Plan Review Details - Permit 05051094
Plan Review Stops For Permit 05051094
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-11-09 Cont ID  
Sent By lmartine Date 2005-11-09 Time 11:22 Rev Time 0.00
Received By lmartine Date 2005-11-09 Time 11:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-16 Cont ID  
Sent By alange Date 2005-08-16 Time 13:21 Rev Time 1.50
Received By alange Date 2005-08-16 Time 10:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-12 Cont ID  
Sent By alange Date 2005-08-12 Time 12:34 Rev Time 2.00
Received By alange Date 2005-08-12 Time 08:19 Sent To E
Notes
2005-08-12 00:00:00DENIED
  
 1. 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 3.BUILDING IS IN FLOOD ZONE "A".
 SHOW THAT THE MINIMUM BASE FLOOD
 ELEVATION IS 7 FT. AND THE MINIMUM
 FINISH FLOOR HEIGHT IS 6" ABOVE THAT.
  
 4.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR SLOPED ROOF, STRAPS AND
 TIEDOWNS AND SKYLIGHT
 ** ALL MIAMI-DADE PRODUCT APPROVALS
 REQUIRE THE FOLLOWING TO BE ATTACHED**
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-20 Cont ID  
Sent By alange Date 2005-06-20 Time 15:25 Rev Time 1.50
Received By alange Date 2005-06-20 Time 14:49 Sent To  
Notes
2005-06-20 00:00:00DENIED
  
 1. 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 2.BUILDING IS IN AN AREA OF
 QUESTIONABLE SOILS.SUBMIT A SOILS
 REPORT SHOWING RECOMMENDATIONS FOR
 FOOTINGS.
  
 3.BUILDING IS IN FLOOD ZONE "A".
 SHOW THAT THE MINIMUM BASE FLOOD
 ELEVATION IS 7 FT. AND THE MINIMUM
 FINISH FLOOR HEIGHT IS 6" ABOVE THAT.
  
 4.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR FLAT ROOF, SLOPED ROOF,
 STRAPS AND TIEDOWNS.
 ** ALL MIAMI-DADE PRODUCT APPROVALS
 REQUIRE THE FOLLOWING TO BE ATTACHED**
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-07 Cont ID  
Sent By btrobaug Date 2005-11-07 Time 11:55 Rev Time 0.50
Received By btrobaug Date 2005-11-07 Time 11:17 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-15 Cont ID  
Sent By btrobaug Date 2005-08-15 Time 16:29 Rev Time 0.33
Received By btrobaug Date 2005-08-15 Time 16:14 Sent To B
Notes
2005-08-15 00:00:00 
 TO LUIS DESK./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-06-01 Cont ID  
Sent By btrobaug Date 2005-06-01 Time 13:22 Rev Time 0.75
Received By btrobaug Date 2005-06-01 Time 12:12 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-14 Cont ID  
Sent By adarroug Date 2005-10-14 Time 11:14 Rev Time 0.00
Received By adarroug Date 2005-10-14 Time 11:14 Sent To Z
Notes
2005-10-14 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 11:39 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 11:39 Sent To B
Notes
2005-08-09 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-25 Cont ID  
Sent By adarroug Date 2005-05-25 Time 15:05 Rev Time 0.00
Received By adarroug Date 2005-05-25 Time 15:05 Sent To E
Notes
2005-05-25 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-20 Cont ID  
Sent By alange Date 2005-06-20 Time 15:25 Rev Time 0.00
Received By alange Date 2005-05-18 Time 15:46 Sent To  
Notes
2005-05-18 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-06-15 Cont ID  
Sent By hmoser Date 2005-06-15 Time 14:40 Rev Time 0.00
Received By hmoser Date 2005-06-15 Time 14:40 Sent To B
Notes
2005-06-15 00:00:00NO PLANS HAVE AIRCONDITIONING CONTRACTOR
 SUBMIT PLANS WITH APPLICATION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-06-13 Cont ID  
Sent By pkrauss Date 2005-06-13 Time 16:07 Rev Time 0.30
Received By pkrauss Date 2005-06-13 Time 16:07 Sent To B
Notes
2005-06-13 00:00:00PROVISO:
 MANUFACTURER'S INSTALLATION INSTRUCTIONS
 DOES NOT INDICATE REQUIRED DISTANCES
 FROM THE BUILDING AND FRESH AIR INTAKES
 I.E., DOORS, WINDOWS, GRILLES IN
 SOFFITS.LOCATION SHALL COMPLY FBC(M)
 804.3.4, & 804.3.5.
  
 SEPARATE GAS PERMIT REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-16 Cont ID  
Sent By jleech Date 2005-08-16 Time 15:02 Rev Time 0.25
Received By jleech Date 2005-08-16 Time 15:02 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-04 Cont ID  
Sent By jleech Date 2005-06-04 Time 12:31 Rev Time 0.25
Received By jleech Date 2005-06-04 Time 12:31 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2006-08-07 Cont ID  
Sent By mmclean Date 2006-08-07 Time 14:14 Rev Time 0.00
Received By mmclean Date 2006-08-07 Time 14:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2005-11-02 Cont ID  
Sent By mmclean Date 2005-11-02 Time 14:31 Rev Time 0.00
Received By mmclean Date 2005-11-02 Time 14:31 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-16 Cont ID  
Sent By lmartine Date 2005-08-16 Time 16:37 Rev Time 0.00
Received By lmartine Date 2005-08-16 Time 16:36 Sent To  
Notes
2005-08-16 00:00:00OK PER MICHELLE

Review Stop Z ZONING
Rev No 1 Status P Date 2005-05-24 Cont ID  
Sent By mmclean Date 2005-05-24 Time 11:15 Rev Time 0.00
Received By mmclean Date 2005-05-24 Time 11:15 Sent To I
Notes
***NONE***