| 2005-08-03 00:00:00 | IN ELEC FOR REVIEW |
| | ********* UNSAT 2ND REVIEW ********* |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE; PLEASE CORRELATE ELECTRICAL SITE |
| | PLAN WITH ELECTRICAL RISER DIAGRAM'S |
| | SUBMITTED. |
| | PLEASE SEE MAINT BLDG ON PLANS INDICATES |
| | A "PROPOSED MAIN", THIS WAS LOCATED ON |
| | RISER AND SEEMS TO BE THE NEW MAIN |
| | REPLACING EXSITNG ATS?, HOWEVER PLEASE |
| | SEE SITE PLAN FOR MAINT BLDG ALSO |
| | INDICATES A NEW "PROPOSED ATS" WHICH |
| | COULD NOT BE LOCATED ON RISER DIAGRAM |
| | FOR "MAINT BLDG". PLEASE SEE THE ONLY |
| | NEW PROPOSED ATSSWITCH SHOWN ON RISER |
| | INDICATES THIS ATS AT PBSO SUB STATION E |
| | EXTERIOR WALL. |
| | IF NEW ATS IS AT SUB STATION, PLEASE |
| | VERIFY IF MDP( NOT ON SITE PLAN) |
| | CONTAINS A MCB. PLEASE SEE IT WAS NOTED |
| | ON PREVIOUS REVIEW AND MAIN DISCONNECT |
| | WILL BE REQUIRED AT PBSO SUB-STATION, |
| | SHALL BE SERVICE ENTRANCE RATED AND |
| | GROUPED.225.31,225.34,225.36. |
| | PLEASE SEE NOTE ON LOWER RIGHT-HAND SIDE |
| | OF E-1 INDICATES, SHEET FOR INFORMATION |
| | ONLY" AND "ALL ELECTRICAL WORK SHOWN ON |
| | E-1 SHALL BE UNDER A SEPARATE PROJECT?? |
| | PLEASE CALRIFY, AS THIS PERMIT |
| | APPLICATION IS FOR THE NEW WORK AS |
| | SUBMITTED AND SHOWN ON RISER? |
| | PLEASE ALSO SEE A NOTE ON E-1 MENTIONS |
| | FOR A SIGN TO BE PROVIDED FOR GEN |
| | LOCATION, HOWEVER THIS NOTE MENTIONS GEN |
| | SHALL BE LOCATED IN AN INTERIOR ROOM |
| | LOCATED IN THE SW CORNER OF BLDG.?? |
| | PLEASE SEE NEW GEN IS HOWN ON SITE PLAN |
| | AT MAINT BLDG? |
| | IS THERE "TWO GEN'S, ONE EXISTING , ONE |
| | NEW? IF SO PLEASE SEE RISER AND SHOW ALL |
| | EXISTING AND PROPOSED. |
| | SITE PLANS SHOW "EXISTING " FEED TO |
| | MAINT BLDG BEING ABANDONED? |
| | PLEASE CALRIFY AND CORRELATE. PLEASE SEE |
| | A TYPED WRITTEN RESPONSE LETTER TO |
| | COMMENTS WOULD HELP IN ANY |
| | CLARIFICATIONS. |
| | |
| | 2)NOTE: PLEASE SEE PREVIOUS NOTE WHICH |
| | REQUESTED SPECS/MANUFACTURE SHEETS FOR |
| | ATS AND GEN. PLEASE SEE SHEET FOR ATS |
| | WERE SUBMITTED, HOWEVER, NONE FOR GEN |
| | COULD BE LOCATED, ONLY A LTR WHICH |
| | MENTIONED GEN SHALL BE RE-BUILT. |
| | PLEASE SEE FUEL TANK SUBMITTIALS ARE NOT |
| | CLEAR AS ONE SHEET MENTIONS A DIESEL GEN |
| | AND YET, NEW SHEET MENTIONS NEW GEN TO |
| | BE GAS? |
| | PLEASE CORRELATE. |
| | |
| | 3)NOTE: PLEASE SEE RISER SHOWS A NEW |
| | 170KW GEN? SITE PLANS MENTIONS A NEW |
| | 175KW GEN? PLEASE SEE RISER DOES NOT |
| | INDICATE ANY 175 KW GEN. |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE VALUE FOR SCOPE PF |
| | WORK WAS NOT INCREASED BY CONTRACTOR. IF |
| | VALUEIS NOT ADJUSTED BY CONTRACTOR FOR |
| | ALL WORK AND MATERIALS, A VALUE WILL BE |
| | APPLIED. PLEASE SEE EVEN IF EQUIPMENT IS |
| | OWNER SUPPLIED THE PERMIT FEE IS BASED |
| | ON TOTAL IMPROVEMENT. |
| | ADIMINSTRATIVE FBC 104.6.5 LOCAL ADMIN |
| | AMENDMENTS. |
| | |
| | 5)NOTE: PLEASE SEE ORIGINAL PERMIT |
| | APPLICATION WAS NOT SUBMITTED BACK WITH |
| | PACKAGE. PLEASE SEE ONLY A PHOTO-COPY OF |
| | FRONT WAS SUBMITTED. PLEASE SEE PACKAGE |
| | MUST CONTAIN SHEET WITH CONTRACTORS |
| | SIGNATURE AND MUST BE ORIGINAL. |
| | PLEASE SEE BLDG REVIEW COMMENTS FOR |
| | THIS. |
| | |
| | 6)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONAL. PLEASE SEE THIS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | ONE SET OF ELECTRICAL SHEETS ARE BEING |
| | RETAINED FOR FILE. |
| | |
| | PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | SHEETS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |