Plan Review Details - Permit 05051024
Plan Review Stops For Permit 05051024
Review Stop E ELECTRICAL
Rev No 1 Status N Date 2005-05-23 Cont ID  
Sent By btrobaug Date 2005-05-23 Time 16:52 Rev Time 0.33
Received By btrobaug Date 2005-05-23 Time 16:39 Sent To P
Notes
2005-05-23 00:00:00 
 THERE IS NO ELECTRICAL PERMIT APPLIED
 FOR. AN ELECTRICAL PERMIT IS REQUIRED IF
 ELECTRICAL WORK IS TO BE DONE IN THESE
 BATHS. PLEASE HAVE ELECTRICAL
 CONTRACTORAPPLY WITH PLANS INDICATING
 THE SCOPE OF ELEC WORK.
  
 1} THE APPLICATION IS NOT SIGNED.
 2} THE ARCHITECT DID NOT DATE THE PLAN.
 3} THERE IS NO CERTIFICATE OF
 AUTHORIZATION ON THE TITLE BLOCK.
  
 SEE 481 FS AND 61G1-16.003 AND .004,
 FAC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-16 Cont ID  
Sent By adarroug Date 2005-05-16 Time 14:51 Rev Time 0.00
Received By adarroug Date 2005-05-16 Time 14:51 Sent To E
Notes
2005-05-16 00:00:00TO "E" BOX

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-05-28 Cont ID  
Sent By kstevens Date 2005-05-28 Time 14:35 Rev Time 1.50
Received By kstevens Date 2005-05-28 Time 14:35 Sent To  
Notes
2005-05-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PERMIT APPLICATION SHALL BE SIGNED BY
 THE QUALIFER OF THE BUSINESS OR AN
 AUTHORIZED AGENT. SECTION 104.1.1.
 2. AN APPLICATION FOR COM. REMODEL FOR
 THE REMODELING THE BATHROOMS SHALL BE
 SUBMITTED BY AN APPROIATE CONTRACTOR TO
 DEMO THE EXISTING FLOOR PLAN AND
 CONSTRUCT NEW WALLS ECT. SECTION 104.1
 3. THE PERSONAL SEAL, SIGNATURE AND DATE
 OF THE ARCHITECT SHALL APPEAR ON ALL
 ARCHITECTURAL DOCUMENTS TO BE FILED FOR
 PUBLIC RECORD. FAC 61G1-16.003 & FS
 481.2055.
 4. THE FIRM LICENSE NUMBER, CERTIFICATE
 OF AUTHORIZATION IS REQUIRED FOR ANY
 ARCHITECTURAL BUSINESS, PARTNERSHIP,
 INCORPORATION, OR FICTICIOUS NAME PER
 FAC 61G1-16.004(2) & FS 481.219.
 5. SUBMIT A DETAIL FOR THE BATHROOMS
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19, & 11-4.22 AND ALL
 SUBSECTIONS. SHOW THE FOLLOWING:
 FOR W/C'S:
 A. CLEAR FLOOR SPACE 11-4.16.2
 B. HEIGHT 11-4.16.3 (SHOWN AS 19"/20")
 C. FLUSH CONTROLS 11-4.16.5
 FOR LAVS:
 A. HEIGHT & CLEARANCES 11-4.19.2
 B. CLEAR FLOOR SPACE 11-4.19.3
 C. EXPOSED PIPES & SURFACES 11-4.19.4
 D. FAUCETS 11-4.19.5
 FOR TOILET ROOMS:
 A. DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 11-4.22.2
 B. AN UNOBSTRUCTED TURNING SPACE
 COMPLYING WITH 11-4.2.3 SHALL BE
 PROVIDED WITHIN AN ACCESSIBLE TOILET
 ROOM. 11-4.22.3
 6. INDICATE THE SQUARE FOOTAGE FOR EACH
 UNIT. SECTION 104.2.1.
 7. A DRINKING FOUNTAIN IS REQUIRED IN
 EACH SPACE. TABLE 403.1.
 8. SUBMIT A SANITARY RISER DIAGRAM. SHOW
 ALL PIPE SIZES, VENTS, AND POINTS OF
 CONNTECTION. SECTION 104.3.1.1.
 9. SUBMIT A WATER RISER DIAGRAM SHOWING
 ALL PIPE SIZE, VALVES, WATER HAMMER
 ARRESTORS, (WHERE REQUIRED BY SECTION
 604.9), AND POINT OF CONNECTION.
 10. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. PLEASE
 INDICATE IF THERE IS AN EXISTINE
 BACKFLOW. SECTION 608.13.2.
 11. MORE COMMENTS MAY BE FORTHCOMING
 DEPENDING ON THE RESPONSES OF THE
 COMMENTS FOR THIS REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  