Plan Review Details - Permit 05050466
Plan Review Stops For Permit 05050466
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-09-08 Cont ID  
Sent By jwitmer Date 2005-09-08 Time 09:23 Rev Time 0.33
Received By jwitmer Date 2005-09-08 Time 09:23 Sent To PC
Notes
2005-09-08 00:00:00REVISION# 3

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-07-29 Cont ID  
Sent By jwitmer Date 2005-07-29 Time 14:35 Rev Time 0.55
Received By jwitmer Date 2005-07-29 Time 14:35 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-19 Cont ID  
Sent By jwitmer Date 2005-07-19 Time 18:14 Rev Time 0.55
Received By jwitmer Date 2005-07-19 Time 18:14 Sent To  
Notes
2005-07-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05050466
 ADD: 4440 BEACON CIR
 CONT: ANDERSON-MOORE
 TEL: (561)753-7400
 *= 2001 FLORIDA BUILDING CODE * WEST
 PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)PROVIDENOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SHEETT INDICATES THIS TO BE A TYPE V
 UNPROTECTED BUILDING. SHEET 4 DETAIL "A"
 INDICATES THE WALL SUB-SHEATHING TO BE
 5/8" CDX PLYWOOD, TYPE V CONSTRUCTION
 DOES NOT HAVE COMBUSTIBLE WALLS.
  
 3)STUCCO VENNER WALLS REQUIRE A TERMITE
 INSPECTION ZONE: 1403.1.6 IN ORDER TO
 PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION,CLEARANCE BETWEEN
 EXTERIOR WALL COVERINGS(STUCCO) AND
 FINAL EARTH GRADE ON THEEXTERIOR OF A
 BUILDING SHALL NOT BE LESS THAN 6 INCHES
 (152 MM).
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-20 Cont ID  
Sent By jwitmer Date 2005-06-20 Time 11:57 Rev Time 1.22
Received By jwitmer Date 2005-06-20 Time 11:57 Sent To PC
Notes
2005-06-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05050466
 ADD: 4440 BEACON CIR
 CONT: ANDERSON-MOORE
 TEL: (561)753-7400
 *= 2001 FLORIDA BUILDING CODE * WEST
 PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDENOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SHEETT INDICATES THIS TO BE A TYPE IV
 UNPROTECTED BUILDING. SHEET 4 DETAIL "A"
 DOES NOT INDICATE THE WALL SUB-SHEATHING
 MATERIAL THAT WILL BE USED?
  
 3)STUCCO VENNER WALLS REQUIRE A TERMITE
 INSPECTION ZONE: 1403.1.6 IN ORDER TO
 PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION,CLEARANCE BETWEEN
 EXTERIOR WALL COVERINGS AND FINAL EARTH
 GRADE ON THEEXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152
 MM).
  
 4) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 6) SHEET A-4 PLANS INDICATE THE MAGNET
 WEIGHT TO BE APPROXIMATELY 48,000LBS,
 BUT THE SOILS MINIMUM BEARING CAPACITY
 IS NOT PROVIDED?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-06 Cont ID  
Sent By dpalmer Date 2005-07-06 Time 18:43 Rev Time 0.33
Received By dpalmer Date 2005-07-06 Time 18:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-20 Cont ID  
Sent By dpalmer Date 2005-05-20 Time 15:23 Rev Time 1.00
Received By dpalmer Date 2005-05-20 Time 15:23 Sent To  
Notes
2005-05-20 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED ON TITLE BLOCK FOR
 ARCHITECTUAL FIRM. PLEASE SEE FAC
 61G1-16.004 AND FS 481.219
 THIS IS FOR ARCH FIRM ONLY, NOT FOR ENG
 FIRM.
 PLEASE SEE SOME OF THE ARCHITECTUAL
 SHEETS IN EACH SET ARE NOT SEALED. SEE
 BLDG REVIEW COMMENTS.
 THE ABOVE IS REQUIRED OF ALL TRADES AND
 FOR ALL SHEETS WHEATHER OR NOT COMMENT
 IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE BE SURE ENGINEER OF
 RECORD SIGNS PLANS WITH SIGNATURE ON
 FILE.
 FS 471.025
  
 3)NOTE: PLEASE SEE 450.3 FOR MAX OCP FOR
 TRANSFORMER.
  
 4)NOTE:PLEASE ALSO CORRELATE CONDUCTORS
 FOR FEED TO TRANSFORMERS. SHOWS 1/0 FOR
 GRND?
  
 5)NOTE: PLEASE INDICATE ANY CONTINUOUS
 LAODS AT 125%. 215.3,230.42 ETC.
  
 6)NOTE: PLEASE SEE ANY POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 7)NOTE: PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING ME.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-07-13 Cont ID  
Sent By mwennerg Date 2005-07-13 Time 12:47 Rev Time 0.00
Received By mwennerg Date 2005-07-13 Time 12:47 Sent To  
Notes
2005-07-13 00:00:00******PROVISO******
  
 PLEASE SEE THAT COMPLIANCE WITH FS AND
 FAC REQUIREMENTS MUST BE MET. PLEASE SEE
 OTHER REVIEW COMMENTS FOR DETAILS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-05-31 Cont ID  
Sent By mwennerg Date 2005-05-31 Time 13:36 Rev Time 0.00
Received By mwennerg Date 2005-05-31 Time 13:19 Sent To  
Notes
2005-05-31 00:00:00****DENIED****
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS
 IN REGARDS TO FS AND FAC REQUIREMENTS.
  
 2) ALL LIFE SAFETY TO COMPLY WITH NFPA
 101, 2003 EDITION.
  
 3) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR THE FIRE ALARM AND FIRE
 SPRINKLER REMODEL IF APPLICABLE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-08-30 Cont ID  
Sent By adarroug Date 2005-08-30 Time 15:25 Rev Time 0.00
Received By adarroug Date 2005-08-30 Time 15:25 Sent To B
Notes
2005-08-30 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-29 Cont ID  
Sent By adarroug Date 2005-07-29 Time 11:45 Rev Time 0.00
Received By adarroug Date 2005-07-29 Time 11:45 Sent To B
Notes
2005-07-29 00:00:00TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-06-28 Cont ID  
Sent By adarroug Date 2005-06-28 Time 14:42 Rev Time 0.00
Received By adarroug Date 2005-06-28 Time 14:42 Sent To  
Notes
2005-07-01 00:00:00TO "COMM" BD#21
2005-06-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-20 Cont ID  
Sent By jwitmer Date 2005-06-20 Time 12:17 Rev Time 0.00
Received By jwitmer Date 2005-05-13 Time 16:43 Sent To  
Notes
2005-05-23 00:00:00TO "COMM" BD#17
2005-05-13 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-19 Cont ID  
Sent By jwitmer Date 2005-07-19 Time 18:24 Rev Time 0.33
Received By jwitmer Date 2005-07-19 Time 18:24 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-13 Cont ID  
Sent By pkrauss Date 2005-06-13 Time 07:39 Rev Time 0.55
Received By pkrauss Date 2005-06-13 Time 07:39 Sent To  
Notes
2005-06-13 00:00:00DENIED:
 1.PLANS ARE TO HAVE A SIGNATURE AND
 NOT INITIALED OF THE ENGINEER OF RECORD
 IN ACCORDANCE WITH FS471.025 & FAC
 61G15-23.002.
  
 2.PLAN SHEET M5.1 INDICATES AHU
 SUPPORTED FROM THE BOTTOM OF THE BAR
 JOIST.PLEASE HAVE THE STRUCTURAL
 ENGINEER INDICATE IF THIS APPLICATION IS
 ALLOWED WITH THIS PARTICULAR JOIST/TRUSS
 SYSTEM.
  
 SEE ALSO COMMENT #1 BY DEWEY PALMER,
 ELECTRICAL PLAN REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-18 Cont ID  
Sent By pschmitz Date 2005-06-18 Time 10:04 Rev Time 0.00
Received By pschmitz Date 2005-06-18 Time 10:04 Sent To B
Notes
***NONE***