGN
 PRESSURE OF LESS THAN -89 PSF AND CITES
 GENERAL LIMITATION #9.GENERAL
 LIMITATION #9 PROHIBITS RATIONAL
 ANALYSIS OR EXTRAPOLATION TO ENHANCE THE
 UPLIFT PRESSURE AT PERIMETER AND CORNER
 AREAS BY REDUCING THE FASTENER SPACING
 IN THESE AREAS.EITHER SELECT AN
 ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL)
 THAT DOES NOT CITE GENERAL LIMITATION
 #9.ALTERNATIVELY IF THE SELECTED
 SYSTEM DOES CITE GENERAL LIMITATION #9,
 IT MUST HAVE A MAXIMUM DESIGN PRESSURE
 THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3
 (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT
 OF 30 FEET OR LESS).
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-05-17 Cont ID  
Sent By jgomez Date 2005-05-17 Time 08:02 Rev Time 0.25
Received By jgomez Date 2005-05-17 Time 08:02 Sent To PC
Notes
***NONE***