Plan Review Details - Permit 05050439
Plan Review Stops For Permit 05050439
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-04 Cont ID  
Sent By shill Date 2005-08-04 Time 16:38 Rev Time 0.50
Received By shill Date 2005-08-04 Time 16:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-24 Cont ID  
Sent By shill Date 2005-07-24 Time 00:10 Rev Time 0.50
Received By shill Date 2005-07-24 Time 00:10 Sent To  
Notes
2005-07-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
  
 1.)SEE PREVIOUS LIST.TITLE BLOCK TO
 COMPLY WITH FAC61G1-16.004. THIS APPLIES
 TO SHEETS CW1 THROUGH CW5.
  
 2.)WHEN RESUBMITTING, REPLACE SHEETS
 WHICH HAVE CHANGED AND SUBMIT OLD SHEETS
 SEPARATELY.THERE SHOULD BE TWO
 COMPLETE COLLATED STAPLED SETS
 SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-15 Cont ID  
Sent By shill Date 2005-06-15 Time 07:46 Rev Time 1.50
Received By shill Date 2005-06-15 Time 07:46 Sent To  
Notes
2005-06-15 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)TITLE BLOCK IS TO BE IN COMPLIANCE
 WITH FAC61G1-16.003, 004.
  
 2.)M OCCUPANCY IS DECLARED.CAR WASH
 IS BUSINESS FBC305.OCCUPANCY
 SEPARATION WOULD BE REQUIRED FBC TABLE
 704.1.PLEASE CLARIFY OCCUPANCY AND
 SHOW CODE COMPLIANCE ON THE PLAN.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-08-03 Cont ID  
Sent By dpalmer Date 2005-08-03 Time 12:53 Rev Time 0.30
Received By dpalmer Date 2005-08-03 Time 12:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-26 Cont ID  
Sent By dpalmer Date 2005-07-26 Time 07:11 Rev Time 0.33
Received By dpalmer Date 2005-07-26 Time 07:04 Sent To  
Notes
2005-07-26 00:00:00********** UNSAT 2ND REVIEW **********
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 PERTAINING TO MISSING INFORMATION
 REQUIRED ON TITLE BLOCK FOR ARCHITECT.
 PLEASE SEE FAC 61G1-16.004,WHICH
 REQUIRES THE PRINTED NAME AND LICENSE #
 OF ARCHITECT.
 PLEASE SEE ELECTRICAL SHEET CW-6
 CONTAINS ARCHITECT'S TITLE BLOCK,
 THEREFORE THIS SHOULD ALSO CONTAI THE
 SAME.
 PLEASE SEE ARCHITECT OF RECORD IS SIGNED
 AND SEALED ON CW-6.
 AS BLDG REVIEW COMMENTS, THIS APPLYS TO
 ALL SHEETS AND FOR ALL TRADES WHEATHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 ANY REPLACED SHEETS WILL BE REQUIRED TO
 BE STAMPED BY ALL TRADES ON REVIEW.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-20 Cont ID  
Sent By dpalmer Date 2005-05-20 Time 12:41 Rev Time 1.50
Received By dpalmer Date 2005-05-20 Time 12:18 Sent To  
Notes
2005-05-20 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002
 WHICH REQUIRES THE "PRINTED NAME AND
 LICENSE #" OF PE.
  
 2)NOTE: PLEASE SEE ON ORIGINAL PLANS THE
 EQUIPMENT GROUNDING WHICH IS INSTALLED
 AFFTER THE FIRST MEANS OF DISC PER
 250.24 WAS REMOVED, HOWEVER THIS SET OF
 PLANS SHOWS THE CONDUCTORS INSTALLED FOR
 "EXISTING SERVICE".
 250.6,250.24
  
 3)NOTE: PLEASE AN EQUIPMENT GROUNDING
 APPEARS TO BE SHOWN AFTER THE MEANS OF
 DISC TO PANEL "CW", HOWEVER RISER DOES
 NOT INCLUDE EQUIPMENT GRND THROUGH TO
 PANEL??
 250.110,250.122
  
 4)NOTE: PLEASE CLARIFY RISER SHOWS A
 GROUNDING ATTACHMENT AT PANEL "CW",
 HOWEVER NO CONNECTION POINTS ARE SHOWN.?
 250.50?
  
 5)NOTE: PLEASE PROVIDE/CLARIFY IF LOAD
 FOR PANEL "CW" WAS INCLUDED ON EXSITING
 SERVICE UNDER PERMIT FOR GAS STATION/
 CONV STORE.
 215.5,220
  
 6)NOTE: PLEASE SEE SHEETS DONE BY THE
 ENGINEER ARE ALSO SIGNED AND SEALED BY
 THE ARCH?
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHALL BE
 SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-06-01 Cont ID  
Sent By mwennerg Date 2005-06-01 Time 15:14 Rev Time 0.00
Received By mwennerg Date 2005-06-01 Time 15:14 Sent To  
Notes
2005-06-01 00:00:00****PROVISO****
  
 PLEASE SEE ELECTRICAL REVIEW COMMENTS IN
 REGARDS TO FS AND FAC REQUIREMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 18:39 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 18:39 Sent To  
Notes
2005-08-02 00:00:00TO "COMM" BD#50
2005-07-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 11:16 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 11:16 Sent To  
Notes
2005-07-21 00:00:00TO "COMM" BD#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-16 Cont ID  
Sent By shill Date 2005-06-16 Time 10:18 Rev Time 0.00
Received By shill Date 2005-05-12 Time 14:12 Sent To PC
Notes
2005-05-23 00:00:00TO "COMM" BD#55
2005-05-12 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-06-13 Cont ID  
Sent By pkrauss Date 2005-06-13 Time 19:38 Rev Time 0.20
Received By pkrauss Date 2005-06-13 Time 19:35 Sent To  
Notes
2005-06-13 00:00:00CAR WASH
 NO MECHANICAL WORK OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-16 Cont ID  
Sent By pschmitz Date 2005-06-16 Time 09:30 Rev Time 0.00
Received By pschmitz Date 2005-06-16 Time 09:29 Sent To  
Notes
2005-06-16 00:00:00PLUMBING PLAN REVIEW FBC 2001
 PROVISO:PASS, PENDING BUILDING PLAN
 REVIEW COMMENTS.
 QUESTIONS PAUL SCHMITZ 561-805-6692

Review Stop Z ZONING
Rev No 1 Status P Date 2005-06-06 Cont ID  
Sent By jlong Date 2005-06-06 Time 12:00 Rev Time 0.33
Received By jlong Date 2005-06-06 Time 12:00 Sent To  
Notes
***NONE***