Plan Review Details - Permit 05050315
Plan Review Stops For Permit 05050315
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-09 Cont ID  
Sent By shill Date 2005-09-06 Time 11:40 Rev Time 0.00
Received By shill Date 2005-09-21 Time 16:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-07-24 Cont ID  
Sent By shill Date 2005-07-24 Time 00:03 Rev Time 0.50
Received By shill Date 2005-07-24 Time 00:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-09 Cont ID  
Sent By shill Date 2005-06-09 Time 06:43 Rev Time 3.00
Received By shill Date 2005-06-07 Time 07:57 Sent To  
Notes
2005-06-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)DECLARE AN OCCUPANCY FBC CHAPTER 4
 AND CLARIFY SYSTEMS USED.PLEASE SEE
 CHAPTER 2, DEFINITIONS, DRY CLEANING
 SYSTEMS, FBC305,FBC407.17.IF THE
 BUSINESS PORTION IS A DIFFERENT
 OCCUPANCY THAN THE DRY CLEANING, SHOW
 REQUIRED SEPARATION FBC TABLE 704.1.
 EXITS ARE TO COMPLY WITH FBC1004.
  
 3.)PLEASE EXPLAIN WHY THERE IS A 2 HR
 SEPARATION BETWEEN THE BOILER ROOM AND
 THE TENANT SPACE, BUT APPARENTLY ONLY A
 1 HR BETWEEN THE BOILER ROOM AND THE
 ADJACENT TENANT.
  
 4.)2-A1 DOES NOT SHOW A FIRE RATING
 FOR THE TENANT SEPARATION WALL.SEE
 FBC704.3 AND CLARIFY.
  
 5.)FBC1012.1.4, THE REST ROOM DOOR
 BLOCKS THE PATH OF EGRESS.
  
 6.)THE ENGINEER?S TITLE BLOCK IS TO BE
 IN COMPLIANCE WITH FAC61G15-23.002.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 13:30 Rev Time 0.30
Received By dpalmer Date 2005-09-03 Time 13:29 Sent To  
Notes
2005-09-03 00:00:00ELECTRICAL PLANS STAMPED, OK.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-07-26 Cont ID  
Sent By dpalmer Date 2005-07-26 Time 07:22 Rev Time 0.50
Received By dpalmer Date 2005-07-26 Time 07:18 Sent To  
Notes
2005-07-26 00:00:00******** UNSAT **********
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCK FOR ARCHITECTUAL FIRM.
 PLEASE SEE MISSING PRINTED NAME AND
 LICENSE # FOR ARCH.
 FAC 61G1-16.004
 PLEASE SEE THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLEASE SEE PERMIT APPLICATION
 VALUATION IS BASED ON ALL LABOR AND
 MATERIALS, EVEN IF EQUIPMENT, MATERIALS
 IS OWNER SUPPLIED.
 PLEASE PROVIDE COMPLETE SIGNED CONTRACT
 FOR ALL WORK AND MATERIALS FOR
 VERIFICATION.
 FBC 104.6.5 ADIMINISTRATIVE SECTIONS,.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABVOE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY
 QUESTIONS,PLEASE DO NOT HESITATE TO
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-18 Cont ID  
Sent By dpalmer Date 2005-05-18 Time 18:08 Rev Time 0.75
Received By dpalmer Date 2005-05-18 Time 18:08 Sent To I
Notes
2005-05-18 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 ALL REQUIRED INFROMATION TO BE PRINTED
 ON TITLE BLOCK.
 PLEASE SEE MISSING PRINTED NAME AND
 PRINTED LICENSE NUMBER OF PE.
  
 2)NOTE: PLEASE SEE SERVICE IS SHOWN AS
 120/240V HOWEVER, PANEL "A" IS SHOWN AS
 120/208V FROM A 120/240V DISCONNECT ETC?
 MISPRINT?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE THIS APPEARS TO BE AN
 EXSITING BUILDING, HOWEVER RISER IS
 SHOWN AS NEWAND FOOTER STEEL TO BE
 PART OF THE GROUNDING ELECTRODE SYSTEM.
 PLEASE SEE 250.50, IF THIS WERE ARE NEW
 BLDG THEN THIS WOULD BE REQUIRED,
 HOWEVER EXISTING BLDG DONOT REQUIRE
 ATTACHMENT TO "EXISTING" FOOTERS. PLEASE
 SEE THIS IS ONL A NOTE AND FOOTER STEEL
 ATTACHMENT IS PERMITTED BUT NOT
 REQUIRED. IF SHOWN ON PLANS, THEN IT
 WILL BE REQUIRED.
  
 4)NOTE: PLEASE VERFIY NEW OR EXISTING
 SIGN CIRCUIT PER 600.5
  
 5)NOTE: PLEASE VERIFY NEW OR EXISTING
 RECEPTS ABOVE WINDOW/DISPLAY AREA.
 210.62, 220.12.
  
 6)NOTE: PLEASE VERIFY RECEPT(S) FOR
 ROOFTOP UNITS PER 210.63. THESE COULD
 NOT BE LOCATED ON PLANS.
  
 7)NOTE: PLEASE SEE OTHER REVIEW
 COMMENTS.
 VALUE FOR PERMIT APPLICATION IS BASED ON
 TOTAL SCOPE OF WORK. THIS IS TO INCLUDE
 ALL LABOR AND MATERIALS PER FBC 104.6.5
 EVEN IF EQUIPMENT ETC IS OWNER SUPPLIED.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFETC ELECTRICAL
 PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE SET OF OLD/VOIDED SHEETS
 SHOULD BE SEPARATE FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-09-09 Cont ID  
Sent By mwennerg Date 2005-09-09 Time 15:06 Rev Time 0.00
Received By mwennerg Date 2005-09-09 Time 15:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-15 Cont ID  
Sent By mwennerg Date 2005-08-15 Time 14:01 Rev Time 0.00
Received By mwennerg Date 2005-08-15 Time 14:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-06-02 Cont ID  
Sent By mwennerg Date 2005-06-02 Time 10:50 Rev Time 0.00
Received By mwennerg Date 2005-06-02 Time 10:50 Sent To  
Notes
2005-06-02 00:00:00****DENIED****
  
 1) PLEASE ILLUSTRATE THE FIRE RATING OF
 THE BOILER ROOM DOOR IN HOURS. IE 1 1/2
 HRS OR 90 MINUTES ETC.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED TO BE MOUNTED AT A TRAVEL
 DISTANCE NOT TO EXCEED 75'.
  
 3) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE ALARM AND FIRE
 SPRINKLER REMODELS IF APPLICABLE.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 835-2951 OR 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-30 Cont ID  
Sent By adarroug Date 2005-08-30 Time 13:37 Rev Time 0.00
Received By adarroug Date 2005-08-30 Time 13:37 Sent To  
Notes
2005-08-30 00:00:00TO "COMM" BD#21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-20 Cont ID  
Sent By adarroug Date 2005-07-20 Time 14:20 Rev Time 0.00
Received By adarroug Date 2005-07-20 Time 14:20 Sent To  
Notes
2005-07-20 00:00:00TO "COMM" BD#57

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-16 Cont ID  
Sent By kstevens Date 2005-06-16 Time 16:41 Rev Time 0.00
Received By kstevens Date 2005-05-09 Time 11:40 Sent To  
Notes
2005-05-20 00:00:00TO "COMM" BD#28
2005-05-09 00:00:00IN INCOMING AWAITING SPACE ON "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-09-20 Cont ID  
Sent By pkrauss Date 2005-09-20 Time 15:06 Rev Time 0.50
Received By pkrauss Date 2005-09-20 Time 15:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-07-27 Cont ID  
Sent By pkrauss Date 2005-07-26 Time 20:38 Rev Time 0.55
Received By pkrauss Date 2005-07-26 Time 20:18 Sent To  
Notes
2005-07-26 00:00:00DENIED:
 MECHANICAL CONTRACTOR INDICATED WITH
 PERMIT APPLICATION.PLAN SHEET A-5
 DETAIL FOR THE BOILER STACK & WATER
 HEATER VENTSHALL COMPLY WITH 2001
 FBC(M)804.3.5 #2.
  
 SEE ALSO COMMENT #1 & 2 BY DEWEY PALMER,
 ELECTRICAL PLANS EXAMINER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date 2005-06-16 Cont ID  
Sent By hmoser Date 2005-06-16 Time 16:44 Rev Time 0.00
Received By hmoser Date 2005-06-16 Time 16:44 Sent To  
Notes
2005-06-06 00:00:00PLAN DENIED
 PLESE SUBMET THE MANUFACTURERS
 INSULLATION INSTRUCTIONS FOR THE BOILER.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-09-21 Cont ID  
Sent By kstevens Date 2005-09-21 Time 16:56 Rev Time 2.33
Received By kstevens Date 2005-09-21 Time 16:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-08-22 Cont ID  
Sent By kstevens Date 2005-08-22 Time 08:47 Rev Time 1.80
Received By kstevens Date 2005-08-22 Time 08:47 Sent To  
Notes
2005-08-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEW
 3. SHT A-3 WATER HAMMER ARRESTORS SHALL
 BE LOCATED IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 5. THE FOLLOWING INFORMATION IS REQUIRED
 FOR PERMIT APPLICATION:
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. - NO
 MANUF. SHEETS FOR WATER HEATER
 SUBMITTED. - MANUF. SHEET FOR BOILER
 INDICATE 1,046,000 BTU, BUT ISOMETRIC
 INDICATES 840,000 BTU. PLEASE CLARIFY.
 **************NEW COMMENTS**************
 1B. SHT A-3 WATER RISER DIAGRAM SHOWS A
 3/4" COLD WATER LINE TO THE AIR
 COMPRESSOR, BUT NO CONNECTION TO AIR
 COMPRESSOR IS SHOWN ON THE MANUF.
 SPECIFICATION SHEET. PLEASE CLARIFY WHAT
 THE WATER LINE TO THE COMPRESSOR IS FOR.
 IF CONNECTED TO THE COMPRESSOR, BACKFLOW
 PROTECTION IS REQUIRED. SECTION 104.2.1.
 2B. SHT A-3 PIPE SIZING ON THE GAS RISER
 DIAGRAM IS NOT CORRECT PER TABLE 402(2).
 SEE RED LINE CORRECTIONS ON ONE SET OF
 PLANS.
 3B. SEE COMMENT #1 OF THE ELECTRICAL
 PLAN REVIEW CONCERNING THE TITLE BLOCK
 OF THE ARCHITECT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-06-16 Cont ID  
Sent By kstevens Date 2005-06-16 Time 15:58 Rev Time 2.24
Received By kstevens Date 2005-06-16 Time 15:58 Sent To  
Notes
2005-06-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS A-2, A-3, A-4 ENGINEER SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS AND
 LICENSE NUMBER ON EACH SHEET. NAME AND
 LICENSE NUMBER NOT SHOWN ON TITLE BLOCK.
 FAC 61G15-23.002(2) & FS 471.025.
 2. SHT A-2 NOTES INDICATE FUTURE
 FIXTURES WITH SAFE WASTE TO FLOOR SINK.
 PLEASE CLARIFY. SAFE WASTE NOT APPROVED.
 INDICATE IF INDIRECT WASTE W/AIR GAP
 INTENDED.
 3. SHT A-2 PLUMBING NOTES: AIR CHAMBERS
 ARE NOT APPROVED. DELETE NOTE. WATER
 HAMMER ARRESTORS REQUIRED AT QUICK
 CLOSING VALVES TO BE LOCATED NEAR THE
 FIXTURE IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING AS SHOWN. (REQD. AT W/M HOT
 & COLD). PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS.
 4. SHT A-2 WATER RISER DIAGRAM. WATER
 LINES TO THE HOSE BIBBS NOT SHOWN.
 SECTION 104.3.1.1. - SHOW ALL WATER
 PIPING ON RISER DIAGRAM.
 5. THE FOLLOWING INFORMATION IS REQUIRED
 FOR PERMIT APPLICATION:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. NOT ALL LENGTHS SHOWN.
 SEE LINE FROM REGULATOR TO FIRST RISER.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]