Plan Review Details - Permit 05050245
Plan Review Stops For Permit 05050245
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-07-14 Cont ID  
Sent By adarroug Date 2005-07-14 Time 13:53 Rev Time 0.00
Received By adarroug Date 2005-07-14 Time 13:53 Sent To M
Notes
2005-07-14 00:00:00TO "PKRAUSS" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-06 Cont ID  
Sent By adarroug Date 2005-05-06 Time 14:18 Rev Time 0.00
Received By adarroug Date 2005-05-06 Time 14:18 Sent To M
Notes
2005-05-06 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-07-21 Cont ID  
Sent By prafter Date 2005-07-21 Time 12:08 Rev Time 0.50
Received By prafter Date 2005-07-21 Time 12:08 Sent To  
Notes
2005-07-21 00:00:00MECH. PLAN RESUB.
  
 PROVISO:1. PROVIDE FOR AUX. DRAIN
 PAN UNDER A.H.U. W/ PROTECTION.
 2003 FBC/M 307.2.3 .
  
 2. MECH. INSPECTOR TO DETURMAN IF R/A
 OUT OF BR/S IS POSSABLE.
 2003 FBC/M 601.4 .
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-05-17 Cont ID  
Sent By pkrauss Date 2005-05-17 Time 06:32 Rev Time 0.35
Received By pkrauss Date 2005-05-17 Time 06:31 Sent To  
Notes
2005-05-17 00:00:00DENIED:
 INSUFFICIENT INFORMATION FOR REVIEW.
 PLEASE PROVIDE THE FOLLOWING:
  
 1. PERMIT APPLICATION INDICATES NEW
 DUCTWORK.PROVIDE PLANS INDICATE NEW
 DUCT, MATERIAL, SIZE AND LAYOUT.
  
 2.INDICATE IF A/C IS NEW SYSTEM AND
 NOT A REPLACEMENT.PROVIDE A COMPLETED
 FORM 600C OR ENERGY AND MANUAL J
 CALCULATIONS AS REQUIRED PER 2001 FBC
 CHAPTER 13 SUB CHAPTER 6.
  
 3.INDICATE LOCATION OF AHU AND THE
 CONDENSER UNIT.PROVIDE LINE SIZE AND
 MATERIAL FOR THE CONDENSATE, LIQUID AND
 SUCTION LINE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719