Plan Review Details - Permit 05051113
Plan Review Stops For Permit 05051113
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-26 Cont ID  
Sent By jwitmer Date 2005-08-26 Time 16:19 Rev Time 0.55
Received By jwitmer Date 2005-08-26 Time 16:05 Sent To PC
Notes
2005-08-26 00:00:00REVISIONSOKJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-07-19 Cont ID  
Sent By jwitmer Date 2005-07-19 Time 18:02 Rev Time 0.55
Received By jwitmer Date 2005-07-19 Time 17:50 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-17 Cont ID  
Sent By jwitmer Date 2005-06-17 Time 15:34 Rev Time 1.11
Received By jwitmer Date 2005-06-17 Time 15:33 Sent To  
Notes
2005-06-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051113
 ADD: 515 N FLAGLER DR # 800
 CONT: BORAN, CRAIG,BBARBER, ENGELS
 TEL: (239)293-6822
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) FL S S 471.025/ FAC 61G15-23.002
 PLANS ARE TO BE DATED, WHEN SIGNING &
 SEALING FOR PUBLIC RECORD.
  
 2) SHEET A-2 INDICATES THE USE OF WOOD
 BUCKS, TYPE I & II BUILDINGS INTERIOR
 WALLS NON-COMBUSTIBLE SEE 604.
  
 3) THE EXISTING KITCHEN INSWING DOOR ;
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-08-11 Cont ID  
Sent By dpalmer Date 2005-08-11 Time 18:41 Rev Time 0.50
Received By dpalmer Date 2005-08-11 Time 18:41 Sent To  
Notes
2005-08-11 00:00:00REDLINED
 2002 NEC
 USED PENCIL TO SHADOW ENGINEER'S SEAL AS
 IT IS NOT CLEAR AND VISBLE ON FRONT OF
 EACH SHEET.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-11 Cont ID  
Sent By dpalmer Date 2005-07-11 Time 16:36 Rev Time 0.30
Received By dpalmer Date 2005-07-11 Time 16:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-06 Cont ID  
Sent By dpalmer Date 2005-06-06 Time 13:02 Rev Time 0.25
Received By dpalmer Date 2005-06-06 Time 12:25 Sent To  
Notes
2005-06-06 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE ALL PLANS MUST BE
 ALSO BE DATED WHEN SIGNING AND SEALING.
 FS 471.025/FAC 61G15-23.002
  
 THIS IS FOR A AND E SHEETS.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-18 Cont ID  
Sent By mwennerg Date 2005-08-18 Time 13:02 Rev Time 0.00
Received By mwennerg Date 2005-08-18 Time 13:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-06-07 Cont ID  
Sent By mwennerg Date 2005-06-07 Time 15:00 Rev Time 0.00
Received By mwennerg Date 2005-06-07 Time 15:00 Sent To  
Notes
2005-06-07 00:00:00****PROVISO****
  
 1) PLEASE NOTE OTHER REVIEW IN REGARDS
 TO FS AND FAC REQUIREMENTS.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL IF APPLICABLE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 10:56 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 10:56 Sent To M
Notes
2005-09-01 00:00:00TO "PKRAUSS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-08 Cont ID  
Sent By adarroug Date 2005-08-08 Time 11:04 Rev Time 0.00
Received By adarroug Date 2005-08-08 Time 11:04 Sent To  
Notes
2005-08-08 00:00:00TO "COMM" BD#42

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-25 Cont ID  
Sent By adarroug Date 2005-07-25 Time 15:15 Rev Time 0.00
Received By adarroug Date 2005-07-25 Time 15:15 Sent To M
Notes
2005-07-25 00:00:00TO "M' BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-05 Cont ID  
Sent By adarroug Date 2005-07-05 Time 13:10 Rev Time 0.00
Received By adarroug Date 2005-07-05 Time 13:10 Sent To  
Notes
2005-07-08 00:00:00TO "COMM" BD#6
2005-07-05 00:00:00WAITING FOR SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-23 Cont ID  
Sent By pkrauss Date 2005-06-23 Time 12:59 Rev Time 0.00
Received By pkrauss Date 2005-05-19 Time 09:13 Sent To  
Notes
2005-05-27 00:00:00TO "COMM" BD#61
2005-05-19 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pkrauss Date 2005-09-01 Time 11:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-08-01 Cont ID  
Sent By rregueir Date 2005-08-01 Time 18:40 Rev Time 0.00
Received By rregueir Date 2005-08-01 Time 18:40 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-07-19 Cont ID  
Sent By hmoser Date 2005-07-19 Time 17:04 Rev Time 0.00
Received By hmoser Date 2005-07-19 Time 16:51 Sent To  
Notes
2005-07-19 00:00:00PLAN DENIED
 PLEASE PROVIDE MORE INFORMATION ON THE
 PLANS.WHAT GRILLS ARE RECEIVING
 DAMPERS.WHAT SIZE DAMPERS.PLEASE SHOW ON
 THE PLANS LOCATION AND SIZE OF BOOT
 PLENUMS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-06-23 Cont ID  
Sent By pkrauss Date 2005-06-23 Time 12:56 Rev Time 0.25
Received By pkrauss Date 2005-06-23 Time 12:55 Sent To  
Notes
2005-06-23 00:00:00NO MECHANICAL CONTRACTOR OR WORK
 INDICATED WITH BUILDING PERMIT
 APPLICATION.PLEASE PROVIDE PLANS AND
 OUTSIDE AIR CALCULATIONS WITH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.