Plan Review Details - Permit 05050427
Plan Review Stops For Permit 05050427
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-08-09 Cont ID  
Sent By jwitmer Date 2005-08-09 Time 07:46 Rev Time 0.77
Received By jwitmer Date 2005-08-09 Time 06:56 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-07-07 Cont ID  
Sent By lsmith Date 2005-07-07 Time 15:01 Rev Time 0.75
Received By lsmith Date 2005-07-07 Time 15:01 Sent To  
Notes
2005-07-07 00:00:00BUILDING PLAN REVIEW: FAILED:
  
 1. ACCORDING TO MARSHALL/SWIFT COST
 GUIDE THE COST OF THE POOL HAS BEEN
 ADJUSTED TO $51575.ADD'L FEES ARE DUE
 BEFORE RESUBMITTING FOR PERMIT.
  
 2. POOL DATA SHOWS 2 1/2 HP POOL PUMP,
 HEAT PUMP, 3 POOL LIGHTS.
  
 3.PAGE 2 OF DRAWINGS (SIGNED 7 SEALED BY
 ENGINEER) SHOW HEAT PUMPS ON PIPING
 ISOMETRIC & ELECTRIC RISER PLAN.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-01 Cont ID  
Sent By lsmith Date 2005-06-01 Time 15:07 Rev Time 1.00
Received By lsmith Date 2005-06-01 Time 15:07 Sent To  
Notes
2005-06-01 00:00:00BUILDING PLAN REVIEW: FAILED
  
  
 1.104.6.5 BUILDING PERMIT VALUATION.
 IF IN THE OPINION OF THE BUILDING
 OFFICIAL THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED ESTIMATES AND/OR BONA FIDED
 SIGNED CONTRACTS (EXCLUDING LAND VALUE)
 TO MEET THE APPROVAL OF THE BUILDING
 OFFICIAL. FOR PERMITTING PURPOSES,
 VALUATION FOR BUILDINGS AND SYSTEMS
 SHALL BE FOUND IN MARSHALL AND SWIFT OR
 THE SOUTHERN BUILDING CODE CONGRESS
 INTERNATIONAL VALUATION TABLES, LATEST
 EDITION, AND SHALL BE BASED ON TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, OVERHEAD AND PROFIT,
 EXCLUDING ONLY LAND VALUE.
  
 2. SUBMIT DOCUMENTS VERIFYING OWNERS OF
 PROPERTY, WARRENTY DEED, HOMESTEAD
 EXEMPTION, ETC.
  
 3. SHOW SQ. FT. OF DECK ON POOL DATA
 SHEET.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-07-26 Cont ID  
Sent By btrobaug Date 2005-07-26 Time 13:39 Rev Time 1.00
Received By btrobaug Date 2005-07-26 Time 12:02 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-07-20 Cont ID  
Sent By btrobaug Date 2005-07-20 Time 13:58 Rev Time 0.50
Received By btrobaug Date 2005-07-20 Time 13:44 Sent To B
Notes
2005-07-20 00:00:00 
 SAME COMMENTS AS PREVIOUS TWO REVIEWS:
 PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDU
 IT SIZE AND TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
  
 THE ENGINEERING FIRMS NUMBER,
 (CERTIFICATE OF AUTHORIZATION)MUST BE ON
 THE TITLE BLOCK PER 61G15.23.003 FAC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-07-11 Cont ID  
Sent By btrobaug Date 2005-07-11 Time 17:11 Rev Time 0.33
Received By btrobaug Date 2005-07-11 Time 14:11 Sent To PC
Notes
2005-07-11 00:00:00 
 SAME COMMENTS AS PREVIOUS TWO REVIEWS:
 PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDU
 IT SIZE AND TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
  
 ALSO THE SCHEMATIC INDICATES A HEAT
 PUMP, THE SUBMITTALS ARE FOR A GAS
 HEATER. PLEASE CLARIFY.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-06-11 Cont ID  
Sent By btrobaug Date 2005-06-11 Time 12:15 Rev Time 0.33
Received By btrobaug Date 2005-06-11 Time 12:04 Sent To P
Notes
2005-06-11 00:00:00 
 SAME COMMENTS AS PREVIOUS REVIEW:
 PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDU
 IT SIZE AND TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
  
 ALSO THE SCHEMATIC INDICATES A HEAT
 PUMP, THE SUBMITTALS ARE FOR A GAS
 HEATER. PLEASE CLARIFY.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-23 Cont ID  
Sent By btrobaug Date 2005-05-23 Time 07:36 Rev Time 0.33
Received By btrobaug Date 2005-05-23 Time 07:08 Sent To P
Notes
2005-05-23 00:00:00 
 PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDU
 IT SIZE AND TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
 IF AN ELECTRIC HEATER IS TO BE INSTALLED
 PLEASE SUBMIT CALCULATIONS FOR THE MAIN
 SERVICE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-26 Cont ID  
Sent By adarroug Date 2005-07-26 Time 11:35 Rev Time 0.00
Received By adarroug Date 2005-07-26 Time 11:35 Sent To E
Notes
2005-07-26 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-07-18 Cont ID  
Sent By adarroug Date 2005-07-18 Time 11:49 Rev Time 0.00
Received By adarroug Date 2005-07-18 Time 11:49 Sent To E
Notes
2005-07-18 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-07-11 Cont ID  
Sent By adarroug Date 2005-07-11 Time 10:44 Rev Time 0.00
Received By adarroug Date 2005-07-11 Time 10:44 Sent To B
Notes
2005-07-11 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 17:54 Rev Time 0.00
Received By shill Date 2005-06-08 Time 17:54 Sent To E
Notes
2005-06-08 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-20 Cont ID  
Sent By adarroug Date 2005-05-20 Time 14:13 Rev Time 0.00
Received By adarroug Date 2005-05-20 Time 14:12 Sent To E
Notes
2005-05-20 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-10 Cont ID  
Sent By adarroug Date 2005-05-10 Time 15:36 Rev Time 0.00
Received By adarroug Date 2005-05-10 Time 15:35 Sent To Z
Notes
2005-05-10 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-07-26 Cont ID  
Sent By jleech Date 2005-07-26 Time 14:10 Rev Time 0.50
Received By jleech Date 2005-07-26 Time 14:10 Sent To B
Notes
2005-07-26 00:00:00PLANS REVISED SPA PUMP ADDED

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-06-22 Cont ID  
Sent By jleech Date 2005-06-22 Time 19:12 Rev Time 0.50
Received By jleech Date 2005-06-22 Time 19:12 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-05-28 Cont ID  
Sent By btrobaug Date 2005-05-23 Time 07:36 Rev Time 0.50
Received By kstevens Date 2005-05-28 Time 05:57 Sent To B
Notes
2005-05-28 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 1. FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 2. FBC-2001424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN THE PUMP IS
 SHUT OFF. (MANUF. SPECIFICATION SHEETS
 SUBMITTAL).
 3. PROVIDE SETS OF PLANS, LOOSE SHEETS
 ARE NOT ACCEPTABLE. SECTIONS 104.2.1,
 AND 104.2.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2005-05-19 Cont ID  
Sent By mmclean Date 2005-05-19 Time 12:00 Rev Time 0.00
Received By mmclean Date 2005-05-19 Time 12:00 Sent To I
Notes
***NONE***