| Plan Review Stops For Permit 05050427 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-08-09 |
Time |
07:46 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2005-08-09 |
Time |
06:56 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-07-07 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2005-07-07 |
Time |
15:01 |
Rev Time |
0.75 |
| Received By |
lsmith |
Date |
2005-07-07 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2005-07-07 00:00:00 | BUILDING PLAN REVIEW: FAILED: | | | | | | 1. ACCORDING TO MARSHALL/SWIFT COST | | | GUIDE THE COST OF THE POOL HAS BEEN | | | ADJUSTED TO $51575.ADD'L FEES ARE DUE | | | BEFORE RESUBMITTING FOR PERMIT. | | | | | | 2. POOL DATA SHOWS 2 1/2 HP POOL PUMP, | | | HEAT PUMP, 3 POOL LIGHTS. | | | | | | 3.PAGE 2 OF DRAWINGS (SIGNED 7 SEALED BY | | | ENGINEER) SHOW HEAT PUMPS ON PIPING | | | ISOMETRIC & ELECTRIC RISER PLAN. | | | | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-06-01 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2005-06-01 |
Time |
15:07 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
2005-06-01 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2005-06-01 00:00:00 | BUILDING PLAN REVIEW: FAILED | | | | | | | | | 1.104.6.5 BUILDING PERMIT VALUATION. | | | IF IN THE OPINION OF THE BUILDING | | | OFFICIAL THE CLAIMED VALUATION OF | | | BUILDING, ALTERATION, STRUCTURE, | | | ELECTRICAL, GAS, MECHANICAL OR PLUMBING | | | SYSTEMS APPEARS TO BE UNDERESTIMATED ON | | | THE APPLICATION, THE PERMIT SHALL BE | | | DENIED, UNLESS THE APPLICANT CAN SHOW | | | DETAILED ESTIMATES AND/OR BONA FIDED | | | SIGNED CONTRACTS (EXCLUDING LAND VALUE) | | | TO MEET THE APPROVAL OF THE BUILDING | | | OFFICIAL. FOR PERMITTING PURPOSES, | | | VALUATION FOR BUILDINGS AND SYSTEMS | | | SHALL BE FOUND IN MARSHALL AND SWIFT OR | | | THE SOUTHERN BUILDING CODE CONGRESS | | | INTERNATIONAL VALUATION TABLES, LATEST | | | EDITION, AND SHALL BE BASED ON TOTAL | | | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR | | | FINISH, NORMAL SITE WORK (EXCAVATION AND | | | BACKFILL FOR BUILDINGS), ARCHITECTURAL | | | AND DESIGN FEES, OVERHEAD AND PROFIT, | | | EXCLUDING ONLY LAND VALUE. | | | | | | 2. SUBMIT DOCUMENTS VERIFYING OWNERS OF | | | PROPERTY, WARRENTY DEED, HOMESTEAD | | | EXEMPTION, ETC. | | | | | | 3. SHOW SQ. FT. OF DECK ON POOL DATA | | | SHEET. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2005-07-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-07-26 |
Time |
13:39 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2005-07-26 |
Time |
12:02 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2005-07-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-07-20 |
Time |
13:58 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-07-20 |
Time |
13:44 |
Sent To |
B |
|
| Notes |
| 2005-07-20 00:00:00 | | | | SAME COMMENTS AS PREVIOUS TWO REVIEWS: | | | PLEASE SUBMIT DETAILS FOR THE PANEL | | | SHOWN ON THE SCHEMATIC, FEEDER AND CONDU | | | IT SIZE AND TYPE, PANEL RATING AND OCP, | | | PANEL SCHEDULE AND COMPUTED LOAD, ETC. | | | | | | THE ENGINEERING FIRMS NUMBER, | | | (CERTIFICATE OF AUTHORIZATION)MUST BE ON | | | THE TITLE BLOCK PER 61G15.23.003 FAC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2005-07-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-07-11 |
Time |
17:11 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2005-07-11 |
Time |
14:11 |
Sent To |
PC |
|
| Notes |
| 2005-07-11 00:00:00 | | | | SAME COMMENTS AS PREVIOUS TWO REVIEWS: | | | PLEASE SUBMIT DETAILS FOR THE PANEL | | | SHOWN ON THE SCHEMATIC, FEEDER AND CONDU | | | IT SIZE AND TYPE, PANEL RATING AND OCP, | | | PANEL SCHEDULE AND COMPUTED LOAD, ETC. | | | | | | ALSO THE SCHEMATIC INDICATES A HEAT | | | PUMP, THE SUBMITTALS ARE FOR A GAS | | | HEATER. PLEASE CLARIFY. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2005-06-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-06-11 |
Time |
12:15 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2005-06-11 |
Time |
12:04 |
Sent To |
P |
|
| Notes |
| 2005-06-11 00:00:00 | | | | SAME COMMENTS AS PREVIOUS REVIEW: | | | PLEASE SUBMIT DETAILS FOR THE PANEL | | | SHOWN ON THE SCHEMATIC, FEEDER AND CONDU | | | IT SIZE AND TYPE, PANEL RATING AND OCP, | | | PANEL SCHEDULE AND COMPUTED LOAD, ETC. | | | | | | ALSO THE SCHEMATIC INDICATES A HEAT | | | PUMP, THE SUBMITTALS ARE FOR A GAS | | | HEATER. PLEASE CLARIFY. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-05-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-05-23 |
Time |
07:36 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2005-05-23 |
Time |
07:08 |
Sent To |
P |
|
| Notes |
| 2005-05-23 00:00:00 | | | | PLEASE SUBMIT DETAILS FOR THE PANEL | | | SHOWN ON THE SCHEMATIC, FEEDER AND CONDU | | | IT SIZE AND TYPE, PANEL RATING AND OCP, | | | PANEL SCHEDULE AND COMPUTED LOAD, ETC. | | | IF AN ELECTRIC HEATER IS TO BE INSTALLED | | | PLEASE SUBMIT CALCULATIONS FOR THE MAIN | | | SERVICE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-07-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-26 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-26 |
Time |
11:35 |
Sent To |
E |
|
| Notes |
| 2005-07-26 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-07-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-18 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-18 |
Time |
11:49 |
Sent To |
E |
|
| Notes |
| 2005-07-18 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-07-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-11 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-11 |
Time |
10:44 |
Sent To |
B |
|
| Notes |
| 2005-07-11 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-06-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-08 |
Time |
17:54 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-08 |
Time |
17:54 |
Sent To |
E |
|
| Notes |
| 2005-06-08 00:00:00 | TO BT DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-05-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-20 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-20 |
Time |
14:12 |
Sent To |
E |
|
| Notes |
| 2005-05-20 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-05-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-10 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-10 |
Time |
15:35 |
Sent To |
Z |
|
| Notes |
| 2005-05-10 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2005-07-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-07-26 |
Time |
14:10 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-07-26 |
Time |
14:10 |
Sent To |
B |
|
| Notes |
| 2005-07-26 00:00:00 | PLANS REVISED SPA PUMP ADDED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2005-06-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-06-22 |
Time |
19:12 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2005-06-22 |
Time |
19:12 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-05-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-05-23 |
Time |
07:36 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2005-05-28 |
Time |
05:57 |
Sent To |
B |
|
| Notes |
| 2005-05-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | FBC-2001 CHAPTER 1 | | | | | | 1. FBC-2001 424.2.14.1 SWIMMING POOL | | | WATER HEATERS SHALL BEAR THE LABEL OF A | | | RECOGNIZED TESTING AGENCY. MANUFACTURE | | | SHEETS REQUIRED. (SUBMITTAL) | | | 2. FBC-2001424.2.14.2 WATER RETENTION, | | | PROVIDE A POSITIVE MEANS OF RETAINING | | | WATER IN THE HEATER WHEN THE PUMP IS | | | SHUT OFF. (MANUF. SPECIFICATION SHEETS | | | SUBMITTAL). | | | 3. PROVIDE SETS OF PLANS, LOOSE SHEETS | | | ARE NOT ACCEPTABLE. SECTIONS 104.2.1, | | | AND 104.2.1.3. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-05-19 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-05-19 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-05-19 |
Time |
12:00 |
Sent To |
I |
|
| Notes |
|
|