Plan Review Details - Permit 05051005
Plan Review Stops For Permit 05051005
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-09-23 Cont ID  
Sent By mjacobs Date 2005-09-23 Time 17:02 Rev Time 2.00
Received By mjacobs Date 2005-09-23 Time 17:02 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-02 Cont ID  
Sent By mjacobs Date 2005-08-02 Time 09:04 Rev Time 2.75
Received By mjacobs Date 2005-08-02 Time 06:50 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-22 Cont ID  
Sent By mjacobs Date 2005-07-22 Time 16:26 Rev Time 2.50
Received By mjacobs Date 2005-07-22 Time 08:38 Sent To PC
Notes
2005-07-22 00:00:00BUILDING PLAN REVIEW
 PERMIT:05051005
 ADD:743 BISCAYNE DR.
 CONT:STEPHEN ROY
 TEL: (561)248-9516
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION:DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 3) WHICH ONE OF THE DECK WILL BE
 CONCRETE? ONE OF THE PRODUCT APPROVAL
 SUBMITTED REFERS TO A CONCRETE DECK.
 ALSO NONE OF THE PRODUCT APPROVALS HAVE
 THE STATE COVER SHEETS. ALL PRODUCTS
 SUBMITTED NEEDS THE MATCHING CURRENT
 STATE COVER SHEET. I AM SUPPLYING YOU
 WITH AN EXAMPLE OF THE STATE COVER SHEET
 WITH ONE OF THE PRODUCT YOU SUBMITTED,
 SO YOU CAN SEE WHAT I AM SPEAKING OF.
  
 4) THE PRODUCT APPROVALS SUBMITTED FOR
 THE METAL ROOF NEEDS A STATE APROVAL
 REPORT ALONG WITH THE STATE COVER
 SHEETS. THE MANUFACTURE INFORMATION
 ALONE IS NOT ACCEPTABLE. ALSO PLEASE SEE
 FBC.1507.6.2 DECK SLOPE. METAL ROOF
 SHINGLES SHALL NOT BE INSTALLED ON ROOF
 SLOPES BELOW 3:12.
 1507.6.3 UNDERLAYMENT. UNDERLAYMENT
 SHALL CONFORM WITH ASTM D 226, TYPE
 I.
 5) IS THE CARRAGE HOUSE GETTING A NEW
 FLAT ROOF? OR IS THE ROOF EXISTING?
 PLEASE CLARIFY. IF IT IS A NEW ROOF,
 SUPPLY PRODUCT APPROVAL FOR THE FLAT
 ROOF.WHEN SUBMITTING PRODUCT APPROVALS
 FOR THE FLAT ROOF, PLEASE KNOW THAT
 SYSTEMS THAT STATES GENERAL LIMITATIONS
 #9 WITH -PSF LESS THAT -89PSF IS NOT
 ACCEPTABLE.
  
 6) FBC 1606.2.5.GENERAL LIMITATION
 #9 PROHIBITS RATIONAL ANALYSIS OR
 EXTRAPOLATION TO ENHANCE THE UPLIFT
 PRESSURE AT PERIMETER AND CORNER AREAS
 BY REDUCING THE FASTENER SPACING IN
 THESE AREAS.EITHER SELECT AN
 ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL)
 THAT DOES NOT CITE GENERAL LIMITATION
 #9.ALTERNATIVELY IF THE SELECTED
 SYSTEM DOES CITE GENERAL LIMITATION #9,
 IT MUST HAVE A MAXIMUM DESIGN PRESSURE
 THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3
 (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT
 OF 30 FEET OR LESS).
  
 7) ON SHEET A.5, IF DOOR 'E' WILL BE
 USED PLEASE SUPLY PRODUCT APPROVAL FOR
 THAT DOOR OR YOU MAY APPLY FOR LOCAL
 PRODUCT APPROVAL. SEE APPLICATION IN
 PACKAGE.
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-27 Cont ID  
Sent By mjacobs Date 2005-06-27 Time 10:30 Rev Time 4.50
Received By mjacobs Date 2005-06-27 Time 06:51 Sent To PC
Notes
2005-06-27 00:00:00BUILDING PLAN REVIEW
 PERMIT:05051005
 ADD:743 BISCAYNE DR.
 CONT:ROY STEPHEN
 TEL: (561)659-5683
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION:DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3) PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 4) PLEASE PROVIDE PRODUCT APPROVALS FOR
 THE FOLLOWING.NEW DOORS/WINDOWS,ROOFING
 MATERIALS, LENTIL PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER
 OCTOBER 1, 2003 ARE REQUIRED TO COMPLY
 WITH THE FLORIDA PRODUCT APPROVAL
 SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE ATWWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE
 REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) PLEASE SHOW A DETAIL DRAWING FOR THE
 NEW PARAPET CONSTRUCTION.
  
 6) FBC 2309.6ACCESS TO ATTIC SPACE
 EACH ATTIC SPACE WITH A CLEAR HEIGHT OF
 24" OR GREATER SHALL BE PROVIDED WITH AN
 INTERIOR ATTIC ACCESS OPENING NOT LESS
 THAN 20"X 36".
  
 7)THE SURVEY SUBMITTED STATES THAT THIS
 LOCATION IN A 'C' ZONE HOWEVER ON THE
 PLANS SHEET A.O. STATES FLOOD ZONE AS
 'A5'. ACCORDING TO OUR FLOOD MAP, THE
 LOCATION IS IN A 'C' ZONE.PLEASE CHANGE
 PLANS TO MATCH.
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026
 [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-10-31 Cont ID  
Sent By btrobaug Date 2006-10-31 Time 12:50 Rev Time 0.50
Received By btrobaug Date 2006-10-31 Time 12:04 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-03-15 Cont ID  
Sent By btrobaug Date 2006-03-15 Time 11:38 Rev Time 0.50
Received By btrobaug Date 2006-03-15 Time 11:38 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-09-10 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 13:57 Rev Time 0.33
Received By dpalmer Date 2005-09-10 Time 13:35 Sent To M
Notes
2005-09-10 00:00:00REDLINED PLANS,
 PANEL "C" SHALL NOT BE LOCATES IN A
 "STORAGE RM".
 240.24D,110.26,408.7
 THIS RM AS SHOWN IS ONLY TO BE A
 ELECTRICAL / EMCH RM OR PANEL IS TO BE
 MOVED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-26 Cont ID  
Sent By btrobaug Date 2005-07-26 Time 12:00 Rev Time 0.50
Received By btrobaug Date 2005-07-26 Time 11:49 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-12 Cont ID  
Sent By btrobaug Date 2005-07-12 Time 12:30 Rev Time 0.50
Received By btrobaug Date 2005-07-12 Time 12:15 Sent To P
Notes
2005-07-12 00:00:00 
 THE ARCHITECT MUST SIGN AND SEAL BOTH
 SETS OF PLANS. 61G1-16.003 FAC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-31 Cont ID  
Sent By btrobaug Date 2005-05-31 Time 14:11 Rev Time 0.50
Received By btrobaug Date 2005-05-27 Time 17:48 Sent To M
Notes
2005-05-31 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE LOCATION OF THE SERVICE
 SO THAT DISCONNECT REQUIREMENTS CON BE
 REVIEWED.
  
 2} SHOW LOCATION OF THE PANEL SERVING
 THE REC ROOM, DISCONNECTING MEANS AND
 GROUNDING.
  
 3} PLEASE PUT ROOM DESIGNATIONS ON THE
 ELECTRICAL FLOOR PLANS.
  
 4} THE PANEL DESIGNATION ON THE RISER
 AND PANEL SCHEDULE DO NOT CCORRELATE.
 "C" & "G".
  
 5} SEE 210.52(C)(2) FOR ISLAND
 RECEPTACLE REQUIREMENTS.INDICATE
 COMPLIANCE ON PLANS.
  
 6} REC ROOM KITCHEN COUNTERTOP
 RECEPTACLE SPACING MUST COMPLY WITH
 210.52(C)(1).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-10-25 Cont ID  
Sent By adarroug Date 2006-10-25 Time 11:01 Rev Time 0.00
Received By adarroug Date 2006-10-25 Time 11:01 Sent To E
Notes
2006-10-25 11:01:53TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-03-15 Cont ID  
Sent By adarroug Date 2006-03-15 Time 10:24 Rev Time 0.00
Received By adarroug Date 2006-03-15 Time 10:24 Sent To E
Notes
2006-03-15 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-09-12 Cont ID  
Sent By adarroug Date 2005-09-12 Time 16:33 Rev Time 0.00
Received By adarroug Date 2005-09-12 Time 16:33 Sent To B
Notes
2005-09-12 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 09:01 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 09:01 Sent To E
Notes
2005-09-08 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date 2005-08-01 Cont ID  
Sent By adarroug Date 2005-07-26 Time 11:52 Rev Time 0.00
Received By adarroug Date 2005-07-26 Time 11:52 Sent To  
Notes
2005-08-01 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 12:42 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 12:42 Sent To E
Notes
2005-07-07 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 09:15 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 09:15 Sent To E
Notes
2005-05-24 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-27 Cont ID  
Sent By mjacobs Date 2005-06-27 Time 14:15 Rev Time 0.00
Received By mjacobs Date 2005-05-16 Time 13:52 Sent To  
Notes
2005-05-16 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-09-12 Cont ID  
Sent By tgordon Date 2005-09-12 Time 11:12 Rev Time 0.30
Received By tgordon Date 2005-09-12 Time 11:43 Sent To  
Notes
2005-09-12 00:00:00*** PROVISO ***
  
 1) A GAS PERMIT IS REQUIRED FOR GAS
 LINES.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL,
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-20 Cont ID  
Sent By rregueir Date 2005-07-20 Time 17:01 Rev Time 0.00
Received By rregueir Date 2005-07-20 Time 17:00 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-15 Cont ID  
Sent By hmoser Date 2005-06-15 Time 13:18 Rev Time 0.00
Received By hmoser Date 2005-06-15 Time 13:19 Sent To P
Notes
2005-06-15 00:00:00PLAN DENIED
 1) PLEASE SUPLY TWO SETS OF ENERGY
 CALCULATIONS,AND MANUAL (J) WITH PLANS
 2) REFER TO SECTION 601.4 2001
 FBC(M)BALANCED RETURN AIR.
 3) REFER TO SECTION 307.2.3 AUXILIAEY
 DRAIN PANS.
 4) PLEASE SHOW TYPE OF DOORS ON PLAN FOR
 WASHER & DRYER
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-07-20 Cont ID  
Sent By pschmitz Date 2005-07-20 Time 10:22 Rev Time 0.00
Received By pschmitz Date 2005-07-20 Time 10:22 Sent To M
Notes
2005-07-20 00:00:00PROVISO:
 SEE NOTES ON SHT P-1

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-18 Cont ID  
Sent By pschmitz Date 2005-06-18 Time 05:12 Rev Time 0.00
Received By pschmitz Date 2005-06-18 Time 05:12 Sent To B
Notes
2005-06-18 00:00:00PLUMBING PLAN REVIEW DENIED FBC 2001
 (1) SEC 909 WET VENTING:
 MASTER BATH, TUB, SHOWER NOT VENTED.
 CONNECT THE LAV WET VENT TO TUB, SHOWER
 FIXTURE DRAINS.
 (2)MINIMUM FACILITES REQUIRED: TAB 403.1
 SHOW LOCATION OF THE WASHING MACHINE
 DRAIN, AND H/C WATER CONNECTIONS,
 (3)SEPERATE PERMIT FOR PLUNGE POOL.
 (4) LOCAL ORD #2853-95
 BACK FLOW PREVENTER REQUIRED ON WATER
 SERVICE FOR PLUNGE POOL.
 END OF COMMENTS.
 QUESTIONS: PAUL SCHMITZ 561-805-6692

Review Stop Z ZONING
Rev No 1 Status P Date 2005-05-23 Cont ID  
Sent By mmclean Date 2005-05-23 Time 11:16 Rev Time 0.00
Received By mmclean Date 2005-05-23 Time 11:16 Sent To I
Notes
2005-05-23 00:00:00APPROVING FOR ADDITION ONLY.