Plan Review Details - Permit 05050316
Plan Review Stops For Permit 05050316
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-06-11 Cont ID  
Sent By shill Date 2005-06-11 Time 19:13 Rev Time 0.50
Received By shill Date 2005-06-11 Time 19:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-07-26 Cont ID  
Sent By   Date 2005-07-26 Time   Rev Time 0.00
Received By dpalmer Date 2005-07-26 Time 07:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-18 Cont ID  
Sent By dpalmer Date 2005-05-18 Time 17:20 Rev Time 0.30
Received By dpalmer Date 2005-05-18 Time 17:17 Sent To I
Notes
2005-05-18 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS.
 PLEASE SEE RISER SHOWS A PANEL "L101",
 HOWEVER PANEL SCHEDULE SHOWS THIS? AS
 "LB101". THIS IS ALSO SHOWN AS 277/480V
 , HOWEVER THIS PANEL SEEMS TO BE ON THE
 LOAD SIDE OF A TRANSFORMER.
 PLEASE ALSO SEE PANEL "105" IS SHOWN AS
 120/208V WHICH IS SHOWN BEING FED FROM
 THE A 277/480V PANEL.
 PLEASE SEE PANEL "LB101"? ALSO SHOWS AN
 ADDITIONAL PANEL , YET THIS IS NOT ON
 RISER?
 PLEASE SEE NOTE AT PANEL ALSO INDICATES
 A PANEL "LB105"???
 PLEASE ALSO SEE PLANS AND PANELS SHOWN.
 PLEASE CORRELATE ALL OF THE ABOVE.
  
 2)NOTE: PLEASE PROVIDE ADDTIONAL
 INFORMATION ON LOAD OF EXISITNG SERVICE
 WITH ADDED LOADS PER NEC
 220.10,220.11,220.13 ETC ALL CONTINUOUS
 LOADS AT 125%215.3,230.42 ETC.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS WHICHMAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-06-01 Cont ID  
Sent By mwennerg Date 2005-06-01 Time 15:46 Rev Time 0.00
Received By mwennerg Date 2005-06-01 Time 15:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-14 Cont ID  
Sent By adarroug Date 2005-09-14 Time 14:38 Rev Time 0.00
Received By adarroug Date 2005-09-14 Time 14:38 Sent To M
Notes
2005-09-14 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-21 Cont ID  
Sent By adarroug Date 2005-07-21 Time 13:28 Rev Time 0.00
Received By adarroug Date 2005-07-21 Time 13:28 Sent To E
Notes
2005-07-21 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2005-06-29 Time   Rev Time 0.00
Received By adarroug Date 2005-05-06 Time 12:47 Sent To  
Notes
2005-05-20 00:00:00TO "COMM" BD#64
2005-05-06 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-28 Cont ID  
Sent By tgordon Date 2005-09-21 Time 10:50 Rev Time 0.45
Received By tgordon Date 2005-09-28 Time 14:01 Sent To  
Notes
2005-09-21 00:00:00*** PROVISO ***
 1) FIRE DAMPER REMOVED FROM 1 HR. RATED
 WALL, AIR DUCT MUST COMPLY WITH 2001
 FBC/M 607.1.3 EXCEPTIONS.
 2) NO RETURN AIR IN COPY/BRAKE ROOM. SEE
 2001 FBC/M 601.4 .
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-06-29 Cont ID  
Sent By hmoser Date 2005-06-29 Time 15:02 Rev Time 0.00
Received By hmoser Date 2005-06-29 Time 14:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-06-20 Cont ID  
Sent By kstevens Date 2005-06-20 Time 07:03 Rev Time 0.75
Received By kstevens Date 2005-06-20 Time 07:03 Sent To  
Notes
***NONE***