Plan Review Details - Permit 05050204
Plan Review Stops For Permit 05050204
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-01-13 Cont ID  
Sent By rmcdouga Date 2006-01-13 Time 08:10 Rev Time 0.00
Received By rmcdouga Date 2006-01-13 Time 07:26 Sent To  
Notes
2006-01-13 00:00:00REVISED SITE PLAN/ CHANGED LOCATION OF
 STRUCTURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-11-14 Cont ID  
Sent By rmcdouga Date 2005-11-14 Time 08:07 Rev Time 0.00
Received By rmcdouga Date 2005-11-14 Time 07:15 Sent To  
Notes
2005-11-14 00:00:00BUILDING PROVISO
  
 INSUFFICENT INFORMATION SUBMITTED FOR
 STORM PANEL REVIEW & KEY PLAN DOES NOT
 MATCH THE ARCHITECTURAL FLOOR PLANS FOR
 NUMBER OF OPENINGS ON LEFT SIDE.
  
 A SEPARATE PERMIT AND FEES WILL BE
 REQUIRED FOR THE STORM PANELS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-10 Cont ID  
Sent By rmcdouga Date 2005-08-10 Time 10:36 Rev Time 0.00
Received By rmcdouga Date 2005-08-10 Time 10:36 Sent To  
Notes
2005-08-10 00:00:00DENIED
  
 1) THE LOCATION OF THE STEEL HEADER
 SHOWN IN THE DETAIL ON THE 8-1/2 X 11
 SHEET IS NOT SPECIFIED ON THE PLANS.
  
 2) THE STEEL HEADER DETAIL ON THE 8-1/2
 X 11 SHEET DOES NOT HAVE THE REQUIRED
 MINIMUM INFORMATION. THE PROJECT IS NOT
 ADEQUATELY IDENTIFIED. THE FIRM LICENSE
 NUMBER IS REQUIRED. THE FIRM ADDRESS IS
 REQUIRED. THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IS REQUIRED. SEE
 FAC 61G-16.004.
  
 3) A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE STORM PANELS UNLESS COMPLETE
 PRODUCT APPROVALS, INSTALLATION SCHEDULE
 AND KEY PLAN IS SUBMIITED AT TIME OF
 PERMIT.
  
 4)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-06-02 Cont ID  
Sent By rmcdouga Date 2005-06-02 Time 11:00 Rev Time 0.00
Received By rmcdouga Date 2005-06-02 Time 06:59 Sent To  
Notes
2005-06-02 00:00:00DENIED
  
 1) THE 2650 CASEMENT WINDOW IN BEDROOM
 #2 IS REQUIRED TO COMPLY WITH EMERGENCY
 EGRESS CLEAR OPENING SIZE. SEE FBC
 1005.4
  
 2) THE ANCHOR SCHEDULE ON A6 SPECIFIES
 USP THD210 HANGERS USING TAPCON
 FASTENERS. THESE CONNECTORS ARE NOT
 DESIGNED OR TESTED WITH THESE FASTENERS.
 PLEASE SPECIFY AN APPROPRIATE MASONRY
 HANGER.
  
 3) THE CONDITIONED FLOOR AREA LISTED ON
 THE ENERGY CALC. FORMS DOES NOT MATCH
 THE A/C AREA SPECIFIED ON THE PLANS.
 PLEASE CORRECT.
  
 4) THE GLASS BLOCK IN THE MASTER BATH
 ARE IN HAZARDOUS LOCATIONS AND AND ARE
 REQUIRED TO HAVE A MINIMUM UNIFORM FACE
 THICKNESS OF .25 INCH PER FBC 2405.2.2.
  
 5) THE 9' HIGH FIXED GLASS WINDOWS IN
 THE LIVING ROOM EXCEED THE MAXIMUM
 HEIGHT SPECIFIED ON THE PRODUCT
 APPROVAL.
  
 6) THE 12' WIDE TRANSOM WINDOW EXCEEDS
 THE MAXIMUM ALLOWED BY THE PRODUCT
 APPROVAL.
  
 7) THE MULLION BETWEEN THE 12' SLIDING
 GLASS DOOR AND THE TRANSOM WINDOW
 EXCEEDS THE MAXIMUM DESIGN PRESSURE
 SPECIFIED IN THE PRODUCT APPROVAL.
  
 8) SUBMIT STATE PRODUCT APPROVAL FOR THE
 12' SLIDING GLASS DOOR.
  
 9) SUBMIT THE EVALUATION REPORT FOR THE
 ROBICO SHUTTERS.
  
 10) SUBMIT (2) COPIES OF A KEY PLAN AND
 INSTALLATION SCHEDULE FOR THE STORM
 PANELS. SPECIFY THE MOUNT TYPE AND
 FASTENER TYPE AND SPACING.
  
 11) ADDITIONAL FEES ARE DUE FOR RADON
 AND INCREASED CALCULATED VALUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-06-16 Cont ID  
Sent By dpalmer Date 2006-06-16 Time 20:34 Rev Time 0.00
Received By dpalmer Date 2006-06-16 Time 20:20 Sent To PC
Notes
2006-06-16 00:00:00REDLINED, OCP FOR AHU'S TO BE VIF.
  
 45A OCP SEEMS HIGH FOR 5KW HEAT.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-06-05 Cont ID  
Sent By btrobaug Date 2006-06-05 Time 17:47 Rev Time 0.50
Received By btrobaug Date 2006-06-05 Time 17:47 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-10-09 Cont ID  
Sent By dpalmer Date 2005-10-09 Time 17:53 Rev Time 0.25
Received By dpalmer Date 2005-10-09 Time 17:46 Sent To P
Notes
2005-10-09 00:00:00REDLINED POSSIBLE CONFLICT PER 410.8 FOR
 CLOSET LTS.
 FIELD VERIFY.
 STAMPED PLANS FOR CODE COMPLIANCE
 REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-09 Cont ID  
Sent By btrobaug Date 2005-08-09 Time 07:32 Rev Time 0.50
Received By btrobaug Date 2005-08-09 Time 07:14 Sent To B
Notes
2005-08-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW. SAME COMMENTS AS PRIOR REVIEW
  
  
 1} INDICATE THE LOCATION OF PANEL "B".
  
 2} INDICATE LOCATION OF OVERCURRENT
 PROTECTION FOR PANELS "A" & "B".
  
 3} THE OCP FOR CIRCUITS 12,13 PANEL "A",
 12,13,14,15 PANEL "B" IS TOO LARGE FOR
 THE CONDUCTORS PER 210.16.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-05-17 Cont ID  
Sent By btrobaug Date 2005-05-17 Time 07:43 Rev Time 0.50
Received By btrobaug Date 2005-05-17 Time 07:40 Sent To M
Notes
2005-05-17 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE LOCATION OF PANEL "B".
  
 2} INDICATE LOCATION OF OVERCURRENT
 PROTECTION FOR PANELS "A" & "B".
  
 3} THE OCP FOR CIRCUITS 12,13 PANEL "A",
 12,13,14,15 PANEL "B" IS TOO LARGE FOR
 THE CONDUCTORS PER 210.16.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 16:12 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 16:12 Sent To E
Notes
2006-05-26 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-05-23 Cont ID  
Sent By adarroug Date 2006-05-23 Time 09:58 Rev Time 0.00
Received By adarroug Date 2006-05-23 Time 09:58 Sent To P
Notes
2006-05-23 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-01-12 Cont ID  
Sent By adarroug Date 2006-01-12 Time 12:00 Rev Time 0.00
Received By adarroug Date 2006-01-12 Time 12:00 Sent To B
Notes
2006-01-12 00:00:00TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-12-16 Cont ID  
Sent By adarroug Date 2005-12-16 Time 16:45 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 16:45 Sent To Z
Notes
2005-12-16 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-07 Cont ID  
Sent By adarroug Date 2005-10-07 Time 17:01 Rev Time 0.00
Received By adarroug Date 2005-10-07 Time 17:01 Sent To E
Notes
2005-10-07 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-05 Cont ID  
Sent By adarroug Date 2005-08-05 Time 14:36 Rev Time 0.00
Received By adarroug Date 2005-08-05 Time 14:36 Sent To E
Notes
2005-08-05 00:00:00TO "BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-05-16 Cont ID  
Sent By adarroug Date 2005-05-16 Time 08:24 Rev Time 0.00
Received By adarroug Date 2005-05-16 Time 08:24 Sent To E
Notes
2005-05-16 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-06-02 Cont ID  
Sent By rmcdouga Date 2005-06-02 Time 11:00 Rev Time 0.00
Received By rmcdouga Date 2005-05-06 Time 14:11 Sent To  
Notes
2005-05-06 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-05-18 Cont ID  
Sent By prafter Date 2005-05-18 Time 08:13 Rev Time 0.50
Received By prafter Date 2005-05-18 Time 08:13 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-10-12 Cont ID  
Sent By jleech Date 2005-10-12 Time 15:36 Rev Time 0.00
Received By jleech Date 2005-10-12 Time 15:36 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-08-10 Cont ID  
Sent By rmcdouga Date 2005-08-10 Time 12:31 Rev Time 0.00
Received By rmcdouga Date 2005-08-10 Time 12:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-05-26 Cont ID  
Sent By kstevens Date 2005-05-26 Time 07:42 Rev Time 0.50
Received By kstevens Date 2005-05-26 Time 07:42 Sent To B
Notes
2005-05-26 00:00:00PASSED/PROVISO
  
  
 WASH MACHINE SHALL NOT CONNECT TO A
 DOUBLE SANT. TEE. SECTION 706.3
 CLEANOUT SHALL BE 4' ABOVE THE FLOOR
 SECTION 708.10

Review Stop Z ZONING
Rev No 3 Status P Date 2006-01-10 Cont ID  
Sent By mmclean Date 2006-01-10 Time 14:51 Rev Time 0.00
Received By mmclean Date 2006-01-10 Time 14:51 Sent To I
Notes
2006-01-10 00:00:00PER MELISSA AT PARAMANT CORP., THE
 REVISION IS CHANGE IN THE PLACEMENT OF
 STRUCTURE ON PROPERTY AND EXTENTED
 MASTER BEDROOM.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-01-07 Cont ID  
Sent By mmclean Date 2006-01-07 Time 08:20 Rev Time 0.00
Received By mmclean Date 2006-01-07 Time 08:20 Sent To  
Notes
2006-01-07 00:00:00DENIED,
 1. NEED TO INDICATE THE CHANGES TO
 PLANS, REVISION INDICATE CLOUDS AND
 CLOUDS DOES NOT SHOW.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2005-05-13 Cont ID  
Sent By mmclean Date 2005-05-13 Time 15:36 Rev Time 0.00
Received By mmclean Date 2005-05-13 Time 15:36 Sent To I
Notes
***NONE***