Review Stop AD ADDRESSING
Rev No 1 Status N Date 2005-05-05 Cont ID  
Sent By ptjomsto Date 2005-05-05 Time 13:28 Rev Time 0.00
Received By btrobaug Date 2005-05-12 Time 12:47 Sent To  
Notes
2005-05-05 00:00:00EXT REQUIRED FOR 640 BELVEDERE RD

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-05-18 Cont ID  
Sent By btrobaug Date 2005-05-18 Time 18:10 Rev Time 0.25
Received By btrobaug Date 2005-05-18 Time 18:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-12 Cont ID  
Sent By btrobaug Date 2005-05-12 Time 12:57 Rev Time 0.50
Received By btrobaug Date 2005-05-12 Time 12:47 Sent To  
Notes
2005-05-12 00:00:00 
 PLEASE SUBMIT PLANS SHOWING LOCATIONS OF
 WORK BEING DONE AND ADDED DEVICES. ALSO
 INDICATE PANEL DESIGNATION AND CIRCUIT
 NUMBERS FOR NEW DEVICES.
  
 CHECK TO SEE THE EMERGENCY LIGHTS ARE ON
 THE LOCAL CIRCUIT AND COMPLY WITH
 700.12(E). PLEASE INDICATE THOSE CIRCUIT
 NUMBERS ON THE PLAN FOR INSPECTOR TO
 REFERENCE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 PLEASE PRINT NAME AND SIGN PLANS PER
 104.2.1 FBC IF DRAWN BY THE CONTRACTOR.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-18 Cont ID  
Sent By adarroug Date 2005-05-18 Time 14:41 Rev Time 0.00
Received By adarroug Date 2005-05-18 Time 14:41 Sent To E
Notes
2005-05-18 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-05-06 Cont ID  
Sent By adarroug Date 2005-05-06 Time 13:55 Rev Time 0.00
Received By adarroug Date 2005-05-06 Time 13:55 Sent To E
Notes
2005-05-06 00:00:00TO "E" BOX