Plan Review Details - Permit 05050326
Plan Review Stops For Permit 05050326
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-07-21 Cont ID  
Sent By jhiggins Date 2005-07-21 Time 10:57 Rev Time 0.00
Received By jhiggins Date 2005-07-21 Time 10:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-10-13 Cont ID  
Sent By shill Date 2005-10-13 Time 08:52 Rev Time 0.50
Received By shill Date 2005-10-13 Time 08:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-09-07 Cont ID  
Sent By shill Date 2005-09-07 Time 11:23 Rev Time 1.00
Received By shill Date 2005-09-07 Time 11:23 Sent To  
Notes
2005-09-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 FROM PREVIOUS TWO REVIEWS; NUMBERS
 STAYING THE SAME FOR CONSISTENCY:
  
 7.)ALTERATIONS SHALL COMPLY WITH
 FBC11-4.1.6(1); DOORS 11.4.13, TURNING
 SPACE AND REACH RANGES, FBC11-4.2.4.
 NOTE THAT THREE DIFFERENT LEVELS OF
 SERVICE ARE OFFERED (TANNING BED, SUN
 CAPSULE, SPRAY BOOTH).
 FOUR DIFFERENT LEVELS OF SERVICE ARE
 OFFERED AS PER CONVERSATION WITH
 DESIGNER.ONLY TWO ARE ACCESSIBLE ON
 THE REVISED PLAN.
  
 8.)SHOW THE CLEAR FLOOR SPACE FOR THE
 SINK, FBC11-4.24.5.
 THIS WAS ADDRESSED BY SHOWING CLEAR
 FLOOR SPACE IN THE LAUNDRY.THIS IS A
 WORK AREA NOT REQUIRED TO BE ACCESSIBLE
 BUT YOU CAN MAKE IT ACCESSIBLE IF YOU
 WOULD LIKE.HOWEVER, THE BATHROOM IS
 REQUIRED TO BE ACCESSIBLE.PLEASE SHOW
 THE CLEAR FLOOR SPACE AT THE BATHROOM
 SINK.
  
 SEE ATTACHED FS553.80(2)(B).A 4X PLAN
 REVIEW FEE WILL BE CHARGED IF THE
 COMMENTS ARE NOT ADDRESSED A THIRD TIME.
 **NOTE - FEE CHARGED AS PER
 FS553-80(2)(B).**THE FEE WILL BE
 CHARGED ON NEXT REVIEW IF THE COMMENTS
 ARE NOT ADDRESSED.
  
 NO RESUB FEE (ONLY 4X FEE)
  
 PLEASE TAKE PLANS TO PALM BEACH COUNTY
 FOR IMPACT FEE REVIEW (CHANGE OF USE),
 561-233-5025.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-15 Cont ID  
Sent By shill Date 2005-08-15 Time 10:48 Rev Time 2.00
Received By shill Date 2005-08-11 Time 07:34 Sent To  
Notes
2005-08-15 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 FROM PREVIOUS REVIEW; NUMBERS STAYING
 THE SAME FOR CONSISTENCY:
  
 2.)THE TITLE BLOCK AND SEAL ARE TO
 COMPLY WITH FAC61G1-16.004 (ARCHITECTS
 AND INTERIOR DESIGNERS).
  
 THE CA NUMBER FOR THE STORETECH IS
 APPLIED FOR BUT NOT APPROVED ON THE
 STATE WEBSITE.NO CA NUMBER WAS
 PROVIDED FOR GUILLERMO RAMON GONZALEZ PA
 AND I WAS UNABLE TO FIND ONE ON THE
 STATE WEBSITE, MYFLORIDALICENSE.COM.
  
 7.)ALTERATIONS SHALL COMPLY WITH
 FBC11-4.1.6(1); DOORS 11.4.13, TURNING
 SPACE AND REACH RANGES, FBC11-4.2.4.
 NOTE THAT THREE DIFFERENT LEVELS OF
 SERVICE ARE OFFERED (TANNING BED, SUN
 CAPSULE, SPRAY BOOTH).
  
 8.)SHOW THE CLEAR FLOOR SPACE FOR THE
 SINK, FBC11-4.24.5.
  
 SEE ATTACHED FS553.80(2)(B).A 4X PLAN
 REVIEW FEE WILL BE CHARGED IF THE
 COMMENTS ARE NOT ADDRESSED A THIRD TIME.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 07:35 Rev Time 3.00
Received By shill Date 2005-06-10 Time 07:35 Sent To  
Notes
2005-06-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)THE TITLE BLOCK AND SEAL ARE TO
 COMPLY WITH FAC61G1-16.004 (ARCHITECTS
 AND INTERIOR DESIGNERS).
  
 3.)PLEASE CLARIFY AS TO WHY YOU HAVE
 DECLARED A MERCANTILE OCCUPANCY RATHER
 THAN BUSINESS.SEE FBC CHAPTER 3.
  
 4.)SHOW EXITING INFORMATION.ONE EXIT
 IS SHOWN TO THE OUTSIDE.TWO OTHER
 EXITS ARE SHOWN BUT IT IS NOT CLEAR AS
 TO WHERE THEY LEAD OR TRAVEL DISTANCE.
 FBC1001.1.3.
  
 5.)MINIMUM INTERIOR FINISH
 CLASSIFICATION TO COMPLY WITH TABLE
 803.3.
  
 6.)THE SERVICE COUNTER IS TO COMPLY
 WITH FBC11-7.2(2).
  
 7.)ALTERATIONS SHALL COMPLY WITH
 FBC11-4.1.6(1); DOORS 11.4.13, TURNING
 SPACE AND REACH RANGES, FBC11-4.2.4.
 NOTE THAT THREE DIFFERENT LEVELS OF
 SERVICE ARE OFFERED (TANNING BED, SUN
 CAPSULE, SPRAY BOOTH).
  
 8.)SHOW THE CLEAR FLOOR SPACE FOR THE
 SINK, FBC11-4.24.5.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-02-15 Cont ID  
Sent By dpalmer Date 2006-02-15 Time 13:34 Rev Time 0.00
Received By dpalmer Date 2006-02-15 Time 13:34 Sent To P
Notes
2006-02-15 00:00:00REV TO ADD JOXES IN FEEDERS TO UNIT
 ONLY.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-10-03 Cont ID  
Sent By dpalmer Date 2005-10-03 Time 11:11 Rev Time 0.50
Received By dpalmer Date 2005-10-03 Time 10:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-09-04 Cont ID  
Sent By dpalmer Date 2005-09-04 Time 13:59 Rev Time 1.33
Received By dpalmer Date 2005-09-04 Time 13:41 Sent To  
Notes
2005-09-04 00:00:00********** UNSAT 3RD REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND PLEASE SEE SOME NEW NOTES DUE
 TO CHANGES IN PLANS ONCE AGAIN.
  
  
 1)NOTE: PLEASE SEE PLANS NOW HAVE
 REVISED TITLE BLOCKS SIGNED AND SEALED
 BY AN ENGINEER, HOWEVER PLEASE SEE SOME
 ELECTRICAL SHEETS CONTAIN THE PRINTED
 ENGINEER OF RECORD TO BE GUILLERMO NUNEZ
 AND PLANS ARE SIGNED AND SEALED BY A
 DIFFERENT ENGINEER???
 PLEASE SEE FAC 61G15-23.002 FOR REQUIRED
 INFORMATION TO BE ON TITLE BLOCKS.
 ***************************************
 PLEASE ALSO SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED FOR
 ENGINEERING FIRM AS SHOWN. FS 471.023
 PLEASE KNOW, TITLE BLOCKS ARE REQUIRED
 TO BE CORRECTED FOR ALL SHEETS AND FOR
 ALL TRADES, WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
 PLEASE SEE A SIGNED, DATED AND SEALED
 LETTER FROM ARCHITECT WAS NOT SUBMITTED
 AS PREVIOUSLY REQUESTED.
 NOTORY SHOULD BE SURE TO NOTORIZE LETTER
 AS REQUIRED UNDER FS 117.05
 (SEE NOTE #2)
  
 ***************************************
  
 PLEASE SEE ONE ENTIRE SET OF PLANS (ALL
 TRADES) IS BEING RETAINED AND WILL NOW
 BE TURNED OVER TO THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS ANDSTATES LEGAL
 COUNSEL TO THE FLORIDA BOARD OF
 ARCHITECTS FOR REVIEW OF LICENSING
 DISCREPANCIES AND CODE COMPLIANCE.
 PLEASE SEE A REVIEW MAY ALSO BE DONE FOR
 PLANS AND CODE COMPLIANCE INFORMATION.
 PLEASE SEE THE FOLLOWING COMMENT.
  
 ****************************************
  
 2)NOTE: PLEASE SEE THAT NOTES WERE GIVEN
 BY MULTIPLE REVIEWERS ON PREVIOUS REVIEW
 WITH REFERENCE TO FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS AND
 PLANS BEING REVIEWED THREE OR MORE TIMES
 WITH ANY OF THE SAME COMMENTS NOT BEING
 ADDRESSED. PLEASE SEE COMMENTS BELOW AS
 SOME COMMENTS FROM PREVIOUS TWO REVIEWS
 STILL NEED TO BE ADDRESSED. PLEASE SEE
 THAT A 4X FEE HAS NOW BEEN ASSESSED FOR
 PLAN REVIEW PER ABOVE MENTIONED FS
 553.80 AND A FEE OF $1500.00 MUST BE
 PAID BEFORE THE PLANS MAY BE SUBMITTED
 FOR NEXT REVIEW.
 PLEASE KNOW, IF PLANS COME BACK IN FOR
 4TH REVIEW WITH ANY OF THE SAME COMMENTS
 FROMPREVIOUS 3 REVIEWS NOT ADDRESSED
 AN ADDTIONAL 4X FEE WILL BE ASSESSED.
 THIS STANDS FOR ALL REVIEWS AFTER 3RD
 SUCH REVIEW.
  
 2)NOTE: PLEASE PROVIDE A SIGNED, DATED
 AND SEALED NOTORIZED LETTER FOR LEGAL
 SIGNATURE VERIFICATION OF ARCHITECT.
 OTHER SHEETS APPEAR TO BE SIGNED WITH
 INITIALS, IF INDEED THIS IS THE LEGAL
 SIGNATURE, PLEASE PROVIDE LETTER AS
 STATED ABOVE. PLEASE BE SURE LETTER IS
 PROPERLY NOTORIZED AS REQUIRED UNDER FS
 117.
  
 3)NOTE:PLEASE SHOW LOCATION OF
 EXISTING SERVICE ON "SERVICE POWER SITE
 PLAN".
 PLEASE SEE THE "SITE POWER PLAN" HAS NOW
 BEEN REMOVED AND GROUPING OF MAINS CAN
 NOT BE VERIFIED AT THIS TIME.
 PLEASE SEE GROUPING OF MAINS WILL BE
 REQUIRED 230.72.
  
 4)NOTE: PLEASE SEE THAT SERVICE IS NOW
 INDICATING A NEW 600A SERVICE, MAIN DISC
 AND PANEL.
 PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS FROM 600A MAIN TO 600A PANEL.
 PLEASE SEE 250.122 FOR SIZING FOR EACH
 OF THE THREE PARALLEL RUNS SHOWN.
 250.110
 PLEASE ALSO SEE MISSING EQUIPMENT
 GROUNDING METHOD TO SUB PANEL "B".
 *NOTE*EMT MAY NOT BE USEDAS AN
 EQUIPMENT GROUNDING METHID UNLESS ALL
 FITTINGS USEDARE THE NEW FITTINGS NOW
 LISTED AS APPROVED FOR "EQUIPMENT
 GROUNDING"
  
 5)NOTE: PLEASE CORRELATE AWG SHOWN FOR
 SAME SUB FEED TO PANEL "B". #3, #1?
 240.4,310.16,215.5
  
 6)NOTE: PLEASE SEE SPECS/MANUFACTURE
 SHEETS FOR ALL TANNING BEDS/ EQUIPMENT
 PROPOSED WAS NOT SUBMITTED FOR REVIEW OF
 THE LISTINGS REQUIRED PER NEC 110.3B,
 ALL LISTINGS MUST BE BY A NATIONAL
 RECOGNIZED TESTING LABORATORY. (NRTL).
 PLANS MENTIONS INSTALLATION OF
 TRANSFORMER FOR THIS EQUIPMENT, HOWEVER
 THIS IS NOT SHOWN ON PLANS AND EQUIPMENT
 CAN NOT BE VERIFIED FOR INSTALLATION.
  
 7)NOTE: PLEASE SEE 250.50, PLEASE SHOW
 COLD WATER PIPE PART OF GROUNDING
 ELECTRODE SYSTEM. (IF METAL) RISER SHOWS
 A CONNECTION, HOWEVER THIS IS NOT CLEAR
 OR LABELED AS TO WHAT CONNECTION THIS
 MAY BE.
 PLANS MENTIONS TO EXISTING GROUNDING
 ELECTRODE SYSTEM, YET THIS CAN NOT
 VERIFIED AS NO DETAIL AS REQUIRED PER
 250.50 IS SHOWN.
 PLEASE SEE FBC 104.2.1 WHICH STATES
 "TECHNICAL CODES SHALL NOT BE QUOTED IN
 LEIU OF PLANS/DETAILS"
  
  
 8)NOTE: PLEASE SEE ON TWO PREVIOUS
 REVIEWS, IT WAS REQUESTED TO "REMOVE ALL
 OLD/VOIDED SHEETS" AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE SEE ALL SETS HAVE COME BACK IN
 ONCE AGAIN WITH ALL OLD/VOIDED SHEETS
 STILL IN SETS.
 THIS MUST BE DONE BEFORE SUBMITTING
 PLANS FOR NEXT REVIEW.
 PLEASE BEAR IN MIND, ONE COMPLETE SET OF
 PLANS ARE BEING RETAINED BY THIS OFFICE.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-10 Cont ID  
Sent By dpalmer Date 2005-08-10 Time 16:38 Rev Time 1.50
Received By dpalmer Date 2005-08-10 Time 15:25 Sent To  
Notes
2005-08-10 00:00:00********** UNSAT 2ND REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND PLEASE SEE SOME NEW NOTES DUE
 TO CHANGES IN PLANS.
  
  
 1)NOTE: PLEASE SEE ALL PLANS SHALL
 CONTAIN TITLE BLOCKS FOR ARCHITECT(S),
 ENGINEER(S) INTERIOR DEISGNER ALONG WITH
 ALL FIRM'S.
 PLEASE SEE MISSING LICENSE INFORMATION
 REQUIRED PER FAC 61G1-16.004, FS
 481.219.
 PLEASE SEECONSULTING ENGINEER OF
 RECORD HAS NOW BEEN REMOVED FROM TITLE
 BLOCK?
 PLEASE SEE FS 471.025, THE ENGINEER OF
 RECORD SHALL SIGN, DATE AND SEAL ALL
 PLANS HE IS RESPONSIBLE FOR. NO OTHER
 PERSON MAY SIGN AND SEAL ANOTHER'S WORK.
 FS 481,471
  
 PLEASE SEE PREVIOUS NOTE MENTIONED, THE
 ABOVE REQUIREMENTS ARE REQUIRED FOR ALL
 TITLE BLOCKS AND FOR ALL TRADES WHETHER
 OR NOT COMMENT IS MADE BY ANY OTHER
 REVIEWER(S).
  
 PLEASE SEE ONE SET OF ELECTRICAL PLANS
 HAVE NOW BEEN RETAINED FOR FILE FOR ANY
 FUTURE REFERENCE.
  
 2)NOTE: PLEASE SEE PLANS HAVE NOW COME
 BACK WITH OUT ANY OF THE ELECTRICAL
 PLANS SIGNED, DATED OR SEALED?
 FS 481.221,471.025
  
 3)NOTE: PLEASE PROVIDE A SIGNED, DATED
 AND SEALED NOTORIZED LETTER FOR LEGAL
 SIGNATURE VERIFICATION OF ARCHITECT.
 OTHER SHEETS APPEAR TO BE SIGNED WITH
 INITIALS, IF INDEED THIS IS THE LEGAL
 SIGNATURE, PLEASE PROVIDE LETTER AS
 STATED ABOVE. PLEASE BE SURE LETTER IS
 PROPERLY NOTORIZED AS REQUIRED UNDER FS
 117.
  
 4)NOTE: PLEASE SHOW LOCATION OF EXISTING
 SERVICE ON "SERVICE POWER SITE PLAN".
 PLEASE SEE GROUPING OF MAINS WILL BE
 REQUIRED 230.72.
  
 5)NOTE: PLEASE CORRELATE RISER, LEGEND
 FOR RISER AND PLANS.
 PLEASE SEE FEEDERS FOR 400A PANEL "A".
 215.5
  
 6)NOTE": PLEASE CORRELATE PANELS, LEGEND
 FOR RISER AND RISER.
 PLEASE SEE PANEL "B". 100A, 125A ??
 215.5
  
 7)NOTE: PLEASE CORRELATE AWG SHOWN FOR
 SMAE SUB FEED TO PANEL "B". #2, #1?
 215.5
  
 8)NOTE: PLEASE SEE SPECS/MANUFACTURE
 SHEETS FOR ALL TANNING BEDS/ EQUIPMENT
 PROPOSED WAS NOT SUBMITTED FOR REVIEW OF
 THE LISTINGS REQUIRED PER NEC 110.3B,
 ALL LISTINGS MUST BE BY A NRTL.
  
 9)NOTE: PLEASE INDICATE NEW OR EXISTING
 SIGN CIRCUIT. 600.5
  
 10)NOTE: PLEASE SEE 250.50, PLEASE SHOW
 COLD WATER PIPE PART OF GROUNDING
 ELECTRODE SYSTEM. (IF METAL) RISER SHOWS
 A CONNECTION, HOWEVER THIS IS NOT CLEAR
 OR LABELED AS TO WHAT CONNECTION THIS
 MAY BE.
  
 11)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO THE DESIGN
 PROFESSIONAL. PLEASE SEE THIS IS A
 NOTICE GIVEN AT THIS TIME ONLY.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STMAPING. ONE SET OF ALL OLD/VOIDED
 SHEET SHALL BE SUBMNITTED FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-19 Cont ID  
Sent By dpalmer Date 2005-05-19 Time 14:01 Rev Time 1.75
Received By dpalmer Date 2005-05-19 Time 13:45 Sent To I
Notes
2005-05-19 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED FOR ARCHITECTUAL
 AND ENGINEERING FIRMS. FAC 61G1-16.004,
 FAC 61G15-23.002, FS 471.023, AND FS
 481.219.
 PLEASE SEE CERTIFICATE OF AUTHORIZATION
 #'S ARE REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
 PLEASE SEE THIS IS ALSO REQUIRED FOR ID
 PLANS AS THEY ALSO FALL UNDER SAME FS
 AND FAC'S.
  
 2)NOTE: PLEASE SEE PLANS CONTAINING
 TITLE BLOCK FOR ENGINEER OF DESIGN,
 SHALL BE SIGNED, DATED AND SEALEDFS
 471.025
  
 3)NOTE: PLEASE ALSO SEE THE ABOVE
 REFERENCED STATUES AND ADMINISTRATIVE
 CODES WHICH REQUIRES THE SEAL TO BE
 RAISED, CLEAR AND VISABLE WITH ALL
 INFORMAITON REQUIRED ON SAID SEAL.
 PLEASE SEE SIGNATURE MUST ALSO BE LEGAL
 SIGNATURE.
  
 4)NOTE: PLEASE CORRELATE RISER, PLANS
 AND RISER LEGEND FOR SIZE OF A/C DISC
 AND OCP.
 125A?100A?
 215.5
  
 5)NOTE: PLEASE SEE 230.2 FOR ADDITIONAL
 SERVICES PERMITTED. PLEASE SEE NEW
 PROPOSED SERVICE DOES NOT SEEM MEET
 REQUIREMENTS OF 230.2. PLEASE PROVIDE
 MORE INFORMATION FOR PROPOSED NEW
 SERVICE FROM FPL. PLEASE SEE THIS WILL
 REQUIRED WRITTEN PERMISSION BY THE AHJ
 AND FPL.
  
 6)NOTE: PLEASE CLARIFY WASHER/DRYER LOAD
 AND CIRCUIT SIZE. ARE THESE BOTH GAS?
  
 7)NOTE: PLEASE SEE CONDUCTORS NOTED FOR
 400A MAIN/PANEL ECT.
 DOES NOT MEET 240.4,310.16 ETC.
  
 8)NOTE: PLEASE CLARIFY EQUIPMENT GROUNDI
 MEANS BETWEEN ALL PANEL/ EQUIPMENT.
 PER 250.110,250.24,250.122 ETC.
  
 9)NOTE: PLEASE SUBMIT MANUFACTURE SPEC
 SHEETS FOR TANNING EQUIPMENT SHOWING
 LISTINGS BY A NRTL.
 110.21
  
 PLEASE BE AWARE OF POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-10-05 Cont ID  
Sent By mwennerg Date 2005-10-05 Time 13:32 Rev Time 0.00
Received By mwennerg Date 2005-10-05 Time 13:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-18 Cont ID  
Sent By mwennerg Date 2005-08-18 Time 10:52 Rev Time 0.00
Received By mwennerg Date 2005-08-18 Time 10:52 Sent To  
Notes
2005-08-18 00:00:00******PROVISO******
  
 PLEASE SEE OTHER REVIEW COMMENTS
 REGARDING FS AND FAC REQUIREMENTS NOT
 ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-06-01 Cont ID  
Sent By mwennerg Date 2005-06-01 Time 14:34 Rev Time 0.00
Received By mwennerg Date 2005-06-01 Time 14:34 Sent To  
Notes
2005-06-01 00:00:00****DENIED****
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS
 IN REGARDS TO FS AND FAC REQUIREMENTS.
  
 2) PLANS NOTE THAT THIS IS A FIRE
 SPRINKLERED BUILDING. SEPARATE SHOP
 DRAWINGS AND PERMITS ARE REQUIRED FOR
 THE FIRE SPRINKLER AND FIRE ALARM
 REMODELS IF APPLICABLE.
  
 3) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 4) 2A-10B,C RATED FIRE EXTINGUISHER(S)
 ARE REQUIRED AND SPACED NOT TO EXCEED
 75' TRAVEL DISTANCE.
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-13 Cont ID  
Sent By adarroug Date 2006-02-13 Time 16:01 Rev Time 0.00
Received By adarroug Date 2006-02-13 Time 16:01 Sent To E
Notes
2006-02-13 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 11:22 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 11:22 Sent To  
Notes
2005-10-03 00:00:00TO "COMM" BD#31
2005-09-23 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-02 Cont ID  
Sent By adarroug Date 2005-09-02 Time 13:46 Rev Time 0.00
Received By adarroug Date 2005-09-02 Time 13:45 Sent To  
Notes
2005-09-02 00:00:00TO "COMM" BD#49

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 10:58 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 10:58 Sent To  
Notes
2005-08-01 00:00:00TO "COMM" BD#27
2005-07-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-28 Cont ID  
Sent By dpalmer Date 2005-06-20 Time 10:58 Rev Time 0.00
Received By adarroug Date 2005-05-06 Time 11:01 Sent To  
Notes
2005-05-20 00:00:00TO "COMM" BD#46
2005-05-09 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-02-09 Cont ID  
Sent By hmoser Date 2006-02-09 Time 09:17 Rev Time 0.00
Received By hmoser Date 2006-02-09 Time 08:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-10-12 Cont ID  
Sent By pkrauss Date 2005-10-12 Time 09:24 Rev Time 0.55
Received By pkrauss Date 2005-10-12 Time 09:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-16 Cont ID  
Sent By pkrauss Date 2005-08-16 Time 15:28 Rev Time 0.55
Received By pkrauss Date 2005-08-16 Time 15:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-06-20 Cont ID  
Sent By hmoser Date 2005-06-20 Time 13:25 Rev Time 0.00
Received By hmoser Date 2005-06-20 Time 13:08 Sent To  
Notes
2005-06-20 00:00:00PLAN DENIED
 PLEASE PROVIDE DUCT SIZES FOR VAV
 NUMBERS ZD-5,ZD-6,ZD-7, AND ZD-8.
 PLAN REVIEW BY HAROLD MOSER 561-80506732

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-10-03 Cont ID  
Sent By pschmitz Date 2005-10-03 Time 12:46 Rev Time 0.00
Received By pschmitz Date 2005-10-03 Time 12:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-27 Cont ID  
Sent By pschmitz Date 2005-08-27 Time 13:21 Rev Time 0.00
Received By pschmitz Date 2005-08-27 Time 13:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-16 Cont ID  
Sent By kstevens Date 2005-06-16 Time 18:46 Rev Time 1.33
Received By kstevens Date 2005-06-16 Time 18:46 Sent To  
Notes
2005-06-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL PLANS DESIGNED BY A PROFESSIONAL
 INTERIOR DESIGNER SHALL SHOW FIRM
 LICENSE NUMBER IN TITLE BLOCK OF EACH
 SHEET, DATE PREPARED FAC
 61G1-16.004(2)(4) AND FS 481.2055
 2. THE PERSONAL SIGNATURE AND THE DATE
 THE SEAL AND SIGNATURE ARE AFFIXED SHALL
 APPEAR ON EACH SHEET. FAC 61G1-16.003 &
 FS 481.2055.
 3. A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1.
 4. THE TOILET ROOM SHALL BE ACCESSIBLE.
 SHOW THE FOLLOWING FOR COMPLIANCE:
 FOR WATER CLOSET:
 A. CLEAR FLOOR SPACE 11-4.16.2
 B. GRAB BARS 11-4.16.4 (SHOW HEIGHT)
 C. FLUSH CONTROLS 11-4.16.5
 FOR LAV:
 A. HEIGHT & CLEARANCES 11-4.19.2 (SHOW
 CLEARANCE MEASURMENT)
 B. CLEAR FLOOR SPACE 11-4.19.3
 C. EXPOSED PIPES & SURFACES 11-4.19.4
 D. FAUCETS 11-4.19.5
 5. THERE HAVE BEEN TWO SHEETS LABELED AS
 P-1. PLEASE CLARIFY. SECTION 104.2.1.
 6. FIRST P-1 WATER RISER DIAGRAM, THE
 WATER HAMMER ARRESTOR SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201.
 - SHUT OFF VALVE REQUIRED FOR THE HOSE
 BIBB. SECTION 606.2(2).
 7. FIRST P-1 SANT. RISER DIAGRAM, THE
 WASH MACHINE SHALL HAVE A STANDPIPE AND
 THE CLEANOUT SHALL INSTALLED 4' ABOVE
 THE FLOOR. SECTIONS 708.10 & 1002.1.
 8. ENGINEER SHALL INDICATE THE
 CERTIFICATE OF AUTHORIZATION NUMBER OF
 THE ENGINEERING BUSINESS ON EACH SHEET.
 FAC 61G15-23.002(2) & FS 471.025
 9. A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL
 SHEETS. THE DATE THAT THE SIGNATURE AND
 SEAL IS AFFIXED SHALL BE ENTERED ON EACH
 SHEET. RULING BY FBPE STATES THAT
 INITIALS ARE NOT APPROVED AND THAT THE
 LEGAL SIGNATURE IS REQUIRED. FAC
 61G15-23.002(1) & FS 471.025.
 10. SEAL SHALL INPRESS ALL INFORMATION
 REQUIRED BY THE FLORIDA AMINISTRATIVE
 CODE AND THE FLORIDA STATUTES.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2005-06-13 Cont ID  
Sent By mmclean Date 2005-06-13 Time 11:28 Rev Time 0.00
Received By mmclean Date 2005-06-13 Time 11:28 Sent To  
Notes
***NONE***