| 2005-05-28 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. PERMIT APPLICATION SHALL BE SIGNED BY |
| | THE QUALIFER OF THE BUSINESS OR AN |
| | AUTHORIZED AGENT. SECTION 104.1.1. |
| | 2. AN APPLICATION FOR COM. REMODEL FOR |
| | THE REMODELING THE BATHROOMS SHALL BE |
| | SUBMITTED BY AN APPROIATE CONTRACTOR TO |
| | DEMO THE EXISTING FLOOR PLAN AND |
| | CONSTRUCT NEW WALLS ECT. SECTION 104.1 |
| | 3. THE PERSONAL SEAL, SIGNATURE AND DATE |
| | OF THE ARCHITECT SHALL APPEAR ON ALL |
| | ARCHITECTURAL DOCUMENTS TO BE FILED FOR |
| | PUBLIC RECORD. FAC 61G1-16.003 & FS |
| | 481.2055. |
| | 4. THE FIRM LICENSE NUMBER, CERTIFICATE |
| | OF AUTHORIZATION IS REQUIRED FOR ANY |
| | ARCHITECTURAL BUSINESS, PARTNERSHIP, |
| | INCORPORATION, OR FICTICIOUS NAME PER |
| | FAC 61G1-16.004(2) & FS 481.219. |
| | 5. SUBMIT A DETAIL FOR THE BATHROOMS |
| | SHOWING COMPLIANCE WITH SECTIONS |
| | 11-4.16, 11-4.19, & 11-4.22 AND ALL |
| | SUBSECTIONS. SHOW THE FOLLOWING: |
| | FOR W/C'S: |
| | A. CLEAR FLOOR SPACE 11-4.16.2 |
| | B. HEIGHT 11-4.16.3 (SHOWN AS 19"/20") |
| | C. FLUSH CONTROLS 11-4.16.5 |
| | FOR LAVS: |
| | A. HEIGHT & CLEARANCES 11-4.19.2 |
| | B. CLEAR FLOOR SPACE 11-4.19.3 |
| | C. EXPOSED PIPES & SURFACES 11-4.19.4 |
| | D. FAUCETS 11-4.19.5 |
| | FOR TOILET ROOMS: |
| | A. DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| | 11-4.22.2 |
| | B. AN UNOBSTRUCTED TURNING SPACE |
| | COMPLYING WITH 11-4.2.3 SHALL BE |
| | PROVIDED WITHIN AN ACCESSIBLE TOILET |
| | ROOM. 11-4.22.3 |
| | 6. INDICATE THE SQUARE FOOTAGE FOR EACH |
| | UNIT. SECTION 104.2.1. |
| | 7. A DRINKING FOUNTAIN IS REQUIRED IN |
| | EACH SPACE. TABLE 403.1. |
| | 8. SUBMIT A SANITARY RISER DIAGRAM. SHOW |
| | ALL PIPE SIZES, VENTS, AND POINTS OF |
| | CONNTECTION. SECTION 104.3.1.1. |
| | 9. SUBMIT A WATER RISER DIAGRAM SHOWING |
| | ALL PIPE SIZE, VALVES, WATER HAMMER |
| | ARRESTORS, (WHERE REQUIRED BY SECTION |
| | 604.9), AND POINT OF CONNECTION. |
| | 10. AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE TO THE BUILDING. PLEASE |
| | INDICATE IF THERE IS AN EXISTINE |
| | BACKFLOW. SECTION 608.13.2. |
| | 11. MORE COMMENTS MAY BE FORTHCOMING |
| | DEPENDING ON THE RESPONSES OF THE |
| | COMMENTS FOR THIS REVIEW. |
| | |