Plan Review Details - Permit 05051034
Plan Review Stops For Permit 05051034
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-07 Cont ID  
Sent By jwitmer Date 2005-08-07 Time 08:00 Rev Time 0.33
Received By jwitmer Date 2005-08-07 Time 07:47 Sent To  
Notes
2005-08-07 00:00:00PLANS REVIEWED & STAMPEDJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-17 Cont ID  
Sent By jwitmer Date 2005-06-17 Time 15:51 Rev Time 1.11
Received By jwitmer Date 2005-06-17 Time 15:51 Sent To  
Notes
2005-06-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05051034
 ADD: 8130 N JOG RD
 CONT: HOLT
 TEL: (954)755-7200
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 2) PROVIDE ADDITIONAL INFORMATION IN
 REGUARDS TO ANCHORING OF THE GENERATOR
 TO THE SLAB.1606.1.3 ANCHORAGE AGAINST
 OVERTURNING, UPLIFT AND SLIDING.
 STRUCTURALMEMBERS AND SYSTEMS, AND
 COMPONENTS AND CLADDING IN A BUILDING OR
 STRUCTURE SHALL BE ANCHORED TO RESIST
 WIND-INDUCED OVERTURNING, UPLIFT
 AND SLIDING AND TO PROVIDE CONTINUOUS
 LOAD PATHS FOR THESE FORCES TO THE
 FOUNDATION.WHERE A PORTION OF THE
 RESISTANCE TO THESE FORCES IS PROVIDED
 BY DEAD LOAD, THE MINIMUM DEAD LOAD
 LIKELY TO BE IN PLACE DURING A DESIGN
 WIND EVENT SHALL BE USED.
  
 3)407.2.3 SPILL CONTROL, DRAINAGE AND
 CONTAINMENT
 PROVIDE INFORMATION ON THE 350 GALLON
 DIESEL FUEL TANK.
 407.2.3.1 GENERAL. ROOMS, BUILDINGS
 OR AREAS USED FOR THE STORAGE OR
 DISPENSING OF SOLID OR LIQUID
 HAZARDOUS MATERIALS SHALL BE PROVIDED
 WITH A MEANS TO CONTROL SPILLAGE AND
 TO CONTAIN OR DRAIN SPILLAGE AND
 FIRE PROTECTION WATER DISCHARGED IN
 THE STORAGE AREA.A MEANS TO
 CONTROL SPILLAGE SHALL BE PROVIDED
 IN OPEN SYSTEMS IN WHICH DISPENSING
 IS DONE INTO CONTAINERS EXCEEDING 1
 GAL (3.79 L) CAPACITY, OR USED IN
 OPEN CONTAINERS OR SYSTEMS EXCEEDING
 5 GAL (18.9 L) CAPACITY, OR IN
 CLOSED SYSTEMS EXCEEDING 55 GAL
 (208.2 L) CAPACITY.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-10 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 10:46 Rev Time 0.75
Received By dpalmer Date 2005-09-10 Time 10:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-03 Cont ID  
Sent By dpalmer Date 2005-08-03 Time 07:03 Rev Time 1.50
Received By dpalmer Date 2005-08-03 Time 06:27 Sent To  
Notes
2005-08-03 00:00:00IN ELEC FOR REVIEW
 ********* UNSAT 2ND REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE; PLEASE CORRELATE ELECTRICAL SITE
 PLAN WITH ELECTRICAL RISER DIAGRAM'S
 SUBMITTED.
 PLEASE SEE MAINT BLDG ON PLANS INDICATES
 A "PROPOSED MAIN", THIS WAS LOCATED ON
 RISER AND SEEMS TO BE THE NEW MAIN
 REPLACING EXSITNG ATS?, HOWEVER PLEASE
 SEE SITE PLAN FOR MAINT BLDG ALSO
 INDICATES A NEW "PROPOSED ATS" WHICH
 COULD NOT BE LOCATED ON RISER DIAGRAM
 FOR "MAINT BLDG". PLEASE SEE THE ONLY
 NEW PROPOSED ATSSWITCH SHOWN ON RISER
 INDICATES THIS ATS AT PBSO SUB STATION E
 EXTERIOR WALL.
 IF NEW ATS IS AT SUB STATION, PLEASE
 VERIFY IF MDP( NOT ON SITE PLAN)
 CONTAINS A MCB. PLEASE SEE IT WAS NOTED
 ON PREVIOUS REVIEW AND MAIN DISCONNECT
 WILL BE REQUIRED AT PBSO SUB-STATION,
 SHALL BE SERVICE ENTRANCE RATED AND
 GROUPED.225.31,225.34,225.36.
 PLEASE SEE NOTE ON LOWER RIGHT-HAND SIDE
 OF E-1 INDICATES, SHEET FOR INFORMATION
 ONLY" AND "ALL ELECTRICAL WORK SHOWN ON
 E-1 SHALL BE UNDER A SEPARATE PROJECT??
 PLEASE CALRIFY, AS THIS PERMIT
 APPLICATION IS FOR THE NEW WORK AS
 SUBMITTED AND SHOWN ON RISER?
 PLEASE ALSO SEE A NOTE ON E-1 MENTIONS
 FOR A SIGN TO BE PROVIDED FOR GEN
 LOCATION, HOWEVER THIS NOTE MENTIONS GEN
 SHALL BE LOCATED IN AN INTERIOR ROOM
 LOCATED IN THE SW CORNER OF BLDG.??
 PLEASE SEE NEW GEN IS HOWN ON SITE PLAN
 AT MAINT BLDG?
 IS THERE "TWO GEN'S, ONE EXISTING , ONE
 NEW? IF SO PLEASE SEE RISER AND SHOW ALL
 EXISTING AND PROPOSED.
 SITE PLANS SHOW "EXISTING " FEED TO
 MAINT BLDG BEING ABANDONED?
 PLEASE CALRIFY AND CORRELATE. PLEASE SEE
 A TYPED WRITTEN RESPONSE LETTER TO
 COMMENTS WOULD HELP IN ANY
 CLARIFICATIONS.
  
 2)NOTE: PLEASE SEE PREVIOUS NOTE WHICH
 REQUESTED SPECS/MANUFACTURE SHEETS FOR
 ATS AND GEN. PLEASE SEE SHEET FOR ATS
 WERE SUBMITTED, HOWEVER, NONE FOR GEN
 COULD BE LOCATED, ONLY A LTR WHICH
 MENTIONED GEN SHALL BE RE-BUILT.
 PLEASE SEE FUEL TANK SUBMITTIALS ARE NOT
 CLEAR AS ONE SHEET MENTIONS A DIESEL GEN
 AND YET, NEW SHEET MENTIONS NEW GEN TO
 BE GAS?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE RISER SHOWS A NEW
 170KW GEN? SITE PLANS MENTIONS A NEW
 175KW GEN? PLEASE SEE RISER DOES NOT
 INDICATE ANY 175 KW GEN.
 215.5
  
 4)NOTE: PLEASE SEE VALUE FOR SCOPE PF
 WORK WAS NOT INCREASED BY CONTRACTOR. IF
 VALUEIS NOT ADJUSTED BY CONTRACTOR FOR
 ALL WORK AND MATERIALS, A VALUE WILL BE
 APPLIED. PLEASE SEE EVEN IF EQUIPMENT IS
 OWNER SUPPLIED THE PERMIT FEE IS BASED
 ON TOTAL IMPROVEMENT.
 ADIMINSTRATIVE FBC 104.6.5 LOCAL ADMIN
 AMENDMENTS.
  
 5)NOTE: PLEASE SEE ORIGINAL PERMIT
 APPLICATION WAS NOT SUBMITTED BACK WITH
 PACKAGE. PLEASE SEE ONLY A PHOTO-COPY OF
 FRONT WAS SUBMITTED. PLEASE SEE PACKAGE
 MUST CONTAIN SHEET WITH CONTRACTORS
 SIGNATURE AND MUST BE ORIGINAL.
 PLEASE SEE BLDG REVIEW COMMENTS FOR
 THIS.
  
 6)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL. PLEASE SEE THIS ONLY A
 NOTICE GIVEN AT THIS TIME.
 ONE SET OF ELECTRICAL SHEETS ARE BEING
 RETAINED FOR FILE.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 SHEETS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-14 Cont ID  
Sent By dpalmer Date 2005-06-14 Time 07:24 Rev Time 0.75
Received By dpalmer Date 2005-06-14 Time 07:12 Sent To  
Notes
2005-06-14 00:00:00******** UNSAT *********
  
 1)NOTE; PLEASE CORRELATE PLANS AND RISER
 DIAGRAM.
 PLEASE SEE E-1 SHOWS EXISTING MAINT BLDG
 BEING FED FROM FPL TRANSFORMER AND THIS
 FEED IS TO REMAIN. HOWEVER, RISER
 DIAGRAM SHOWS THIS MAINT BLDG BEING FED
 FROM EXISTING PBSO BLDG??
 PLEASE CORRECT.
  
 2)NOTE: PLEASE SEE FEED IS SHOWN ON
 RISER COMING INTO MAIN DISCONNECT AND
 NOT ATS. PLEASE SEE MEANS OD DISC
 REQUIRED FOR FEED FROM GEN LOCATED AT
 BLDG, THESE SHALL ALSO BE GROUPED BE
 RATED FOR SERVICE ENT EQUIPMENT.
 PLEASE SEE 225.31-225.36, SIGNAGE PER
 702.8
 215.5
  
 3)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECS/CUT SHEETS FOR GENERATOR, ATS.
 PLEASE SEE 225.31-225.36 FOR ATS/DISC.
  
 PLEASE SUBMIT MANUFACTURE CUT/SPECS FOR
 SUB-BASE FUEL TANK ALSO FOR MECH/FIRE
 REVIEW. 110.3 SHOWING ALL LISTINGS BY A
 NRTL.
 215..5
  
 4)NOTE: PLEASE SUPPLY LOAD CALCULATIONS
 FOR LOAD TO BE SERVED PER 702.5
  
 5)NOTE: PLEASE SEE VALUE FOR SCOPE OF
 WORK IS TO INCLUDE ALL LABOR AND
 MATERIALS EVEN IF OWNER SUPPLIED PER FBC
 104.6.5
 THIS WOULD INCLUDE GEN/ATS/TANK ETC.
  
 6)NOTE: PLEASE SEE BLDG REVIEW COMMENTS.
 PLEASE SEE MISSING LICENSE INFORMATION
 REQUIRED ON TITLE BLOCK FOR ENGINEERING
 FIRM.
 FAC 61G15-23.002, FS 471.023
 THIS COMMENT IS NOT FOR ELECTRICAL ENG
 FIRM.
  
 7)NOTE: PLEASE SEE ELEVATION ON SURVEY
 FOR FLOOD ZONE AND MIN ELEVATION OF
 EQUIPMENT.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-18 Cont ID  
Sent By mwennerg Date 2005-08-18 Time 14:58 Rev Time 0.00
Received By mwennerg Date 2005-08-18 Time 14:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-06-14 Cont ID  
Sent By mwennerg Date 2005-06-14 Time 09:27 Rev Time 0.00
Received By mwennerg Date 2005-06-14 Time 09:19 Sent To  
Notes
2005-06-14 00:00:00****DENIED****
  
 1) PLEASE PROVIDE CUT SHEETS/
 INFORMATION IN REGARDS TO THE GENERATOR
 AND ASSOCIATED FUEL.
  
 2) PLEASE ILLUSTRATE VENTING
 REQUIREMENTS AND VENT PIPE SIZE,
 CLEARANCE AND DIAMETER.
  
 3) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS AND FAC REQUIREMENTS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-06 Cont ID  
Sent By adarroug Date 2005-09-06 Time 11:45 Rev Time 0.00
Received By adarroug Date 2005-09-06 Time 11:45 Sent To E
Notes
2005-09-06 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 13:26 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 13:26 Sent To  
Notes
2005-07-28 00:00:00TO "COMM" BD#20/ W RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-27 Cont ID  
Sent By adarroug Date 2005-07-27 Time 08:44 Rev Time 0.00
Received By adarroug Date 2005-07-27 Time 08:44 Sent To  
Notes
2005-07-27 00:00:00TO "COMM" BD#20

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-20 Cont ID  
Sent By shill Date 2005-06-20 Time 09:00 Rev Time 0.00
Received By shill Date 2005-06-20 Time 09:00 Sent To Z
Notes
2005-06-20 00:00:00TAKEN OFF OF BOARD, ROUTED TO ZONING
 (ALL OTHER REVIEWS COMPLETE)

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-21 Cont ID  
Sent By adarroug Date 2005-06-20 Time 10:31 Rev Time 0.00
Received By adarroug Date 2005-05-16 Time 13:58 Sent To  
Notes
2005-05-27 00:00:00TO "COMM" BD#35
2005-05-16 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-29 Cont ID  
Sent By pkrauss Date 2005-07-29 Time 14:24 Rev Time 0.25
Received By pkrauss Date 2005-07-29 Time 14:24 Sent To  
Notes
2005-07-29 00:00:00PASSED:
 NEW GENERATOR WAS CHANGED FROM FUEL TO
 NATURAL GAS.GENERATOR IS 10 FT FROM
 PROPERTY LINE & 36' 4" FROM THE BUILDING
 (PLAN SHEET 1 OF 2).
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-14 Cont ID  
Sent By pkrauss Date 2005-06-14 Time 19:54 Rev Time 0.40
Received By pkrauss Date 2005-06-14 Time 19:48 Sent To  
Notes
2005-06-14 00:00:00DENIED:
 INSUFFICIENT INFORMATION FOR REVIEW.
 ADDTIONAL COMMENTS MAY RESULT WHEN
 REVIEW COMMENTS ARE ADDRESSED.
 1.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE GENERATOR WITH
 SUB-BASE FUEL TANK.
  
 2.PROVIDE DISTANCE TO PROPERTY LINES.
  
 PROVIDE LICENSE NUMBER FOR THE ENGINEER
 IN ACCORDANCE WITH FS 471.023.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-08-27 Cont ID  
Sent By pschmitz Date 2005-08-27 Time 13:50 Rev Time 0.00
Received By jwitmer Date 2005-08-27 Time 13:50 Sent To Z
Notes
2005-08-27 00:00:00PLUMBING PLAN REVIEW EXAMINER, FBC 2001
 PAUL SCHMITZ561-805-6692
  
 [email protected]
 FBC 2001
 SEPERATEM PLANS AND PERMIT FOR NATURAL
 GAS PIPING.
 END OF COMMENTS

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-29 Cont ID  
Sent By mmclean Date 2005-08-29 Time 16:09 Rev Time 0.00
Received By mmclean Date 2005-08-29 Time 16:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-06-20 Cont ID  
Sent By mmclean Date 2005-06-20 Time 16:48 Rev Time 0.00
Received By mmclean Date 2005-06-20 Time 16:48 Sent To I
Notes
2005-06-20 00:00:00DENIED,
 1. NEED TO STATE ON THE PLANS HOW FAR
 THE GENERATOR IS FROM THE PROPERTY LINE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720