Plan Review Details - Permit 05050621
Plan Review Stops For Permit 05050621
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-09-09 Cont ID  
Sent By alange Date 2005-09-09 Time 10:58 Rev Time 0.66
Received By alange Date 2005-09-09 Time 10:58 Sent To Z
Notes
2005-09-09 00:00:00REVISION NOTES:
  
 1.SQUARE FOOTAGE HAS CHANGED.REVISE
 ON PLANS.
  
 2.ROOF VENTILATION HAS BE REMOVED.
 SHOW HOW ROOF VENTILATION WILL BE
 COMPLETED.SUPPLY VENTILATIONS
 CALCULATIONS.
  
 3.ATTIC ACCESS HAS BEEN REMOVED.A-1
 HAS IT BEEN RELOCATED?
  
 4.NOT ALL REVISIONS HAVE BEEN CLEARLY
 MARKED.
  
 5.MEW DOORS AND WINDOWS HAVE BEEN
 ADDED.DO WE HAVE THE PRODUCT APPROVALS
 FOR THESE PRODUCTS ALREADY?
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-07-11 Cont ID  
Sent By alange Date 2005-07-11 Time 07:43 Rev Time 0.66
Received By alange Date 2005-07-11 Time 07:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-08 Cont ID  
Sent By alange Date 2005-07-08 Time 14:02 Rev Time 1.00
Received By alange Date 2005-07-08 Time 14:02 Sent To  
Notes
2005-07-08 00:00:00DENIED
  
 NEW COMMENT:
  
 PAGE A-5 ONE SET IS NOT SEALED.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-13 Cont ID  
Sent By alange Date 2005-06-13 Time 15:10 Rev Time 3.50
Received By alange Date 2005-06-13 Time 11:49 Sent To  
Notes
2005-06-13 00:00:00DENIED
  
 1.BUILDING VALUATION IS TOO LOW BASED
 ON SBCCI BUILDING VALUATION TABLES.
 6031SQ.FT. AC X $76.96 = $464,145.00
 1331SQ.FT. X $41.60 = $55,369.00
 TOTAL $519,515.00.ADDITIONAL PERMIT
 FEES OF $257.42 ARE DUE.
  
 2.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR FLAT ROOF, TILE ROOF,
 LINTELS AND OVERHEAD GARAGE DOOR.
  
 NOTE:ALL PRODUCT APPROVALS SUBMITTED
 WITH QUALITY ASSURANCE, MIAMI-DADE FOR
 EXAMPLE, REQUIRE THE FOLLOWING STATE
 APPROVAL TO BE ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3.SHOW HOW CHIMNEY WILL COMPLY WITH
 FBC 2113.
  
 4.OWNER/BUILDER APPLICATION WAS
 SUBMITTED.PLEASE SUPPLY AN APPROVED
 HOMESTEAD EXEMPTION.FS 489
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-03 Cont ID  
Sent By btrobaug Date 2006-02-03 Time 09:19 Rev Time 0.50
Received By btrobaug Date 2005-11-14 Time 06:41 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-06-23 Cont ID  
Sent By btrobaug Date 2005-06-23 Time 10:19 Rev Time 0.50
Received By btrobaug Date 2005-06-23 Time 07:49 Sent To P
Notes
2005-06-23 00:00:00 
  
 PROVISO
 ~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 ALONG WITH ANY REVISIONS, PRIOR TO ROUGH
 INSPECTION.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR
 MUST BE A MINIMUM OF #1/0 CU TO COMPLY
 WITH 250.66. THIS IS CRITICAL AT THE
 BEGINING STAGES OF THE JOB AS IT
 CONNECTS TO FOOTER STEEL.
  
 2} INDICATE THE SIZE OF THE GUTTER SHOWN
 ON THE RISER PER 366.6. ALSO SHOW
 DISCONNECT LOCATIONS ON THE DRAWING.
  
 3 THE 2" CONDUIT TO FPL IS TOO SMALL FOR
 THE CONDUCTORS LISTED. SEE TABLES. C-10
 IF PVC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-27 Cont ID  
Sent By btrobaug Date 2005-05-27 Time 11:08 Rev Time 0.75
Received By btrobaug Date 2005-05-27 Time 09:57 Sent To M
Notes
2005-05-27 00:00:00 
  
  
  
 1} PLEASE SUBMIT PANEL SCHEDULES WITH
 CIRCUIT DESIGNATIONS,OCP AND WIRE SIZE
 TO BRANCH CIRCUITS.
  
 2} THE 3-"MAIN BREAKER" 200AMP
 DISCONNECTS AS STATED ON THE RISER WOULD
 BE IN VIOLATION OF 310.15(B) FEEDING #1
 CONDUCTORS TO THE PANELS. PLEASE
 CLARIFY.
  
 3}INDICATE THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOE PER 250.66.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-10-22 Cont ID  
Sent By adarroug Date 2005-10-22 Time 12:12 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 12:12 Sent To E
Notes
2005-10-22 00:00:00TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-07 Cont ID  
Sent By adarroug Date 2005-09-07 Time 08:52 Rev Time 0.00
Received By adarroug Date 2005-09-07 Time 08:51 Sent To B
Notes
2005-09-07 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-08 Cont ID  
Sent By shill Date 2005-07-08 Time 08:08 Rev Time 0.00
Received By shill Date 2005-07-08 Time 08:08 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-11 Cont ID  
Sent By alange Date 2005-07-11 Time 07:43 Rev Time 0.00
Received By alange Date 2005-07-05 Time 15:39 Sent To  
Notes
2005-07-05 00:00:00TO "JLEECH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-06-27 Cont ID  
Sent By adarroug Date 2005-06-27 Time 11:05 Rev Time 0.00
Received By adarroug Date 2005-06-27 Time 11:05 Sent To B
Notes
2005-06-27 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-17 Cont ID  
Sent By shill Date 2005-06-17 Time 12:02 Rev Time 0.00
Received By shill Date 2005-06-17 Time 12:02 Sent To E
Notes
2005-06-17 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 14:18 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 14:18 Sent To E
Notes
2005-05-24 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-13 Cont ID  
Sent By adarroug Date 2005-05-13 Time 16:44 Rev Time 0.00
Received By adarroug Date 2005-05-13 Time 16:44 Sent To Z
Notes
2005-05-13 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-08 Cont ID  
Sent By rregueir Date 2005-07-08 Time 11:03 Rev Time 0.00
Received By rregueir Date 2005-07-08 Time 10:53 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-06-01 Cont ID  
Sent By hmoser Date 2005-06-01 Time 18:04 Rev Time 0.00
Received By hmoser Date 2005-05-29 Time 11:31 Sent To P
Notes
2005-05-29 00:00:00HAVE AIRCONDITIONING CONTRACTOR SUBMIT
 PLANS WITH APPLICATION.MANUAL (J) AND
 ENERGY CALCULATIONS ARE WITH MASTER
 PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-07-06 Cont ID  
Sent By jleech Date 2005-07-06 Time 07:36 Rev Time 0.50
Received By jleech Date 2005-07-06 Time 07:36 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-01 Cont ID  
Sent By jleech Date 2005-06-01 Time 17:10 Rev Time 0.50
Received By jleech Date 2005-06-01 Time 17:10 Sent To B
Notes
2005-06-01 00:00:00DENIED;
 COMPLETE NOTE 6 .
 ADD NOTE, 1/4" SLOPE PER FOOT REQUIRED
 ON UNDER GROUND PIPING. (MAX.OF 36
 FIXTURE UNITS PERMITED ON 1/8 " SLOPE
 PER FOOT).
 BATHROOM # 2 SHROWER NOT VENTED.
 BATHROOM # 4 TUB NOT VENTED.
 POOL HOUSE SHOWER NOT VENTED.
 SEE RED LINE DRAWING ONE SET.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status F Date 2005-09-12 Cont ID  
Sent By mmclean Date 2005-09-12 Time 17:52 Rev Time 0.00
Received By mmclean Date 2005-09-12 Time 17:52 Sent To  
Notes
2005-09-12 00:00:00DENIED,
 1. SEE STRUCTURAL NOTES REGARDING THE
 SQUARE FOOT CHANGE.
 2. MUST PROVIDE THE TWO CURRENT COPY OF
 SURVEY SHOWING THE NEW SETBACKS OR SHOW
 THE LOCATION OF THE CHANGES & INDICATE
 IF THE SETBACKS CHANGE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 05-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2005-05-20 Cont ID  
Sent By mmclean Date 2005-05-20 Time 09:01 Rev Time 0.00
Received By mmclean Date 2005-05-20 Time 09:01 Sent To I
Notes
2005-05-20 00:00:00NOTE: MUST PULL SEPERATE PERMIT FOR
 FENCE/WALL/COLUNMS/GATE WITH CITY OF
 WEST PALM BEACH UTILITY EASEMENT
 APPROVAL &
 BELLSOUTH/ADELPHIA/FPL/FLORIDA PUBLIC
 UTILTIES.
  
 NOTE: MUST PULL SEPERATE PERMIT FOR
 POOL/SPA/DECK.