| 2005-05-16 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | |
| | 1- PRODUCT APPROVAL SUBMITTED WAS |
| | REVISED FROM ONE SUBMITTED AT TIME OF |
| | BLDG PERMIT APPLICATION. PRODUCT |
| | APPROVAL SUBMITTED AT THAT TIME WAS |
| | APPROVED BECAUSE IT WAS GOOD FOR UP TO |
| | -92PSF MAX. DESIGN PRESSURE. PRODUCT |
| | APPROVAL SUBMITTED NOW IS GOOD FOR UP TO |
| | -57PSF DESIGN PRESSURE. ACCORDING TO |
| | TABLE 1606.2B FLORIDA BUILDING CODE 2001 |
| | ROOF ZONES 2 AND 3 NEED TO RESIST |
| | PRESSURES TO -68.1PSF. PRODUCT APPROVAL |
| | SUBMITTED IS GOOD UP TO -57.5 PSF DESIGN |
| | PRESSURE. |
| | SYSTEM LIMITATIONS ON PAGE 5 OF 5 OF |
| | PRODUCT APPROVAL SAYS THAT FASTENING |
| | ENHANCING BY RATIONAL ANALYSIS TO BE |
| | DONE BY ENGINEER, ARCHITECT OR |
| | REGISTERED ROOF CONSULTANT. PROVIDE |
| | RATIONAL ANALYSIS AS REQUIRED. |
| | |
| | 2- POLYSTICK UNDERLAYMENT IS DESIGNED |
| | FOR TILE UNDERLAYMENT, NOT METAL. SEE |
| | POLYSTIC PRODUCT DESCRIPTION. |
| | SEE METAL ROOF SYSTEM PRODUCT APPROVAL |
| | FOR REQUIRED UNDERLAYMENT. |
| | |