Plan Review Details - Permit 05050970
Plan Review Stops For Permit 05050970
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-09-15 Cont ID  
Sent By jwitmer Date 2005-09-15 Time 10:55 Rev Time 0.55
Received By jwitmer Date 2005-09-07 Time 08:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-08-22 Cont ID  
Sent By jwitmer Date 2005-08-22 Time 12:35 Rev Time 0.55
Received By jwitmer Date 2005-08-22 Time 12:35 Sent To PC
Notes
2005-08-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05050970
 ADD: 777 S FLAGLER DR 12 FL
 CONT: CATALFUMO
 TEL: (561)307-4836
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW REVISIONS
 ACTION: DENIED
  
 1) SEE ROOMS 206 A & B, MISSING THE
 18" CLEAR FLOOR SPACE:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-06-30 Cont ID  
Sent By jwitmer Date 2005-06-30 Time 17:37 Rev Time 0.44
Received By jwitmer Date 2005-06-30 Time 17:37 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-26 Cont ID  
Sent By jwitmer Date 2005-06-26 Time 11:49 Rev Time 1.77
Received By jwitmer Date 2005-06-26 Time 11:41 Sent To PC
Notes
2005-06-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05050970
 ADD: 777 S FLAGLER/ 12 FL W
 CONT: CATALFUMO
 TEL: (561)307-4836
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 3) HANDICAPPED ACCESSIBILITYIS MISSING
 AT DOOR# 1201, 1209B, 1222,1223 & 1255.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
  
 PRIMARY FUNCTION. A "PRIMARY FUNCTION"
 IS A MAJOR ACTIVITY FOR WHICH THE
 FACILITY IS INTENDED.AREAS THAT
 CONTAIN A PRIMARY FUNCTION INCLUDE, BUT
 ARE NOT LIMITED TO, OFFICES AND OTHER
 WORK AREAS IN WHICH THE ACTIVITIES
 OF THE PUBLIC ACCOMMODATION OR OTHER
 PRIVATE ENTITY USING THE FACILITY ARE
 CARRIED OUT.
  
 THESE ARE AREA OF CONTRACT THAT CAN BE
 BACKED OUT OF CONTRACT TO DETERMINE PER
 CENTAGES FOR DISPROPORTIONATE COST.
  
 MECHANICAL ROOMS, BOILER ROOMS, SUPPLY
 STORAGE ROOMS, EMPLOYEE LOUNGES OR
 LOCKER ROOMS, JANITORIAL CLOSETS,
 ENTRANCES,CORRIDORS, AND RESTROOMS ARE
 NOT AREAS CONTAINING A PRIMARY FUNCTION.
  
 ALTERATIONS TO AN AREA CONTAINING A
 PRIMARY FUNCTION:
  
 (1) ALTERATIONS THAT AFFECT THE
 USABILITY OF OR ACCESS TO AN AREA
 CONTAINING A PRIMARY FUNCTION
 INCLUDE, BUT ARE NOT LIMITED TO:
  
 (A) REMODELING MERCHANDISE DISPLAY
 AREAS OR EMPLOYEE WORK AREAS IN A
 DEPARTMENT STORE;
  
 (B) REPLACING AN INACCESSIBLE
 FLOOR SURFACE IN THE CUSTOMER SERVICE
 OR EMPLOYEE WORK AREAS OF A BANK;
  
 (C) REDESIGNING THE ASSEMBLY LINE
 AREA OF A FACTORY; OR
  
 (D) INSTALLING A COMPUTER CENTER
 IN AN ACCOUNTING FIRM.
  
 (2) FOR THE PURPOSES OF THIS
 SECTION, ALTERATIONS TO WINDOWS,
 HARDWARE, CONTROLS, ELECTRICAL
 OUTLETS, AND SIGNAGE SHALL NOT BE DEEMED
 TO BE ALTERATIONS THAT AFFECT THE
 USABILITY OF OR ACCESS TO AN AREA
 CONTAINING A PRIMARY FUNCTION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-09-20 Cont ID  
Sent By dpalmer Date 2005-09-20 Time 17:54 Rev Time 0.40
Received By dpalmer Date 2005-09-20 Time 17:54 Sent To  
Notes
2005-09-20 00:00:00*** NEW SHEETS ADDED TO REVISIONS.
  
  
 PLEASE SEE REDLINED PLANS FOR GFI
 PROTECTION IN KITCHEN AREAS IN OTHER
 THAN DWELLING UNITS.
 2002 NEC 210.8B3
  
  
 PLEASE SEE ALL REVISIONS ARE REQUIRED
 BEFORE ROUGH/ FINAL FOR CIRCUITING AND
 IDENTIFICATION.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-07-29 Cont ID  
Sent By dpalmer Date 2005-07-29 Time 07:41 Rev Time 0.75
Received By dpalmer Date 2005-07-28 Time 21:25 Sent To  
Notes
2005-07-29 00:00:00******** NOTE REDLINED ********
  
 1)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLING UNITS
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
 REVISE ANY CIRCUTING/LABELING OF GFI
 CIRCUITS/RECEPTS.
  
2005-07-28 00:00:00IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-30 Cont ID  
Sent By dpalmer Date 2005-06-30 Time 19:17 Rev Time 0.50
Received By dpalmer Date 2005-06-30 Time 19:07 Sent To  
Notes
2005-06-30 00:00:00PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-06-08 Cont ID  
Sent By dpalmer Date 2005-06-08 Time 10:10 Rev Time 1.00
Received By dpalmer Date 2005-06-08 Time 10:10 Sent To  
Notes
2005-06-08 00:00:00********** UNSAT **********
  
 1)NOTE: PLEASE SEE MIN CLEARENCE
 REQUIRED IN ELECTRICAL ROOM. 110.26
  
 2)NOTE: PLEASE PLACE NOTE ON ELECTRICAL
 PLANS FOR RATING OF IT ROOM,
 DISCONNECTING MEANS AND OR/ FIRE DAMPERS
 PER 645.10,645.2
  
 3)NOTE: PLEASE ALSO SEE 645.11 FOR
 DISCONNECTING MEANS.
  
 4)NOTE: PLEASE SEE PANEL "L" WHICH IS
 REQUIRED TO BE A MCB PANEL. 408.16
 PLEASE CLARIFY. PLEASE ALSO SEE WITH THE
 AMOUNT OF WORK BEING DONE TO THIS SPACE
 A MCB WILL BE REQUIRED TO BE INSTALLED
 IF NOT PRESENT AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-09-21 Cont ID  
Sent By mwennerg Date 2005-09-21 Time 13:58 Rev Time 0.00
Received By mwennerg Date 2005-09-21 Time 13:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-08-15 Cont ID  
Sent By mwennerg Date 2005-08-15 Time 15:08 Rev Time 0.00
Received By mwennerg Date 2005-08-15 Time 15:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-15 Cont ID  
Sent By mwennerg Date 2005-08-15 Time 15:02 Rev Time 0.00
Received By mwennerg Date 2005-08-15 Time 15:01 Sent To  
Notes
2005-08-15 00:00:00APPROVED ON 6/9/05
  
 REVISION DATED 6/29/05
  
 IN ACCORDANCE WITH LOCAL REQUIREMENTS,
 NEW DUCT SMOKE DETECTORS SHALL BE WIRED
 TO CAUSE A GENERAL FIRE ALARM CONDITION
 WHEN ACTIVATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-06-09 Cont ID  
Sent By mwennerg Date 2005-06-09 Time 10:38 Rev Time 0.00
Received By mwennerg Date 2005-06-09 Time 10:37 Sent To  
Notes
2005-06-09 00:00:001) NEW DUCT SMOKE DETECTOR INSTALLATIONS
 WHERE PROVIDED SHALL BE WIRED TO THE
 FIRE ALARM SYSTEM TO CAUSE A GENERAL
 FIRE ALARM, IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
 2) AS NOTED ON THE DRAWINGS, SEPARATE
 SHOP DRAWINGS AND PERMITS ARE REQUIRED
 FOR FIRE ALARM AND FIRE SPRINKLER
 REMODEL.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-31 Cont ID  
Sent By adarroug Date 2005-08-31 Time 17:02 Rev Time 0.00
Received By adarroug Date 2005-08-31 Time 17:02 Sent To  
Notes
2005-08-31 00:00:00TO "COMM" BD#14

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-22 Cont ID  
Sent By adarroug Date 2005-07-22 Time 13:07 Rev Time 0.00
Received By adarroug Date 2005-07-22 Time 13:07 Sent To  
Notes
2005-07-25 00:00:00TO "COMM" BD#48
2005-07-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-30 Cont ID  
Sent By adarroug Date 2005-06-30 Time 16:06 Rev Time 0.00
Received By adarroug Date 2005-06-30 Time 16:06 Sent To B
Notes
2005-06-30 00:00:00TO "JWITMER" DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-29 Cont ID  
Sent By adarroug Date 2005-06-29 Time 11:29 Rev Time 0.00
Received By adarroug Date 2005-06-29 Time 11:29 Sent To  
Notes
2005-06-29 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-26 Cont ID  
Sent By jwitmer Date 2005-06-26 Time 12:01 Rev Time 0.00
Received By jwitmer Date 2005-05-13 Time 16:44 Sent To PC
Notes
2005-05-27 00:00:00TO "COMM" BD#7
2005-05-13 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-09-19 Cont ID  
Sent By pkrauss Date 2005-09-19 Time 09:42 Rev Time 0.45
Received By pkrauss Date 2005-09-19 Time 09:42 Sent To  
Notes
2005-09-19 00:00:00REVISION APPROVED
 PLANS M0.1, M2.1, M7.1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-19 Cont ID  
Sent By pkrauss Date 2005-09-19 Time 09:41 Rev Time 0.00
Received By pkrauss Date 2005-08-11 Time 15:11 Sent To  
Notes
2005-08-11 00:00:00APPROVED 8-11-05
 REVISED PAGES M0.1,M2.1,M7.1.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-06-23 Cont ID  
Sent By pkrauss Date 2005-06-23 Time 16:24 Rev Time 0.40
Received By pkrauss Date 2005-06-23 Time 15:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-09-22 Cont ID  
Sent By pschmitz Date 2005-09-21 Time 11:55 Rev Time 0.00
Received By jleech Date 2005-09-21 Time 11:55 Sent To  
Notes
2005-09-22 00:00:00PASSED BY P SCHMITZ ENTERED BY J LEECH

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-20 Cont ID  
Sent By pschmitz Date 2005-08-20 Time 10:09 Rev Time 0.00
Received By pschmitz Date 2005-08-20 Time 10:08 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-18 Cont ID  
Sent By pschmitz Date 2005-06-18 Time 12:38 Rev Time 0.00
Received By pschmitz Date 2005-06-18 Time 12:38 Sent To M
Notes
***NONE***